BAC VTL-E Quick start guide

VTL-E Open Cooling Towers
RIGGING AND INSTALLATION INSTRUCTIONS
RVTL-Ev14EN

About rigging and installation
The BAC equipment should be rigged and installed as outlined in this bulletin.
These procedures should be thoroughly reviewed prior to the rigging and operation to acquaint all personnel with
the procedures to be followed and to assure that all necessary equipment will be available at the job site.
Be sure to have a copy of the unit certified drawing available for reference. If you do not have a copy of this drawing
or if you need additional information about this unit, contact the local BAC Balticare representative. His name and
phone number can be found on the www.BaltimoreAircoil.eu. The model type and serial number of your equipment
are indicated on the unit nameplate.
Recommended maintenance and
monitoring programme
Checks and adjustments Start-Up Weekly Monthly Quarterly Every 6
months
Annually Shutdown
Cold water basin & strainer X X
Operating level and make-up X X
Blow down X X
Sump heater package X X
Belt tension X X
Drive alignment X X
Locking collar X X
Rotation of fan(s) and pump(s) X
Motor voltage and current X X
Unusual noise and/or vibration X X
Inspections and monitoring Start-Up Weekly Monthly Quarterly Every 6
months
Annually Shutdown
General condition X X
Heat transfer section X X
Drift eliminators X X
Water distribution X X
Fan shaft X X
Fan motor X X
Electric water level control package (optional) X X
TAB test (dip slides) X X
Circulating water quality X X
System overview X X
Record keeping as per event
Lubrication Start-Up Weekly Monthly Quarterly Every 6
months
Annually Shutdown
Fan shaft bearings X X X
Motor bearings* X X
Adjustable motor base X X X
* only for motors with grease fittings with typical frame size > 200L (>30 KW)
W W W . B A L T I M O R E A I R C O I L . E U
2

Cleaning procedures Start-Up Weekly Monthly Quarterly Every 6
months
Annually Shutdown
Mechanical cleaning X X X
Disinfection** (X) (X) (X)
Drain basin X
** depends on applied code of practice
Notes
1. Water treatment and auxiliary equipment integrated in the cooling system may require additions to the table
above. Contact suppliers for recommended actions and their required frequency.
2. Recommended service intervals are for typical installations. Different environmental conditions may dictate
more frequent servicing.
3. When operating in ambient temperatures below freezing, the unit should be inspected more frequently (see
Cold weather operations in the appropriate Operating and Maintenance Instructions).
4. For units with belt drive, tension on new belts must be readjusted after the first 24 hours of operation and
monthly thereafter.
W W W . B A L T I M O R E A I R C O I L . E U
3

Table of contents
RIGGING AND INSTALLATION INSTRUCTIONS
1 General information 5
About engineering and application practices 5
Shipping 5
Inspection before rigging 5
Unit weights 7
Anchoring 7
Leveling 7
Electrical connections 8
Connecting pipework 8
Freeze protection 8
Bleed Line Installation 8
Safety Precautions 8
Non-walking surfaces 10
Modifications by others 10
Warranty 10
2 Rigging 11
General notes 11
Rigging method discharge accessories 13
3 Optional accessories assembly 14
General Information 14
Clean out port 16
4 Inspection prior to start-up 17
General 17
5 Further Assistance & Information 18
Assistance 18
More information 18
W W W . B A L T I M O R E A I R C O I L . E U
4

1 General information
1 General information W W W . B A L T I M O R E A I R C O I L . E U
5
GENERAL INFORMATION
About engineering and application practices
This bulletin only refers to the assembly of the unit. To ensure a proper operation, a correct integration of the unit in
the overall installation is mandatory. For good engineering and application practices on layout, levelling,
connecting pipework, etc., please refer to our website:
http://www.baltimoreaircoil.eu/knowledge-center/application-information.
Shipping
BAC cooling equipment is factory assembled to assure uniform quality and minimum field assembly.
The models are shipped in one single section.
CAUTION
Do not cover units with PVC eliminators or fill with a plastic tarpaulin.
Temperature increase due to sun radiation could deform the fill or eliminators.
Inspection before rigging
When the unit is delivered to the job site, it should be checked thoroughly to ensure all required items have been
received and are free of any shipping damage prior to signing the bill of lading.
The following parts should be inspected:
• Sheaves and belts
• Bearings
• Bearing supports
• Fan motors
• Fan wheels and shafts
• Wet deck surface
• Water distribution system
• Strainers
• Float valve assembly
• Eliminators
• Interior surfaces
• Exterior surfaces
• Miscellaneous items
VTL-E
1

An envelope with check-list is stored in a wooden no nail crate or a plastic container which is placed in the lower
section. For safety reasons, access doors / panels may be sealed with bolts. The following table specifies which
wrench is required to open them.
Wrench to open access door
17 mm
Required wrench to open access door
The wooden no nail crate / plastic container also contains miscellaneous parts such as gasket, hardware and
accessory items.
At temperatures below -10°C the butyl sealer tape might loose it's flexibility. We recommend to store the sealer
tape in a heated room before using it during rigging at freezing temperatures.
CAUTION
Be sure to remove all miscellaneous items from the pan before the unit is assembled.
The hardware is packed in a plastic container and located inside the lower section of the unit.
If a plastic container is used; it will be fixed to the make-up valve using a cable tie.
Hardware location
W W W . B A L T I M O R E A I R C O I L . E U
6

If heaters are shipped loose, they will be wrapped in plastic and fixed to the strainer.
Heater location if shipped loose.
1. Heater
Unit weights
Before rigging any BAC equipment, the weight of each section should be verified on the unit certified drawing.
These weights are approximate and should be confirmed by weighing before lifting when available
hoisting capacity provides little margin for safety.
CAUTION
Before an actual lift is undertaken, ensure no water, snow, ice or debris has collected in the sump
or elsewhere in or on the unit. Such accumulations will add substantially to the equipment’s lifting
weight.
In the event of extended lifts or where hazards exist, the lifting devices should be used in conjunction with safety
slings placed under the unit.
Anchoring
The unit must be properly anchored in place.
Refer to the suggested support details on the certified drawing for locations of the mounting holes. Anchor bolts
must be provided by others.
Holes suitable for 20 mm bolts are provided in the bottom flange of the lower section for bolting the unit to the
support beams.
Leveling
The unit must be level for proper operation and ease of piping.
Support beams must also be level as shims should not be used between pan and support beams to level the unit.
W W W . B A L T I M O R E A I R C O I L . E U
7
1 General information
1 General information

Electrical connections
The units are delivered with a number of electrical components that need to be connected after rigging.For all
electrical components, please refer to the specific wiring diagrams in the submittal package.
Connecting pipework
All piping external to BAC cooling equipment must be supported separately.
In case the equipment is installed on vibration rails or springs, the piping must contain compensators to eliminate
vibrations carried through the external pipework.
The equipment outlet piping must be installed under the operating level of the equipment to prevent air suction and
pump cavitation.
Suction pipe sizing should be done according to good practice, which may for larger flows require larger pipe
diameters than the outlet connection. In such cases adapter pieces need to be installed.
Freeze protection
These products must be protected against damage and/or reduced effectiveness due to possible freeze-up by
mechanical and operational methods. Please contact your local BAC Balticare representative for recommended
protection alternatives.
Bleed Line Installation
On all open cooling towers, install a bleed line with valve between the system circulating pump discharge riser and
a convenient drain. Locate the bleed line in a portion of the riser piping that drains when the pump is off.
The bleed valve should always be open when the unit is in operation, unless the bleed rate is automatically
controlled by a water treatment system.
Safety Precautions
All electrical, mechanical and rotating machinery constitutes a potential hazard, particularly for those not familiar
with its design, construction and operation. Accordingly, adequate safeguards (including use of protective
enclosures where necessary) should be taken with this equipment both to safeguard the public (including minors)
from injury and to prevent damage to the equipment, its associated system and the premises.
If there is doubt about safe and proper rigging, installation, operation or maintenance procedures, contact the
equipment manufacturer or his representative for advice.
When working on operating equipment, be aware that some parts may have an elevated temperature. Any
operations on elevated level have to be executed with extra care to prevent accidents.
AUTHORIZED PERSONNEL
The operation, maintenance and repair of this equipment should be undertaken only by personnel authorized and
qualified to do so. All such personnel should be thoroughly familiar with the equipment, the associated systems
and controls and the procedures set forth in this and other relevant manuals. Proper care, personal protective
equipment, procedures and tools must be used in handling, lifting, installing, operating, maintaining and repairing
this equipment to prevent personal injury and/or property damage. Personnel must use personal protective
equipment where necessary (gloves, ear plugs, etc...)
W W W . B A L T I M O R E A I R C O I L . E U
8

MECHANICAL SAFETY
Mechanical safety of the equipment is in accordance with the requirements of the EU machinery directive.
Depending upon site conditions it also may be necessary to install items such as bottom screens, ladders, safety
cages, stairways, access platforms, handrails and toe boards for the safety and convenience of the authorized
service and maintenance personnel.
At no time this equipment should be operated without all fan screens, access panels and access doors in place.
When the equipment is operated with a variable fan speed control device, steps must be taken to avoid operating
at or near to the fan's «critical speed».
For more information consult your local BAC Balticare representative.
ELECTRICAL SAFETY
All electrical components associated with this equipment should be installed with a lockable disconnect switch
located within sight of the equipment.
In the event of multiple components, these can be installed after a single disconnect switch but multiple switches
or a combination thereof are also allowed.
No service work should be performed on or near electrical components unless adequate safety measures are
taken. These include, but are not limited to the following:
• Isolate the component electrically
• Lock the isolation switch in order to prevent unintentional restart
• Measure that no electrical voltage is present anymore
• If parts of the installation remain energized, make sure to properly demarcate these in order to avoid confusion
Fan motor terminals and connections may have residual voltage after unit shut-down. Wait five minutes after
disconnecting the voltage at all poles before opening the fan motor terminal box.
LIFTING
CAUTION
Failure to use designated lifting points can result in a dropped load causing severe injury, death
and/or property damage. Lifts must be performed by qualified riggers following BAC published
Rigging Instructions and generally accepted lifting practices. The use of supplemental safety
slings may also be required if the lift circumstances warrant its use, as determined by the rigging
contractor.
LOCATION
All cooling equipment should be located as far away as possible from occupied areas, open windows or air intakes
to buildings.
CAUTION
Each unit must be located and positioned to prevent the introduction of discharge air into the
ventilation systems of the building on which the unit is located and of adjacent buildings.
W W W . B A L T I M O R E A I R C O I L . E U
9
1 General information
1 General information

For detailed recommendations on BAC equipment layout, please see the BAC Application Handbook EU-
Edition, the BAC website www.BaltimoreAircoil.eu or contact your local BAC-Balticare Representative.
LOCAL REGULATIONS
Installation and operation of cooling equipment may be subject to local regulations, such as establishment of risk
analysis. Ensure regulatory requirements are consistently met.
Non-walking surfaces
Access to and maintenance of any component needs to be performed in accordance with all local applicable laws
and regulations. If the proper and required access means are not present, temporary structures need to be
foreseen. Under no circumstance can one use parts of the unit, that are not designed as an access mean, unless
measures can be taken to mitigate any risks that might occur from doing so.
Modifications by others
Whenever modifications or changes are made by others to the BAC equipment without written permission of BAC,
the party who has done the modification becomes responsible for all consequences of this change and BAC
declines all liability for the product.
Warranty
BAC will guarantee all products to be free from manufactured defects in materials and workmanship for a period of
24 months from the date of shipment. In the event of any such defect, BAC will repair or provide a replacement.
For more details, please refer to the Limitation of Warranties applicable to and in effect at the time of the
sale/purchase of these products. You can find these terms and conditions on the reverse side of your order
acknowledgement form and your invoice.
W W W . B A L T I M O R E A I R C O I L . E U
10

2 Rigging
2 Rigging W W W . B A L T I M O R E A I R C O I L . E U
11
RIGGING
General notes
1. If the delivery consists of separate sections, do not assemble before lifting, as the lifting devices provided are
not designed to support the weight of the entire assembly.
When the unit is installed, all metal parts created by drilling, fastening self tapping screws, grinding, welding or
other mechanical works must be removed from the unit.If they remain on the unit (typically on the double break
flanges) this could lead to corrosion and eventually coating damage.
2. Spreader bars of the full width of the section must be used between the lifting cables to prevent damage to the
section.
3. For extended lifts or where hazards exist, it is recommended to use the lifting devices in conjunction with
safety slings placed under the unit.
4. Lifting devices have been provided on all sections. The table below gives the preferred method for rigging each
section of a unit.
5. For asymmetrical load distribution shorten the slings at one end so the casing is approximately horizontal.
6. There is a difference in lifting ear and tie down buckle
1. Lifting ear: use this ear to lilft unit (rigging purpose). Do not use ear for lashing.
2. Eyebolt for lashing purpose only. Do not use for lifting the unit.
VTL-E
2

Logo for proper use of tie down buckle & lifting ear
1. Proper use for lifting ear
2. Proper use for tie down buckle/eyebolt
Rigging method units
1. Spreader bar
2. Lifting device
3. Safety slings
4. Spreader bar length
Model Unit
L & W
(mm)
Min.
"H "
(mm)
Spreader
bar
length
(mm)
Discharge
accessory
1
minimum
"H"
VTL-E-039-G to
VTL-E-079-K
3350 x 1250 3100 1250 3100
VTL-E-058-G to
VTL-E-117-M
4560 x 1250 4300 1250 4300
VTL-E-070-J to
VTL-E-137-M
5480 x 1250 5000 1250 5000
VTL-E-113-J to
VTL-E-227-O
4560 x 2400 4300 2450 4300
VTL-E-183-L to
VTL-E-272-P
5480 x 2400 5000 2450 5000
W W W . B A L T I M O R E A I R C O I L . E U
12

Rigging method and discharge accessory
1Discharge accessories can be: plume abatement coil, positive closure damper, tapered discharge hood, sound attenuation.
Rigging method discharge accessories
CAUTION
When lowering a section, ensure nothing can be trapped between the upper and lower flanges.
W W W . B A L T I M O R E A I R C O I L . E U
13
2 Rigging
2 Rigging

W W W . B A L T I M O R E A I R C O I L . E U
OPTIONAL ACCESSORIES ASSEMBLY
General Information
1. Optional discharge accessories such as tapered hoods, positive closure dampers, discharge sound
attenuators, desuperheaters, plume abatement coils and/or access plenums can be fitted.
2. Rigging method of optional accessories is indicated in the rigging tables.(see "General notes" on page11
3. If the delivery consists of separate sections, do not assemble before lifting, as the lifting devices provided are
not designed to support the weight of the entire assembly.
4. Refer to the unit certified drawing for installation sequence of optional accessories.
5. Position the unit of the supporting steel and bolt in place.
6. Remove any protective wood from the top horizontal flanges of the lower section. Wipe down the flanges to
remove dust, dirt or moisture that may have accumulated during shipment and storage.
7. Apply the 25 mm wide tape sealer around the periphery of the top flange of the unit.
This tape sealer must be centred directly over the centreline of the tapper holes and on the centreline of the end
flanges where there are no tapper holes. The sealer is to be spliced only along the flanges with tapper holes. When
it is necessary to splice sealer, mitre and press the two ends together so as to form a smooth, continuous bead.
Tape sealer is trapezoidal in shape and must be installed wide side down (see figure "Installation of tape sealer").
Do not stretch sealer tape.
8. Sealer applied to the end flanges of the unit must be continuous.
Installation of tape sealer
1. Discharge accessory
2. Unit
3. 25 mm flat tape sealer laid over punch line wide side down.
When rigging the discharge accessory one might consider to hang the discharge accessory under a small angle (1-
2°) in the crane. This way one short end can be positioned first and then the rest of the discharge accessory can be
lowered slowly.
Once the discharge accessory is put on the tape sealer,
it can not be moved any more so gentle positioning is required.
14
VTL-E
3
3 Optional accessories assembly
3 Optional accessories assembly

9. Remove the discharge accessory from the skid. Lift the discharge accessory and position it over the unit so
that the flanges of the section are about 50 mm above the unit. Dot not let the section swing and damage the
sealer.
Use at least four drift pins (see figure) in the fastening holes located on the long sides of the sections to align
the discharge accessory to the unit. To avoid incorrect alignment, refer to the below drawing for the position of
the fastening holes to be used. Use additional drift pins in the middle of the unit if required, to align long panels.
(See figure "Usage of drift pin to align the screw holes")
Make sure all holes from the discharge accessory and the unit are properly aligned before lowering the
discharge accessory completely to the unit.
Position of the fastening holes to be used.
1. Drift pin position
2. The distance between the fastening hole in which the drift pin is inserted and the corner should be at least 30cm
3. Usage of additional drift pin for long sides
4. Fastening hole
Usage of drift pin to align the screw holes
10. Using the self-tapping screws, drive screws down through the middle section and into the lower section. Start
next to lifting ear towards centre of unit. Continue to install the screws using the drift pin to align the screw
holes until all holes are filled with screws
CAUTION
Make sure coupling is installed on external piping if delivered with the dry coil.
W W W . B A L T I M O R E A I R C O I L . E U
15
3 Optional accessories assembly
3 Optional accessories assembly

Clean out port
Due to transport width limits, the cover flanges of the clean out port are mounted with flanges towards the inside
(1). On site, the cover can be placed with flanges to the outside for easy access to hardware (2).
Clean out port cover mounted for transport
Final installation of clean out port cover
W W W . B A L T I M O R E A I R C O I L . E U
16

4 Inspection prior to start-up
4 Inspection prior to start-up W W W . B A L T I M O R E A I R C O I L . E U
17
INSPECTION PRIOR TO START-UP
General
Prior to start-up, the following services, which are described in detail in the Operating and Maintenance Manual
(see table "Recommended maintenance and monitoring programme" ) must be performed.
Proper start-up procedures and scheduled periodic maintenance will prolong the life of the equipment and ensure
trouble-free performance for which the unit is designed.
VTL-E
4

W W W . B A L T I M O R E A I R C O I L . E U
FURTHER ASSISTANCE & INFORMATION
Assistance
BAC has established a specialized total care company called Balticare. The BAC Balticare offering involves all
elements required to ensure a safe and efficient operation of your evaporative cooling products.
For more details, contact your local BAC representative for further information and specific assistance at
www.BaltimoreAircoil.eu
More information
REFERENCE LITERATURE
• Eurovent 9-5 (6) Recommended Code of Practice to keep your Cooling System efficient and safe.
Eurovent/Cecomaf, 2002, 30p.
• Guide des Bonnes Pratiques, Legionella et Tours Aéroréfrigérantes. Ministères de l'Emploi et de la Solidarité,
Ministère de l'Economie des Finances et de l'Industrie, Ministère de l'Environnement, Juin 2001, 54p.
• Voorkom Legionellose. Minsterie van de Vlaamse Gemeenschap. December 2002, 77p.
• Legionnaires' Disease. The Control of Legionella Bacteria in Water Systems. Health & Safety Commission.
2000, 62p.
• Hygienische Anforderungen an raumlufttechnische Anlagen. VDI 6022.
INTERESTING WEBSITES
• www.BaltimoreAircoil.eu
• www.eurovent-certification.com
• www.ewgli.org
• www.ashrae.org
• www.uniclima.org
• www.aicvf.org
• www.hse.gov.uk
ORIGINAL DOCUMENTATION
This manual is originally made in English.Translations are provided for your convenience. In the event of
discrepancies, the English original text shall prevail over the translation.
18
VTL-E
5
5 Further Assistance & Information
5 Further Assistance & Information

W W W . B A L T I M O R E A I R C O I L . E U

W W W . B A L T I M O R E A I R C O I L . E U
Table of contents
Other BAC Desktop manuals
Popular Desktop manuals by other brands

Dell
Dell Inspiron 5720 quick start guide

Lenovo
Lenovo 3000 K100 user guide

Compaq
Compaq BL10e - HP ProLiant - 512 MB RAM introduction

Lenovo
Lenovo ThinkCentre M70e Kullanma kılavuzu

Compaq
Compaq dc7800 - Convertible Minitower PC Illustrated parts & service map

Optima
Optima WorkPro K8X supplementary guide