  9. Barber-Colman DYN1-10704 Series Operating and installation instructions

Barber-Colman DYN1-10704 Series Operating and installation instructions

Calibration and Troubleshooting
Service Information
F-24419-1
GENERAL INFORMATION
TheDYN1-10704and10724controllersarebasiccontrollerswithoutanoverspeed. The10704controllerisnormally
used on diesel engines and the 10724 is normally used on ignition engines.
TheDYN1-10714and10734controllersarealsobasiccontrollerswithoverspeedprotection12.5%abovesetspeed.
The10714controllerisnormallyusedondieselenginesandthe10734controllerisnormallyusedonignitionengines.
CALIBRATION AND TROUBLESHOOTING
FOR BASIC LINEAR CONTROLLERS
MODELS
DYN1-10704*
DYN1-10714
DYN1-10724*
DYN1-10734
*
2
TYPICAL WIRING DIAGRAM
Controllers with conformity are wired as shown in
Figure 2 Wiring Diagram.
Black
Purple
Purple
White
Black
ACT SPEED
GAIN
+
-
MPU
-
~
Red
0100
Battery
12 or 24
Vdc Supply
Purple
Black
White
Purple
Black
Red
-
+
AAA
AAA
AAA
AAA
A
A
MPU
DYNC-10200
Linear
Actuator
Non
General information, wiring and calibration procedure for the DYN1-10704, 10714, 10724 and
10734 controllers for the linear governor system.
CALIBRATION
1. With no power to the governor, adjust the GAIN to
9:00 o’clock.
2. Start the engine and adjust the speed by turning
the SPEED pot clockwise to desired speed.
NOTE
Controllers are factory adjusted to mini-
mumRPM. However,forsafety,oneshould
be capable of disabling the engine if an
overspeed should exist.
3. At no load, turn the GAIN potentiometer clockwise
until the engine begins to hunt. If the engine does
not hunt, physically upset the governor linkage.
4. Turn the GAIN potentiometer counterclockwise
until stable.
WIRING
All four non controllers are wired as shown in
Figure 1 Wiring Diagram.
1. Red to battery positive.
2. Black to battery negative.
3. Purple to the actuator, no polarity.
4. White to one side of the magnetic pickup.
5. Black and white to the other side of the magnetic
pickup connected with the shield drain wire.
Figure 1 Figure 2
Red
Black
Purple
Purple
White
Blk/Wht
MPU
ACT SPEED
GAIN
AA
AA
AA
AA
+
-
-
~
+-
AA
AA
MPU
12 or 24 Vdc
Supply
DYNC-10200
Linear
Actuator
Optional
Connections
Customer has option
on how to connect
leads to controller.
*See color
code on front
of controller. *
A
A
A
Note: The shield on the MPU is to be connected to
the black wire along with one of the MPU
conductors.
I. System appears dead. (Actuator fails to
move to full fuel) Check connections to battery.
Note: Turn off power and reconnect Purple lead.
III. Actuator hunts during operation.
Note: Reconnect actuator leads properly after
completing this test.
II. Actuator lever goes to full fuel whenever
the power is turned "ON" and engine is
not running.
1. CHECK CONTROLLER by removing actuator lead to
Purple lead and turning power “ON” to controller.
a. Actuator goes to full fuel.
b. Actuator does not go to full fuel.
1. CHECK BATTERY VOLTAGE AT CONTROLLER
with power switch “ON”. Measure DC battery voltage
between the Red (+) and Black (-) leads. Battery
voltage should be present.
2. CHECK LINKAGE. Manually operate linkage to see
that it is not sticking or binding.
3. NO SIGNAL OR WEAK SIGNAL FROM MAGNETIC
PICKUP. Measure AC voltage between the White and
Black/White leads on controller while cranking engine.
Voltage should be 2.5 volts RMS or greater. (AC input
impedance of meter must be 5000 ohms/volt or greater.)
4. CHECK ACTUATOR with power “ON” to controller.
Measure following terminals on control box with respect
to the Black lead. All points should read BATTERY
VOLTAGE. (+0.00/-0.75 VDC)
a. Purple lead to Black lead on controller.
b. Second Purple lead to Black lead on controller.
(Continue this test only if battery voltage is not
present.)
c. Following checks are terminals on the actuator
and the Black lead on controller.
1) Low voltage (1.0-2.0 VDC) at either
actuator connector.
2) Battery voltage at both actuator connectors.
3) Battery voltage at one actuator lead but not
at the other.
Check for damage to or improper
adjustment of magnetic pickup.
Replace or re-adjust.
Free linkage.
Replace controller if battery voltage
is not present at both Purple leads.
Broken actuator lead.
Replace actuator.
Broken actuator lead.
1. Linkage or rod end bearings sticking or binding.
2. Improper linkage arrangement.
(Stroke too short or improper non-linear linkage used)
3. Improper governor adjustment.
4. Inadequate power supply voltage.
a. Turn power switch "OFF".
b. Connect a DC voltmeter to Red and Black leads
at control box.
c. Disconnect both leads to actuator at Purple
leads of control box.
d. Connect one actuator lead to the Red lead and
one actuator lead to the Black lead of the
control box.
e. Momentarily turn "ON" the DC power. The
actuator should go to full fuel and the DC
voltage must be greater than 80% of supply.
24 VDC @ 80% = 19.2 VDC
12 VDC @ 80% = 9.6 VDC
Check for shorted actuator lead.
Replace Controller because it should not
cause actuator lever to go to full fuel with
engine not running.
Lubricate or replace.
Readjust calibration.
If actuator doesn’t get to full fuel, then
check actuator leads. If voltage is less
than specified, check for loose or poor
connections to battery, or get larger supply
leads or larger power supply.
See installation information.
LINEAR TROUBLESHOOTING CHART
Corrective ActionProblem Detection
3
F-24419-1
An Invensys company
As a safety measure, the engine should be equipped with an
independent overspeed shutdown device in the event o
f
failure which may render the governor inoperative.
CAUTION
Barber-Colman believes that all information provided herein is
correct and reliable and reserves the right to update at an
y
time. Barber-Colman does not assume any responsibility fo
r
its use unless otherwise expressly undertaken.
NOTE
Barber-Colman DYNA Products
1354 Clifford Avenue (Zip 61111) Telephone (815) 637-3000
P.O. Box 2940 Facsimile (815) 877-0150
Loves Park, IL 61132-2940 www.dynaproducts.com
United States of America
In Europe contact: Barber-Colman GmbH
Am Neuen Rheinhafen 4, D-67346 Speyer, Germany
Telephone (49) 6232 29903, Facsimile (49) 6232 299155
In Japan contact: Ranco Japan Ltd.
Shiozaki Bldg. 7-1, 2-chome, Hirakawa-Cho, Chiyoda-Ku
Tokyo 102, Japan
Telephone (81) 3 3261 4293, Facsimile (81) 3 3264 4691

This manual suits for next models

5

Other Barber-Colman Controllers manuals

Barber-Colman DYNA 8000 User manual

Barber-Colman

Barber-Colman DYNA 8000 User manual

Barber-Colman MACO Series User manual

Barber-Colman

Barber-Colman MACO Series User manual

Popular Controllers manuals by other brands

Griffin Technology PowerMate quick start guide

Griffin Technology

Griffin Technology PowerMate quick start guide

ADC PG-FlexPlus FSU-571 Quick installation guide

ADC

ADC PG-FlexPlus FSU-571 Quick installation guide

Allen-Bradley Compact GuardLogix 5370 user manual

Allen-Bradley

Allen-Bradley Compact GuardLogix 5370 user manual

Sealey SGA3.V2 instructions

Sealey

Sealey SGA3.V2 instructions

WEIGL ProCommander LTC instruction manual

WEIGL

WEIGL ProCommander LTC instruction manual

Brooks SLA7950S Installation and operation manual

Brooks

Brooks SLA7950S Installation and operation manual

Siemens SIMOTION Series Commissioning and hardware installation manual

Siemens

Siemens SIMOTION Series Commissioning and hardware installation manual

Victron energy MultiPlus-II 48/3000/35-32 230V GX manual

Victron energy

Victron energy MultiPlus-II 48/3000/35-32 230V GX manual

Ytc YT-2500 SERIES product manual

Ytc

Ytc YT-2500 SERIES product manual

Emerson Branson 2000X ae operating manual

Emerson

Emerson Branson 2000X ae operating manual

Tornatech VP series Installation and maintenance manual

Tornatech

Tornatech VP series Installation and maintenance manual

DH Instruments PPC2 PLUS manual

DH Instruments

DH Instruments PPC2 PLUS manual

Quicksmart EtherRain user guide

Quicksmart

Quicksmart EtherRain user guide

Citizen CBM-909 Series user manual

Citizen

Citizen CBM-909 Series user manual

Infineon TLD5099EP quick start guide

Infineon

Infineon TLD5099EP quick start guide

Cielo Breez Eco user manual

Cielo

Cielo Breez Eco user manual

IFM Ecomat 300 AS-i Series Basic device manual

IFM

IFM Ecomat 300 AS-i Series Basic device manual

Spectronik MGPR user guide

Spectronik

Spectronik MGPR user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.