BAPI 900 MHz WAM Connect User manual

900 MHz
WAM Connect
Wireless Gateway
Installation and User Guide

Installation & Operating Instructions
Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI 54631 USA
Specications subject to change without notice.
rev. 02/09/21
39021_RCV_900_BACnet_2020
2 of 12
900MHz WAM Connect
Table of Contents
Mounting and Termination ...................................................................................................................................3
Overview..............................................................................................................................................................4
Customer Provided Equipment and Materials.....................................................................................................4
Placement Recommendations and Building Material Attenuation Losses ..........................................................4
Setup ............................................................................................................................................................... 5-9
Foreign Device Registry Information .................................................................................................................10
BACnet Information ......................................................................................................................................10-11
Backup or Restore Gateway Information...........................................................................................................12
Specications ....................................................................................................................................................12

Installation & Operating Instructions
Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI 54631 USA
Specications subject to change without notice.
rev. 02/09/21
39021_RCV_900_BACnet_2020
3 of 12
900MHz WAM Connect
Mounting and Termination
Remove the gateway from the box and attach the antenna. Remove the gateway mounting plate by twisting 1/4 turn
counterclockwise. Plug in the network cable. Connect the Ethernet cable into the gateway and then into the wall outlet.
Secure the mounting plate to the preferred mounting surface after shing the wires through the center wireway hole
or the wireway hole next to the antenna connection. Hold the gateway up to the plate and secure by twisting 1/4 turn
clockwise.
POWER OPTIONS:
Direct 24VAC/VDC, Power Supply Included
Power Over Ethernet (PoE) on board device
LED INDICATORS
Heartbeat: Blinks to show gateway is “alive”
Radio: Green when radio is found
LAN: Green when network is congured
Power: Green on 24V power supply / Red on PoE
WAM DESIGN - FEATURES:
Gateways discoverable via TCP/IP with USB dongle
Conguration via TCP/IP with USB dongle
Supports EDE (Engineering Data Exchange) via standardized CSV or Excel File
NETWORK:
DHCP/static IP
Class A,B,C network support
Updates available via user initiated update
NOTE: Range can vary greatly based on building materials, device positioning, interference, etc. Contact a BAPI
representative for a site consult prior to purchase.
Fig. 11: Gateway Mounting and Termination
Power LED
Radio LED
LAN LED
Heartbeat LED
Antenna
Connection
Power In
LAN Connection

Installation & Operating Instructions
Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI 54631 USA
Specications subject to change without notice.
rev. 02/09/21
39021_RCV_900_BACnet_2020
4 of 12
900MHz WAM Connect
Overview
Customer Provided Equipment and Materials
The user must provide an active local network for this gateway. The user’s Windows
7 or higher computer must have the WAM Link connected via a USB port and WAM
Design installed on their PC.
At locations where there is a secure network and foreign equipment is not allowed,
it may be necessary to provide a separate router and network switch. This decision
depends on the number of connections needed, which will allow the installer to set
up an isolated network for the gateway network connections.
Placement Recommendations and Building Material Attenuation Losses
• 275 feet line of sight (LOS) is the maximum range that can be
expected. Actual range will vary based on the environment.
• All materials that block the path of transmission between a sensor
and gateway contribute to signal loss. See chart to the right for
some common materials and expected signal loss.
• The gateway should be mounted as far away from metal
obstacles as possible to avoid RF reections or blockages.
• Mounting to drywall between studs, ceiling tiles, brick, glass or
concrete is very common. Mounting to ceiling T-Bar is common
but will aect distance due to the metal in the T-Bar and the
horizontal orientation.
BAPI recommends conducting a bench test before permanently
mounting the gateway to assure strong communication between the
gateway and sensors. Once bench testing is complete, temporarily
place the gateway and sensors in their desired locations.
Material Attenuation Loss
Brick 3.5" (89 mm) 3.5 dB
Brick 7" (178 mm) 5 dB
Brick 10.5" (276 mm) 7 dB
Concrete 4" (102 mm) 12 dB
Concrete 8" (204 mm) 23 dB
Concrete 12" (305 mm) 35 dB
Glass 0.25" (6.5 mm) 0.8 dB
Glass 0.5" (12.7 mm) 2 dB
Lumber 3" (76 mm) 2.8 dB
Masonry Block 8" (204 mm) 12 dB
Masonry Block 16" (406 mm) 17 dB
Masonry Block 24" (610 mm) 28 dB
Open Air 33' (10 m) 72.5 dB
Open Air 329' (100 m) 92.5 dB
Open Air 3290' (1000 m) 112.5 dB
Reinforced Concrete 3.5" (89 mm) 27 dB
900 MHz Wireless System
Fig. 1:
900MHz
BACnet
Gateway
Fig. 2: USB
Conguration Tool
Dongle
Multiple communication options including BACnet IP and MQTT.
Each gateway supports up to 50 sensors that can be congured remotely via the gateway.
The system uses “smart logic” to nd and secure a clean frequency channel rather than “frequency hopping”.
Easily congure wireless sensors to be presented to BACnet network via a at mode for single gateway device with
sensors as associated objects.
The BAPI wireless gateway is a device that allows for the receiving of up to 50 BAPI
900MHz wireless sensing devices and outputs that received information in one of two
formats: BACnet IP for your typical Building Automation system and MQTT for BAPI WAM
(Wireless Asset Monitoring).
The BAPI gateway can be powered from the supplied plug-in power supply or Power
over Ethernet (PoE) if your network supports that feature. The wireless network setup
application (WAM Design) lets you assign your wireless devices to the appropriate gateway
while also allowing you to note sensor names, location, settings, etc.
You will need to have a BAPI Wireless USB Dongle (WAM Link) to commission the system.
This dongle acts as a default radio module which you will need to discover the wireless
sensors that are in the factory default mode. With this tool and the application on your
computer you will be able to “hand o” the sensors to the appropriate gateway.

Installation & Operating Instructions
Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI 54631 USA
Specications subject to change without notice.
rev. 02/09/21
39021_RCV_900_BACnet_2020
5 of 12
900MHz WAM Connect
Setup
Note: BAPI’s 900 MHz System has many available features and options, so patience is key while conguring the gateway
and sensors. Please read all the steps prior to starting which will help with the process. If you have questions after reading
all the steps, call BAPI for assistance and one of our wireless tech will walk you through this process.
1. Choose a convenient location for a “bench setup” of your system prior to installing it in the nal
location.
Choose a “bench setup” location with the sensors, gateway and computer within easy reach. Remove the gateway
from the box and attach the antenna. Connect the supplied ethernet cable to the gateway and the network. Connect the
supplied power cord to the gateway and then into the wall outlet if you are not able to use PoE.
2. Download and open the BAPI WAM Design Application
Download the WAM Design from this address (Contact BAPI for link
address.) Plug WAM Link into an available USB port on your computer.
Open the Design Application. Make sure your WAM Link Dongle
displays in the pull down box of the initial screen (Fig 3). If it does not,
click the red “retry” arrows to the right of the box. The WAM Link dongle should
automatically identify itself to WAM Design software.
3. Run the WAM Design Application
Click start. A dialog box will show up asking for a password. If you wish, assign
a password to the gateway. If not, press “Yes” to continue. This will open the
Conguration Screen shown in Fig 4. The left column lists the available gateways
that are on the same network as your computer. Click on the gateway that you
plan to congure and “hand o” the sensors to.
The center column tabs show the selectable options for the gateway.
• Network: This is the network setting for your LAN should you decide to change any of them.
• Settings: This is where you can make changes to the gateway such as its name.
• WAM: This is where you select the end destination path for all MQTT settings.
• Sensors: This is where you “hand
o” sensors to the gateway.
• FDR: This is the Foreign Device
Registry BACnet tool.
• Backup: This is where you can
back up your settings or recover a
stored backup. See the “Backup and
Restore Gateway” section for more
information.
There are also some additional options
on the Settings dropdown in the upper
left menu:
Sensor Cloud On/Off:
“On” – saves the names of the sensor
and gateway to a secure BAPI cloud
location for retrieval at a later time.
“O” – Sensor and gateway names are
not saved to the cloud.
Continued on next page... Fig. 4: Network Tab on the Design Application Conguration Screen
Fig. 3: BAPI Design Application
Initial Screen

Installation & Operating Instructions
Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI 54631 USA
Specications subject to change without notice.
rev. 02/09/21
39021_RCV_900_BACnet_2020
6 of 12
900MHz WAM Connect
WAM Link Radio Settings:
Adjusts the radio setting on
the WAM Link 900 MHz USB
Dongle
4. Congure the “Network
Tab”
Under the “WAM Connect”
column you will nd a list
of all the gateways that are
present on the LAN (Local
Area Network) that you are on.
Select one of the gateways and
then congure the options on
the center column “Network
Tab” (Fig. 4) as needed.
Removing the check mark
next to “DHCP” will switch
your Gateway from DHCP to
Static IP Address. IP Address,
Subnet Mask, and Gateway will
be editable. The gateway will
attempt 10 times to get an IP
from a DHCP. If that fails, it will set itself to a fall back IP of 192.168.100.100.
5. Congure the “Settings Tab”
Congure the options on the “Settings Tab” as needed.
• Network: Self assigned by gateway, not adjustable.
• AES Key: Self assigned by gateway, not adjustable.
• Firmware: Current Firmware Version.
• Power Level: Adjust the dBm level of the gateway radio.
• Channel: The gateway picks the channels to use. There is no need to adjust this.
• Unit: Set the unit of measurement displayed in the gateway. Options are Celcius or Fahrenheit.
• Name: This editable eld allows you to assign a gateway name. See Step 8 “Conguring the Sensor” for more info.
•
Location: This editable eld allows you to assign a gateway location. See Step 8 “Conguring the Sensor” for more info.
• BACnet ID: This is assigned by the gateway and how it will appear on your network. Note: If you have more than one
gateway on the same BACnet network, be sure to change the BACnet ID of the gateway from the default number.
• BACnet Port: This is the port the gateway will be on in the Bacnet IP network. Default Port is 47808.
• Reboot: Allows you to remotely restart the gateway.
• Reset: Allows you to reset the gateway.
• EDE: Export Devices names and BACnet IDs.
• Request: You can request data from the gateway.
• Send: This is what sends all your conguration data to the gateway. Think of it as a “save settings button”.
NOTE: You must click the “Send” button after handing off the sensors to the gateway to save
the sensor setup in the gateway!
Setup continued...
Continued on next page...
Fig. 5: Settings Tab on the Design Application Conguration Screen

Installation & Operating Instructions
Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI 54631 USA
Specications subject to change without notice.
rev. 02/09/21
39021_RCV_900_BACnet_2020
7 of 12
900MHz WAM Connect
• Bottom Dialogue Box: The dialog box at the bottom of this window displays the
communication between the gateway and any sensors that are communicating with that gateway.
Bottom Buttons: (not
required to change for
setup)
The “CLR” buttons clear the list
should you need to clean it up
for training purposes.
The “Find” button below the left
column is used to search for
gateways and sensors if they
have not already populated in
the list.
The column on the right allows
you to turn o the sensor
discovery application.
6. Congure the “WAM
Tab”
Congure the options on the
“WAM Tab” as needed.
Off: Turns o the MQTT output.
WAM: Sends the MQTT output
to the BAPI WAM System or
your own MQTT Broker.
Local: Sends the information
to an MQTT broker that sits on
the LAN.
URL: Location of the MQTT Broker.
User: Username for the MQTT
Broker.
Password: Your Password for the
MQTT Broker.
7. “Handing off” Sensors to
the Gateway
Sensors will appear in the right
column once the battery is
installed and WAM Link receives
a transmission from the sensor (or
the unit is powered for non-battery
powered units). To assign or “hand o”
a sensor to the gateway, click on the
desired gateway from the left column
of the Conguration Screen (Fig. 7).
Then click the center “Sensors” tab.
Now drag one of the available sensors
from the right column to the center
“sensors” column.
The “Link Sensor” dialog box will
Fig. 6: Settings Tab on the Design Application Conguration Screen
Fig. 7: Conguration Screen showing a completed sensor setup
Continued on next page...
Setup continued...

Installation & Operating Instructions
Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI 54631 USA
Specications subject to change without notice.
rev. 02/09/21
39021_RCV_900_BACnet_2020
8 of 12
900MHz WAM Connect
appear (Fig. 9). Enter the sensor
name and BACnet ID if using
BACnet. See Step 8 “Conguring the
Sensors” for more info.
When prompted, press the ping/train
button on the sensor. This “hands
o” the sensor to the gateway from
the USB dongle. The communication
between the sensor and gateway
will then appear in the dialog box at
the bottom of this window. This is a
good way to conrm your sensor has
accepted the “hando”.
If after a “hando” process the sensor
still appears in the right sensor
column and turns green at the press
of the ping/train button, the hando
was unsuccessful. Please repeat the
process.
(Note: The sensor may appear in
both columns. If this happens, right
click on the sensor in the center
column and select delete, and then
repeat the hand o process.)
The Conguration Screen in
Fig 8 shows a successful hando of
sensors to the gateway. Note that all
the sensors have been removed from
the right column and are now in the
center column. These sensors are now “handed o” or assigned to the gateway that is highlighed in the left column.
Note: When all the sensors are “handed o” to the gateway, you must click the “Send” button to upload all the
settings changes to the gateway. After clicking the “Send” button, a dialog box will appear asking if you want to
reboot the gateway. This is not required.
8. Conguring the Sensors
The sensor can be congured when it is rst assigned to the gateway but if changes need to be made, you can get to
these settings by right clicking on a sensor in the center column of the Conguration Screen which opens the Edit Link
Sensor window (Fig 9).
Note: To properly set up a sensor, the sensor must be
handed off and associated with the gateway.
The “Sensor Info” section at the top of the window shows the
following:
• Serial Number: The serial number of the radio on the sensor.
• Sensor Type: The type of sensor.
The “Naming Tab” (Fig 9) lets you edit the following:
• Name: The name of the sensor.
• Location: The location of the sensor.
• BACnet ID: Assigns the BACnet Object Instance ID.
Continued on next page...
Fig. 8: Conguration Screen showing a completed sensor setup
Fig. 9: Naming Tab on the Edit Link Sensor
Window
Setup continued...

Installation & Operating Instructions
Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI 54631 USA
Specications subject to change without notice.
rev. 02/09/21
39021_RCV_900_BACnet_2020
9 of 12
900MHz WAM Connect
By default the gateway assigns the BACnet Object Instance ID for the rst sensor starting at 1000. It will go up by 1000
for each additional sensor added, so the BACnet Object Instance ID for the second sensor will be 2000. If a sensor is
removed, the next sensor added to the system will have the lowest available default number. This is important to know
when replacing a sensor.
Notice in Fig. 13 on page 10 that each sensor has multiple objects related to it. For example, room sensor 9544 has a
BACnet Object Instance ID of 1000, so all the objects associated with it (temp, humidity, setpoint, etc.) will begin with
1000. As shown in the chart below, the object instance for the temperature value is always “0” so the temperature value
for the rst sensor is 1000. The object instance for the Humidity value is always “1”, so the humidity value for the rst
sensor is 1001. For the second sensor (749E), the temperature and humidity values are 2000 and 2001 respectively. Note
that the object instance is skipped if that value is not available from that sensor, so there is no 1003 or 2003 for the rst
two sensors since neither of them has light level sensing.
You can assign your own BACnet Object Instance IDs for the sensors rather than taking the defaults assigned by the
gateway. However the IDs must be at least 10 numerals apart from each other. If you do not assigned them at least 10
apart, the system will not recognise them. For example, if you assign BACnet IDs for three sensors as of 6000, 6001 and
6002, the second two sensors will not save on the system because their IDs are already being used as the humidity and
setpoint or Barometric pressure values for the rst sensor. Instead you must assign numbers that are at least 10 apart
from each other, such as 6000, 7000 and 8000 or 6000, 6010 and 6020.
BACnet Object Instance Chart
Object Type .....Object Instance ..........Object Description
Analog Input ................. 0.......................Temperature in °C or °F
Analog Input ................. 1.......................Relative humidity in %RH
Analog Input ................. 2.......................Setpoint for room sensors / Barometric pressure in kPa for non-room sensors
Analog Input ................. 3.......................Light level in LUX
Analog Input ................. 4.......................Battery voltage level in volts
Analog Input ................. 5.......................Received wireless signal strength in dBm
Binary Input .................. 6.......................Occupancy override status
Analog Ouput................ 9.......................Heartbeat check (described on page 11)
Note: the object instance is skipped if that variable is available from the sensor, so there would be no “2” value for a
sensor without humidity measurement.
The “Radio Tab” (Fig 10) on Edit Link Sensor Window lets you edit
the following:
• Network: The network address of the sensor assigned by the
gateway
• AES Key: This is the AES encryption used between the gateway
and device assigned by the gateway
• Channel: This is the radio channel the sensor is using. Assigned
by the gateway
• Power level: dBm level of the radio. 0 dBm will yield good battery
life. Default = 0 dBm. Adjustment range = -30 to +5 dBm.
• Interval: Is the time between transmissions in seconds.
300 sec = 5 min. Default = 5 min. Adjustment range = 30 sec to 15
min.
• Battery: The voltage at which the battery is going to stop
transmissions due to an expiring battery.
Note: Once the battery drops below 3 volts, the battery is very
close to end of life and should be replaced.
Setup continued...
Fig. 10: Radio Tab on Edit Link Sensor Window

Installation & Operating Instructions
Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI 54631 USA
Specications subject to change without notice.
rev. 02/09/21
39021_RCV_900_BACnet_2020
10 of 12
900MHz WAM Connect
BACnet Information
BAPI BACnet Vendor ID: 1069
BACnet Object Instance
Fig 13 is an example of what the BACnet Objects
will look like from the BAPI Gateway using YABE
(Yet Another BACnet Explorer). Notice the Object
Instance ID changes based on the type of value being
transmitted.
Fig. 13: BACnet Object Instance info using hierarchical
topology
Continued on next page...
Fig. 12: FDR Tab on the Design Application Conguration Screen
Foreign Device Registry (FDR) Information
Fig 12 shows the settings for the
BACnet FDR (Foreign Device
Registry) tab. If more information
is needed for your network FDR
settings, please discuss it with
the network administrator for the
BACnet network in your facility.

Installation & Operating Instructions
Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI 54631 USA
Specications subject to change without notice.
rev. 02/09/21
39021_RCV_900_BACnet_2020
11 of 12
900MHz WAM Connect
BACnet Properties without a Fault
Fig 14 shows the BACnet Properties for a
temperature sensor without a sensor fault. Notice that
the “Reliability” says “0: No Fault Detected”.
The “Cov Increment” at the top is a writeable value
and the Default value is 1.
BACnet Properties with a Fault
Fig 15 shows the BACnet Properties for a
temperature sensor with a sensor fault. Notice that
the “Reliability” says “1: No Sensor”.
BACnet “Heartbeat Check” Properties
Fig 16 shows the properties for the “Heartbeat Check
Object”. Notice the “Present Value” is set for 900
which is in seconds and equals 15 minutes. This
value is writeable and adjusts the amount of time
between a missed transmission before it trips a
Reliability ag. Monitoring this “Flag” can be used as
an alert for sensor issues
Suggestion: the Heartbeat should be set to 3 times
the transmit interval value to prevent a fault on one or
two missed transmissions.
BACnet Information continued...
Fig. 14: BACnet information for a temperature sensor without
a sensor fault
Fig. 15: BACnet information for a temperature sensor with
a sensor fault
Fig. 16: BACnet “Heartbeat Check Object” information for
a temperature sensor
Replacing a Sensor
When replacing a BACnet sensor, change the ID to
the previous sensor’s BACnet ID. This will retain the
links from the previous sensor through the network.
The procedure is described below:
1. Right click the sensor you want to replace and
click “Edit”.
2. Make note of current Name and BACnet ID, then
click “Cancel”.
4. Right click on the sensor, click delete, then “Yes”.
6. Insert batteries or pull battery insulators on the
NEW sensor.
7. Press the NEW sensor Ping button and the
sensor will show up in the right column.
8. Click and drag the sensor from the right column to
the center “Sensors” column.
9. Enter the Name and BACnet ID so the new
sensor has the same information as the original
sensor noted in Step 2 and click “Save”.
11. Press the sensor Ping button when prompted.
12. Click “Send” to save settings, and click “Yes”
to reboot the gateway or “No” to not reboot the
gateway.

Installation & Operating Instructions
Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI 54631 USA
Specications subject to change without notice.
rev. 02/09/21
39021_RCV_900_BACnet_2020
12 of 12
900MHz WAM Connect
The BAPI gateway can be backed up and restored
locally. This allows you to reset the gateway in the
rare instance that it would be locked up. It also allows
you to copy the conguration to a new gateway if you
chose to replace a gateway, eliminating the need to
perform a network setup procedure on the gateway.
BACKUP - LOCAL
1. Create a folder on your computer or server to
store and retrieve the backup content.
2. Go to the center “Backup” tab and click the “Local”
icon and then click the “Backup” button (Fig 17).
This will open the “Select Backup Folder” screen
(Fig 18).
3. Select the local folder that you created in Step #1
and click “Open” to save the backup to the folder.
You will receive a “Backup Successful” message
as shown in Fig 19.
RESTORE - LOCAL
1. Go to the “Backup” tab on the WAM Design
Conguration Screen of the gateway that you
would like to restore (or the new gateway if
replacing the gateway) and click the “Restore”
button.
2. Select the backup folder on your local computer or
network from in the “Select Folder” Screen (Fig 20)
and click “Open”. You will receive a “Restore
Successful” conrmation screen (Fig 21) and also a
request to reboot the system. Click “yes”.
Backup or Restore the Gateway
Fig. 17: Backup Tab on the Design Application
Conguration Screen
Fig. 18: Select Backup Folder
Screen.
Fig. 20: Select Restore Folder
Screen.
Fig. 21: Restore
Successful Message.
Fig. 19: Backup
Successful Message.
Processor: AM3358 1GHz ARM® Cortex-A8 Processor
On-board Flash: 4GB Rated
Voltage: 12 to 42 VDC, 20 to 30 VAC
Rated Power: 12 Watt
RAM: 1 GB Cache 256KB Power over Ethernet (PoE) Power Requirements 3 watts @ 48 volts
Specications for the 900MHz WAM Connect
Table of contents
Other BAPI Gateway manuals
Popular Gateway manuals by other brands

WAGO
WAGO 758-915 manual

DBL Technology
DBL Technology VoIP FXS+PSTN Gateway user manual

Ruckus Wireless
Ruckus Wireless ZoneDirector ZD1100 Upgrade instructions

ABB
ABB AWIN GW100 user manual

ZyXEL Communications
ZyXEL Communications Unified Security Gateway ZyWALL 300 user guide

Coalesenses
Coalesenses iSense user guide