Netbiter Netbiter EasyConnect EC150 User manual

EC150 User Guide
General
The Netbiter® EasyConnect EC150 is a small remote gateway that connects any Modbus device with the Netbiter Argos server
over Ethernet. This ma es it possible to remotely monitor and control Modbus devices and networ s.
The Netbiter® EasyConnect series is always used together with the Netbiter Argos server (www.netbiter.net) to ma e the remote
monitoring and control solutions easy to install, configure and maintain. This unique combination provides;
Access and security features
• No need for public or static IP number in the installation.
• Easy passing through firewalls in a secure way without the need of complex VPN solutions.
Data management features
The Netbiter Argos offers through a web interface a wide range of features.
• Monitor and control of data
• Alarm management (email, SMS etc)
• Historical data logging and graphical trend graphs
• Reports (wee ly / monthly etc)
• Map overview and trac ing
• Web services interface to exchange data to
other web sites
Service management features
The Netbiter Argos offers many management features, especially suitable for large sites.
• Management of authorized users, projects, devices etc
• Documentation of remote sites
• Automatic bac up / restore or remote configurations and software
• Traffic analyser and reports
Additional functionality
• Transparent Modbus RTU/TCP Gateway
The Netbiter® EasyConnect product family is designed to be plug-n-play and easy to install, configure and maintain. It’s plug-n-
play structure ma es it possible to do large scale installations quic ly without being an
IT/mobile networ expert. Simplicity is ey and this is what the Netbiter® EasyConnect series is about.

EC150 User Guide
Connectors Power
The Netbiter EC150 can be pow-
ered with 9-24 V DC or AC.
RS485
RS232 y wire or d-su connector
Can be used to connect ModbusRTU slave devices, called sub
device at Netbiter Argos. There are two ways to connect RS232 to
EC150, directly by wire or through a standard 9-pin d-sub connec-
tor.
Connect directly y wire
RS232 using a d-su connector
Ethernet

EC150 User Guide
Activate the EC150
LED indicators
Module status LED
Name Color Function
Module Status OFF No power
Red/Green See Module status below
Serial Status Green Flashing – Serial pac et receive
Red Flashing – Serial pac et transmit
Activity/Collision Green Flashing – Ethernet Pac et, receive
Red Flashing – Ethernet Collision de-
tected
Ethernet link Green Turned on – Ethernet networ de-
tected, 10 Mbps
Orange Turned on – Ethernet networ de-
tected, 100 Mbps

Configure EC150
The configuration of the EasyConnect is done under the Menu Configure Devices
at NetBiter Argos. All the available devices will be listed.
Clic Configure to get access to all settings.
Su device
Every EasyConnect must have a sub device. The built in I/O will automatically show as a virtual sub device, and will be ready to
use immediately.
Every parameter in a sub device can be viewed as live values at the Overview page for the remote gateway.
Device templates
To communicate with a Modbus sub device connected to the EasyConnect, you need a Device template
which is a interface between the sub device
and the EasyConnect. The Device template contains information about the parameters in your sub device and how they should be han
dled. You can
upload, edit and create new device templates under the menu Device templates
. To create a new device template you will need the Modbus docu-
mentation from the manufacturer of your sub device.
Adding a new Su device
Press “add sub device” and fill in it´s settings.
EC150 User Guide

EC150 User Guide
•
Su device: The sub device that has the parameter that shall be logged.
•
Group: The group in where the parameter resides.
•
Parameter: The parameter that shall be logged.
•
Description: A name and description for the parameter. If the box isn´t chec ed, the default description from the template
will be used.
•
Unit: The unit of the parameter. If the box isn´t chec ed, the default description from the template will be used.
•
Scaling: The logged parameter can be scaled with this value (Actual value at terminal/Scale).
•
Offset: An offset that is added to the parameter value.
•
Num er of decimals: Defines the number of decimals to use for this parameter. If the box isn´t chec ed, the default descrip-
tion from the template will be used.
•
Valid range: Defines the maximum and minimum for a write parameter. If a user tries to enter a value outside the range a
warning message will appear. If used in combination with scaling, it is the scaled value that should be used. If the box isn´t
chec ed, the default description from the template will be used.
•
Log interval: The interval for every sample (5 minutes to 60 minutes). This could be set to Live value if the parameter only
should be read/(writeable) and not logged. If it is set to Live value this parameter will be accessible on the Live value page
under the device overview.
•
Log type: Set the log type. Here you can choose between Value and Delta. Value logs the parameters actual value and Delta
logs the difference since last log sample.
Example of use of scaling and offset:

•
Su device: The sub device that has the parameter that shall be logged.
•
Group: The group in where the parameter resides.
•
Parameter: The parameter that shall be logged.
•
Description: A name and description for the parameter. If you clic the down arrow on the right hand side of the pa-
rameter list, the parameter name will be copied.
•
Trigger: Equal to, Not equal to, Greater than or Less than value.
•
Value: Triggvalue.
•
Scaling: The logged parameter can be scaled with this value (Parameter/Scale).
•
Offset: An offset that is added to the parameter value.
•
Alarm Class: Sets the class for the Alarm. You can choose between Class 1 to Class 10.
•
Severity: Can be set to Indeterminate, Warning, Minor, Major and Critical.
EC150 User Guide

EC150 User Guide
Mod us
•
Physical:Choose what physical Modbus interface your sub device is connected to.
•
Baudrate:Set the speed which your sub device is communicating with. Refer to the sub device’s manual.
•
Parity:Set the parity that your sub device uses for error detection. Refer to it’s manual.
•
Stop its:Set the the amount of stopbits your sub device uses. 1 or 2 stopbits can be used. Refer to the sub device’s man-
ual.
Advanced configuration
The EasyConnect has the capability to handle Device profiles, which are a shared configurations between several Remote gate-
ways. When changing a device profile it will apply to all devices that are connected to the Device profile. Every device that is
sharing the Device profile has to be synchronized.
Using Device profiles decrease the wor load for administrators and ma e it easy to manage installations that are similar.
Alarms and/or logs can be configured in a Device profile, and several Device profiles can be connected to one Remote gate-
way.
A Remote gateway that have Device profiles connected can also have individual alarm and log parameters, which ma es it
quic and flexible to ma e powerful configurations and also easy to maintain.
In the example above there are log and alarm parameters configured in the device profiles. Device profile A is shared for all
the three slaves. Device Profile B, and the configured parameters, are shared by the sub device in the middle and to the right.
The device profile C are shared by the sub devices to the right and to the left.
The devices also has individual set of parameters, named configuration in the image above.

EC150 User Guide
Clic connect device profile to add a profile to a sub device.
To edit or create a device profile go to Device Profiles in the menu. Parameters are configured in the same way as for a remote
gateway.

EC150 User Guide
Help & Support
Heatherose Connected Solutions Limited
Newar 01636 702805 - www.heatherose.co.u