Barber-Colman DYNA 8000 User manual

TECHNICAL MANUAL
FOR
DYNA 8000, 8200 & 8400
ELECTRONIC GOVERNOR
DYNA 8000 DYNA 8200
DYNA 8000-400 & DYNA 8400-400
DYNA 8400
F-23721-5

CONTENTS
SECTION DESCRIPTION PAGE
1 GENERAL INFORMATION........................... 3
2 SPECIFICATIONS......................................... 3
3 FUNCTIONAL DESCRIPTION .....................5
4 INSTALLATION............................................. 6
5 CALIBRATION OF DYN1-1065X.................. 9
6 CALIBRATION OF DYN1-1068X................ 11
7 TROUBLESHOOTING................................ 13
8 INSTALLATION DIMENSIONS................... 15
2

=
Input Signal
Frequency in Hertz
3
2.1.10 DYNA 8000 CONTROLLER
Nominal Quiescent Current 80 mA
Maximum Amperes @ Stall 13 amps
Nominal Quiescent Current 80 mA
Maximum Amperes @ Stall 13 amps
Kilograms 0.863
Pounds 1.9
Output Current
@ 24 VDC
Weight
Output Current
@ 12 VDC
2.1.11 DYNA 8000 CONTROLLER
INPUT SIGNAL FREQUENCY
Engine RPM x Number of Gear
Teeth on Flywheel
60 Seconds
Select controller for the correct input signal frequency range
generated by the magnetic pickup at the maximum engine
operated (RPM) speed.
2.1.12 AVAILABLE CONTROLLER MODELS
Controllers: Speed Input Signal Frequency
•DYN1-10652-000-0-12/24 250 - 1200 Hz
•DYN1-10653-000-0-12/24 1200 - 2500 Hz
•DYN1-10654-000-0-12/24 2500 - 5000 Hz
•DYN1-10656-000-0-12/24 5000 - 9500 Hz
•DYN1-10682-000-0-12/24 250 - 1200 Hz
•DYN1-10683-000-0-12/24 1200 - 2500 Hz
•DYN1-10684-000-0-12/24 2500 - 5000 Hz
•DYN1-10686-000-0-12/24 5000 - 9500 Hz
2.2. DYNA 8000 & DYNA 8000 UL APPROVAL,
HAZARDOUS DUTY, CLASS 1, DIVISION 2, GROUP D
ACTUATOR SPECIFICATIONS
2.2.1 Operating Voltage: 12 VDC or 25 VDC ±20%
2.2.2 Ambient Operating Temperature:
-65 to +255°F (-55 to +125°C).
2.2.3 Sealed Unit: Oil, water and dust tight.
2.2.4 Connection: Terminal strip or "MS" Connector.
2.2.5 Mechanical Vibration: 5 to 500 Hz, Curve F, per
MIL-STD. 810D, Method 514-2.
2.2.6 DYNA 8000 ACTUATORS
Joules 1.2
Foot-Pounds 0.9
Newton-Meters 1.4
Pound-Foot 1.0
Rotary 35°
Kilograms 5
Pounds 11.0
Maximum Amperes @ Stall 12.5
Nominal Steady State Amperes 3.5
Maximum Amperes @ Stall 9.5
Nominal Steady State Amperes 1.5
Nominal Response Time for 63% of Stroke
(Seconds)
Current @
12 VDC
Current @
24 VDC
Torque
Output
Weight
Work
0.030
1. GENERAL INFORMATION
1.1 INTRODUCTION
TheDYNA8000,DYNA8200andDYNA8400governorsystem
provides an engine governor for speed and power control of
piston and gas turbine engines or steam and water turbines.
The actuator is a simple, proportional, electric solenoid having
aslidingarmaturewhosemagneticforceisproportionaltoinput
coilcurrent.Thearmatureglidesonanti-frictionbearingsandis
balanced between the force of its return spring and the mag-
netic force, thus providing a hysteresis-free linear movement.
The linear motion is converted to an output shaft rotation by a
crank arm.
The hazardous duty DYNA 8000 and DYNA 8400 actuators
provide units that are UL listed for Class I, Division 2, Group D,
hazardous duty applications that are often encountered in the
petroleum or chemical industries. The hazardous duty actua-
tors can be used to provide an engine governor for speed and
power control of piston and gas turbine engines.
1.2 TYPICAL APPLICATIONS
Typical applications are speed governing, remote throttle con-
trol, generator sets, power carts and pump set applications.
1.3 STANDARD FEATURES
•All electric
•All engine compatible
•Mounts in any position
•Engine mounted (actuator only)
•High reliability due to few moving parts
•Proportional actuator
•No hydraulic or oil lines
•No special maintenance
•Spring returns output shaft to minimum position on removal
of power or loss of magnetic pickup signal
•Precise repeatability
2. SPECIFICATIONS
2.1 CONTROLLER SPECIFICATIONS
2.1.1 Operating Voltage: 12 VDC or 24 VDC ±20%
2.1.2 Ambient Operating Temperature:
-40 to +180°F (-40 to +85°C).
2.1.3 Temperature Stability: Better than ±0.5% over a
temperature range of -40 to +167°F (-40 to +75°C).
2.1.4 Steady State Speed Band: ±0.25%
2.1.5 Adjustments: Speed, Gain, Integral, and Droop.
2.1.6 Circuit Boards: Boards are covered with a heavy
conformal coating for moisture and vibration protection.
2.1.7 Connection: Terminal strip.
2.1.8 Mechanical Vibration: Withstands the following vibra-
tion without failure of degraded performance: 0.06 inch double
amplitude at 5 to 18 Hz; 1 G at 18 to 30 Hz; 0.02 inch double
amplitude at 30 to 48 Hz; 2.5 G's at 48 to 70 Hz.
2.1.9 The same DYN1-1065X or DYN1-1068X Series can be
used on a DYNA 8000, DYNA 8200 or DYNA 8400 actuator.
TheDYN1-1068Xgovernor control boxprovides awider range
ofadjustmentthantheDYN1-1065X.The DYN1-1068Xcanbe
used where maximum performance is desired or for some
engines which are possibly more difficult to control.

2.2.11 AVAILABLE DYNA 8000 HAZARDOUS DUTY
ACTUATOR MODELS WITH CLOCKWISE OUTPUT SHAFT
ROTATION (Standard Mounted Units)
•DYNC-11020-400-0-12 Standard Clockwise
DYNC-11020-400-0-24 Output Shaft Rotation
•DYNC-11021-400-0-12 Actuator Head Positioned 180°
DYNC-11021-400-0-24 from Standard DYNC-11020
•DYNC-11022-400-0-12 Actuator Head Positioned 90°
DYNC-11022-400-0-24 CCW from Standard DYNC-11020
2.2.12 AVAILABLE DYNA 8000 HAZARDOUS DUTY
ACTUATOR MODELS WITH COUNTERCLOCKWISE
OUTPUT SHAFT ROTATION (Standard Mounted Units)
•DYNC-11024-400-0-12 Standard Clockwise
DYNC-11024-400-0-24 Output Shaft Rotation
•DYNC-11025-400-0-12 Actuator Head Positioned 90°
DYNC-11025-400-0-24 CW from Standard DYNC-11024
•DYNC-11026-400-0-12 Actuator Head Positioned 180°
DYNC-11026-400-0-24 CCW from Standard DYNC-11024
2.2.13 AVAILABLE DYNA 8000 HAZARDOUS DUTY
ACTUATOR MODELS WITH CLOCKWISE OUTPUT SHAFT
ROTATION (Side Mounted Units)
•DYNC-11020-401-0-12 Standard Clockwise
DYNC-11020-401-0-24 Output Shaft Rotation
•DYNC-11021-401-0-12 Actuator Head Positioned 180°
DYNC-11021-401-0-24 from Standard DYNC-11020
•DYNC-11022-401-0-12 Actuator Head Positioned 90°
DYNC-11022-401-0-24 CCW from Standard DYNC-11020
2.2.14 AVAILABLE DYNA 8000 HAZARDOUS DUTY
ACTUATOR MODELS WITH COUNTERCLOCKWISE
OUTPUT SHAFT ROTATION (Side Mounted Units)
•DYNC-11024-401-0-12 Standard Clockwise
DYNC-11024-401-0-24 Output Shaft Rotation
•DYNC-11025-401-0-12 Actuator Head Positioned 90°
DYNC-11025-401-0-24 CW from Standard DYNC-11024
•DYNC-11026-401-0-12 Actuator Head Positioned 180°
DYNC-11026-401-0-24 CCW from Standard DYNC-11024
2.3 DYNA 8200 ACTUATORS
2.3.1 Operating Voltage: 12 or 24 VDC ±20%.
2.3.2 Ambient Operating Temperature:
-65 to +255F (-55 to +125°C).
2.3.3 Sealed Unit: Oil, water and dust tight.
2.3.4 Connection: Terminal strip or "MS Connector.
2.3.5 Mechanical Vibration: 5 to 500 Hz, Curve F, per MIL-
STD. 810D, Method 514-2.
4
2.2.7 AVAILABLE DYNA 8000 ACTUATOR MODELS
WITH CLOCKWISE OUTPUT SHAFT ROTATION
(Standard Mounted Units)
•DYNC-11020-000-0-12 Standard Clockwise
DYNC-11020-000-0-24 Output Shaft Rotation
•DYNC-11021-000-0-12 Actuator Head Positioned 180°
DYNC-11021-000-0-24 from Standard DYNC-11020
•DYNC-11022-000-0-12 Actuator Head Positioned 90°
DYNC-11022-000-0-24 CCW from Standard DYNC-11020
•DYNC-11023-000-0-12 Actuator Head Positioned 90°
DYNC-11023-000-0-24 CW from Standard DYNC-11020
2.2.8 AVAILABLE DYNA 8000 ACTUATOR MODELS
WITH CLOCKWISE OUTPUT SHAFT ROTATION
(Side Mounted Units)
•DYNC-11020-300-0-12 Standard Clockwise
DYNC-11020-300-0-24 Output Shaft Rotation
•DYNC-11021-300-0-12 Actuator Head Positioned 180°
DYNC-11021-300-0-24 from Standard DYNC-11020
•DYNC-11022-300-0-12 Actuator Head Positioned 90°
DYNC-11022-300-0-24 CCW from Standard DYNC-11020
•DYNC-11023-300-0-12 Actuator Head Positioned 90°
DYNC-11023-300-0-24 CW from Standard DYNC-11020
2.2.9 AVAILABLE DYNA 8000 ACTUATOR MODELS
WITH COUNTERCLOCKWISE OUTPUT SHAFT
ROTATION (Standard Mounted Units)
•DYNC-11024-000-0-12 Standard Clockwise
DYNC-11024-000-0-24 Output Shaft Rotation
•DYNC-11025-000-0-12 Actuator Head Positioned 90°
DYNC-11025-000-0-24 CW from Standard DYNC-11024
•DYNC-11026-000-0-12 Actuator Head Positioned 180°
DYNC-11026-000-0-24 CCW from Standard DYNC-11024
•DYNC-11028-000-0-12 Actuator Head Positioned 90°
DYNC-11028-000-0-24 CCW from Standard DYNC-11024
2.2.10 AVAILABLE DYNA 8000 ACTUATOR MODELS
WITH COUNTERCLOCKWISE OUTPUT SHAFT
ROTATION (Side Mounted Units)
•DYNC-11024-300-0-12 Standard Clockwise
DYNC-11024-300-0-24 Output Shaft Rotation
•DYNC-11025-300-0-12 Actuator Head Positioned 90°
DYNC-11025-300-0-24 CW from Standard DYNC-11024
•DYNC-11026-300-0-12 Actuator Head Positioned 180°
DYNC-11026-300-0-24 CCW from Standard DYNC-11024
•DYNC-11028-300-0-12 Actuator Head Positioned 90°
•DYNC-11028-300-0-24 CCW from Standard DYNC-11024

Current @
24 VDC
Current@
12 VDC
Weight
Output
Torque
Work
Nominal Response Time for 63% of Stroke
(Seconds) .138
Work
Torque
Output
Weight
Current @
24 VDC
Nominal Response Time for 63% of Stroke
(Seconds) 0.104
2.3.6 AVAILABLE DYNA 8200 ACTUATOR MODELS
WITH CLOCKWISE OUTPUT SHAFT ROTATION
•DYNC-12000-000-0-12 Standard Clockwise
DYNC-12000-000-0-24 Output Shaft Rotation
•DYNC-12001-000-0-12 Actuator Head Positioned 180°
DYNC-12001-000-0-24 from Standard DYNC-12000
•DYNC-12002-000-0-12 Actuator Head Positioned 90°
DYNC-12002-000-0-24 CCW from Standard DYNC-12000
•DYNC-12003-000-0-12 Actuator Head Positioned 90°
DYNC-12003-000-0-24 CW from Standard DYNC-12000
2.4 DYNA 8400 & DYNA 8400 UL APPROVAL,
HAZARDOUS DUTY, CLASS 1, DIVISION 2, GROUP D
ACTUATOR SPECIFICATIONS
2.4.1 Operating Voltage: 24 VDC ±20%.
2.4.2 Ambient Operating Temperature:
-65 to +255F (-55 to +125°C).
2.4.3 Sealed Unit: Oil, water and dust tight.
2.4.4 Connection: Terminal strip or "MS Connector.
2.4.5 Mechanical Vibration: 5 to 500 Hz, Curve F, per MIL-
STD. 810D, Method 514-2.
Joules 2.85
Foot-Pounds 2.10
Newton-Meters 4.07
Pound-Foot 3.00
Rotary 45°
Kilograms 8.4
Pounds 18.5
Maximum Amperes @ Stall 14.75
Nominal Steady State Amperes 4.5
Maximum Amperes @ Stall 14.0
Nominal Steady State Amperes 3.5
2.4.7 AVAILABLE DYNA 8400 ACTUATOR MODELS
WITH TERMINAL STRIP CONNECTION
•DYNC-14800-000-0-24 Through Output Shaft Making
Available CW and CCW Output
2.4.8 AVAILABLE DYNA 8400 ACTUATOR MODELS
WITH 2-PIN MS SCREW ON CONNECTOR
•DYNC-14801-000-0-24 Through Output Shaft Making
Available CW and CCW Output
2.4.9 AVAILABLE DYNA 8400 HAZARDOUS DUTY
ACTUATOR WITH TERMINAL STRIP CONNECTION
INSIDE CAST IRON JUNCTION BOX
•DYNC-14800-400-0-24 Through Output Shaft Making
Available CW and CCW Output
3. FUNCTIONAL DESCRIPTION
3.1 ACTUATOR
The actuator consists of an electro-magnet with an iron
armature rolling on the center shaft bearings. The actuator is
provided with a return spring which balances the magnetic
force of the armature. When DC current flows in the coil, the
magnetic force tends to move the armature in the stator and
this linear motion is transformed into rotary motion through a
crank arm that forms part of the output shaft.
3.2 CONTROLLER
The electronic controller is the information processing unit of
the governor assembly. It contains electronic components
which process the input signal from the magnetic pickup and
control the engine to the desired speed/RPM set into the
controller.Electronicadjustmentsareavailableonthecontrol-
ler for field adjusting the unit as necessary.
3.3 DC POWER SOURCE
The governor system receives its power from a battery or an
AC to DC power supply supplying 12 or 24 VDC ±20% to
match the governor voltage. The average operating current
consumption is 2.5 to 3.5 amperes and the highest consump-
tion is 14.75 amperes during engine start-up or during a large
load change. The power source must be rated above maxi-
mum stall current.
3.4 COMPONENT LOCATION
The actuator of the governor assembly is mounted on the
engine next to the fuel system. The magnetic pickup is
normally mounted in the flywheel housing in such a way that
itcan count theteeth on thestarterring gear. Thecontroller is
off-mountedorinstalledintheenginecontrolpanelorcabinet.
2.4.6 DYNA 8400 ACTUATORS
Joules 5.8
Foot-Pounds 4.3
Newton-Meters 7.3
Pound-Foot 5.4
Rotary 45°
Kilograms 12.2
Pounds 27
Maximum Amperes @ Stall 13
Nominal Steady State Amperes 2.0
5

Full Load
Engine RPM
No Load
Engine RPM
Adjustable
100%
% of Engine Load
0%
Engine
RPM
NOTE
Mounting information and kits are usually available for
a particular engine. Contact Sales Representative.
4.1.2 Set up the linkage and rod end bearings (see 4.2).
4.1.3 Install the speed sensor with SAE threads (magnetic
pickup)*.
4.1.3.1 Remove the inspection cover over the ring gear teeth.
The teeth should be free of burrs, excessive grease or dirt.
4.1.3.2 The magnetic pickup should not be installed in inspec-
tion covers. Inspect the ring gear housing and pick a location
where a 37/64" hole can be drilled such that the ring gear teeth
will pass in front of the pickup pole face. After the 37/64" hole
is drilled, use a 5/8-18 starting tap to cut threads for the
magnetic pickup, then run a bottom tap through the hole.
4.1.3.3 Manuallyrotatetheringgearuntilatoothfaceisdirectly
inthecenterofthetappedhole.Gentlyturnthemagneticpickup
clockwiseintotheholeuntilitbottomsonthetooth,andbackoff
1/4 turn. Tighten the jam nut firmly, maintaining the 1/4 turn
position.
*Magnetic pickups with metric threads are available.
Thread — M16 x 1.5 — 6 g. Tap Drill Size — 14.5 0 mm.
NOTE
The tapped hole should be drilled as nearly perpendicular
as possible over the center of the ring gear teeth.
6
Desired
Engine RPM
Isochronous
Operation Mode
Engine
RPM
Engine Load 100%
3.6 DROOP OPERATION
Droop operation is obtained by setting the droop potentiom-
eter.Clockwiseincreasesthe droop. The amountof droop for
a given setting depends on the magnetic pickup frequency
and no load to full load actuator shaft rotation. A droop
potentiometer setting of 10 o'clock will give about 4% droop,
noload tofull load whenthe pickup frequencyis 4260 Hzand
actuator shaft rotation is approximately 30 degrees from no
load to full load. Lower pickup frequency or smaller shaft
rotation results in less droop for the system.
3.5 ISOCHRONOUS OPERATION
Isochronousoperationisobtainedbysettingdrooppotentiom-
eter fully counterclockwise. The DYNA governor is all electric,
and it is normally operated in the isochronous mode; i.e.,
engine RPM is constant (±0.25%) under steady state load
conditions, up to the engine's maximum capability, regardless
of load on the engine.
3.7 REMOTE SPEED ADJUSTMENT
Anoptional remote speedselector (DYNS-10000) isavailable
foradjustingengineRPMfromupto90meters(300ft.)fromthe
engine. See the Electrical Wiring Schematic. The potentiom-
eter can be connected for a narrow (fine) or wide speed range
control.
4. INSTALLATION
4.1 PROCEDURE
4.1.1 Mount the actuator on a suitable rigid steel bracket or
plate.

4.2.1 ROTARY ACTUATOR TO ROTARY FUEL PUMP
4.2 TYPICAL LINKAGE ARRANGEMENTS FOR THE ACTUATOR AND FUEL SYSTEM
4.2.2 ROTARY ACTUATOR TO LINEAR FUEL PUMP
INSTALLATION OF MAGNETIC PICKUP
4.1.4 Mount the controller in the control panel.
4.1.5 Connect the wiring as shown in section 4.3 or according to your particular wiring diagram.
Speed Sensor
Ring Gear
Gap
.37 ± .127 mm
[.015 ± .005]
Magnetic Pickup
has 5/8-18 Threads
Jam Nut
2 Pin Connector
No.MS3106A 10-SL-4S
Engine
Housing
Actuator
AAA
AAA
AAA
AAA
Max
Fuel Lever
Assembly
Min
Fuel
Rod End
Bearing 1
Fuel
Pump
Min
Fuel Max
Fuel
AAA
AAA
AAA
Rod End
Bearing
Lever
Assembly
2
Rod
Actuator
AAA
AAA
AAA
AAA
Max
Fuel Lever
Assembly
Min
Fuel
Rod End
Bearing
Rod
1
2
Min
Fuel Max
Fuel
Rod End
Bearing
Fuel
Pump
Choose hole in actuator lever which causes actuator to rotate through its maximum rotation to provide
minimum to maximum fuel.
Non-Linear linkage to actuator is proper for best operation. Provides low GAIN at light loads and high
GAIN at heavy loads.
1
2
7

† The5Kremote speedpotentiometercan bewired two differentways:
1. As shown by the solid line from the wiper of the 5K potentiometer
and then connected to terminal #9 (no resistor required). Adjust-
able range is approximately ±5% at 1800 RPM.
2. As shown by the dashed line from the wiper of the 5K potentiom-
eter through resistor R and then connected to terminal #8.
Reducing the value of R increases the remote adjustable speed
range.
8
Cable A -- DYNK-44-XX (specify length) (90°connector)
Cable B -- E26-22 (specify length)
Cable C -- DYNZ-70-4 (specify length) (terminal strip)
Cable C -- DYNK-210 (specify length) (MS connector)
* Shielded cable -- Should be purchased from Barber-Colman or
customer should purchase a cable with a wrapped mylar supported
aluminum foil shield with a drain wire.
** Remote speed potentiometer and 499K ohm resistor is B-C P/N
(DYNS-10000).
DIMENSIONS -- DYNA 8000 CONTROLLER -- DYN1 1065X and DYN1 1068X
Dimensions are in mm except as otherwise noted.
Dimensions in [ ] are in inches.
4.3 TYPICAL WIRING DIAGRAM & CONTROLLER INSTALLATION DIMENSIONS
TP1
12345678910 11
TP2
Failsafe
AAAAAAA
AAAAAAA
AAAAAAA
AAAAAAA
A
+8V +4V
ILS
External
Speed
Adjust
Chassis
Gnd
Screw
AAAA
AAAA
AAAA
AAAA
AA
Chassis
Gnd
Screw
Blk Wht
Magnetic Pick-up
+
-
Battery
Actuator
Wiring Diagram for Controllers
Chassis ground
screw
I

2500 to 5000 Hz
5000 to 9000 Hz
DYN1-10652-000-0-12/24
DYN1-10652-001-0-12/24*
DYN1-10653-000-0-12/24
DYN1-10653-001-0-12/24*
]
]
250 to 1200 Hz
1200 to 2500 Hz
Part Number
DYN1-10654-000-0-12/24
DYN1-10654-001-0-12/24*
DYN1-10656-000-0-12/24
DYN1-10656-001-0-12/24*
]
]
Part Number
Input Signal
Frequency
Maximum
Input Signal
Frequency
Maximum
5. CALIBRATION OF DYNA 8000 SERIES CONTROLLER— DYN1-1065X
5.1 CONNECTION INFORMATION
5.1.1 When using an ILS unit, the remote speed potentiom-
eter may be left connected to the controller as shown.
5.1.2 WhenanILSunitisused,connect3-wireshieldedcable
toterminals6,7and8.Connectdrainshieldwiretoterminal10
atthecontrolleronly. Other end ofdrain shield wire isto be cut
off and taped.
5.2 CALIBRATION AND ADJUSTMENTS
5.2.1 See diagram on page 8 for a reference guide before
making any adjustments of the potentiometers, DROOP, I,
GAIN and SPEED.
5.2.2 Power OFF - engine not operating.
5.2.3 Initial potentiometer settings:
5.2.3.1 Set the I adjustment three divisions from zero and
the GAIN at the second division from zero.
5.2.3.2 For isochronous operation, set DROOP counter-
clockwise to minimum position as shown in paragraphs 3.5
and 3.6.
5.2.3.3 For DROOP operation, set DROOP potentiometer
clockwisetoobtaindesiredamountofDROOPfromno-loadto
fullload. Turning potentiometerclockwise increases DROOP.
NOTE
See Step 5.3 for proper procedures for setting switches S1
and S2, if you have a controller that has the two switches
located on top of the controller.
9
NOTE
Ifthefull35°rotationoftheactuatorshaftisusedand
thelinkageadjustedtouseonlytheactivefuelrange,
the maximum obtainable DROOP would be approxi-
mately 12% at full load.
5.3.3.4 See step 5.3 for setting switches S1 and S2.
5.2.4 If a remote speed potentiometer is used for narrow
range,setitto mid-range. If theremote speed potentiometer is
connected to terminals 6, 7 and 9, a resistor "R" in the wiper is
not needed. This will provide approximately a ±5% adjustable
speed range.
NOTE
Exceptforthespeedadjustment,thepotentiometers
have internal stops at the 0 and 100% positions.
5.2.5 Start the engine.
5.2.5.1 Adjust the controller speed potentiometer until the
engine is operating at the desired engine RPM. Clockwise
increases engine RPM.
5.2.5.2 Ifthegovernorsystemisunstable,slightlyreducethe
GAIN setting.
5.2.6 With the engine unloaded, finalize the settings, I and
GAIN adjustments as follows:
5.2.6.1 Turn the GAIN adjustment clockwise slowly until the
actuator lever oscillates. (One may need to disturb actuator
levertocauseoscillation.) ReducetheGAINadjustmentslowly
counterclockwise until the lever is stable. Upset the lever by
hand. If the lever oscillates 3 to 5 diminishing oscillations and
stops, the setting is correct.
Ifsystemperformancetoloadchangesissatisfactory,omitstep
5.2.6.2.
5.2.6.2 Reduce the GAIN setting counterclockwise one divi-
sion.Next,turntheIadjustmentfullyclockwisewhileobserving
theactuatorlever.Iftheleverdoesnotbecomeunstable,upset
itbyhand.Whentheleverslowlyoscillates,turntheadjustment
counterclockwiseslowlyuntiltheleverisstable.Upsetthelever
again; it should oscillate 3 to 5 times and then become stable
for optimum response.
NOTE
Use the settings of step 5.2.6.1 or step 5.2.6.2,
whichever provides the best performance.
5.2.6.3 Unit is now calibrated.
*

Side View
"On"
ON OFF
Side View
"Off"
OFFON
O
N
O
F
F
Top View
S1 S2
5.5 PROPER PROCEDURES FOR SETTING SWITCHES S1
AND S2
Question: How do I know if the switches in the dual-in-line
packages are correctly set as far as being in the OFF position
or the ON position?
Answer: The drawings above should clarify any confusion
aboutswitch settings. The easiestway tosetthe switches isto
applypressurewithasmallpointedobjectuntiltheswitchclicks
into position.
CAUTION
As a safety measure, the engine should be equipped with
an independent overspeed shutdown device in the event
of failure which may render the governor inoperative.
10
NOTE
Forsomedieselengines,better operation may be
obtained by placing SW1 in "ON" position. If
difficultyisexperiencedin"OFF"position,trySW1
ON and recalibrate.
5.3 ALL CONTROLLERS WITH REVISION J AND ABOVE
HAVE SWITCHES S1 AND S2
These units have two new features now added to the DYN1
1065X series controllers. They are:
5.3.1 Two response ranges, for matching either the diesel or
gas engine dynamics.
•Set S1 to the OFF position for diesel engine applications.
•Set S1 to the ON position for gas/gasoline engine
applications.
5.3.2 Two actuator selections, so the same controller can be
usedontheDYNA8000,DYNA8200orDYNA8400actuator.*
•Set S2 to the OFF position when using a DYNA 8000
actuator.
•SetS2totheONpositionwhenusingaDYNA8200orDYNA
8400 actuator.
5.4. GENERAL INFORMATION ON S1 AND S2
•Switch S1 selects one of two integrating rate ranges. The
diesel version integrates at twice the rate of the gas version
•Switch S2 selects the point at which actuator coil current
level causes the integrator limit to be actuated. This level
is nominally 6.3 amperes for the DYNA 8000 and 7.3 am-
peres for the DYNA 8200 and 8400 actuator.
*DYNA 8000 -- DYNC 11020 Series
DYNA 8200 -- DYNC 12000 Series
DYNA 8400 -- DYNC 14800 Series
These actuators do not have a potentiometer feedback
transducer.

6. CALIBRATION PROCEDURE FOR 8000 GOVERNOR CONTROLLER —
DYN1-10682, 10683, 10684, 10686
DYN1-10682-000-0-12/24
DYN1-10682-001-0-12/24*
DYN1-10683-000-0-12/24
DYN1-10683-001-0-12/24*
Input Signal
Frequency
Maximum
Input Signal
Frequency
Maximum
Part NumberPart Number
DYN1-10684-000-0-12/24
DYN1-10684-001-0-12/24*
DYN1-10686-000-0-12/24
DYN1-10686-001-0-12/24*
2500 to 5000 Hz
5000 to 9000 Hz
250 to 1200 Hz
1200 to 2500 Hz
WARNING
For gas engines, make certain that method used
does not put gas in exhaust which might result in
an explosion.
6.1 CALIBRATION PROCEDURE
6.1.1 Observethatpotentiometersettingsareadjustablefrom
zero to 100%. Each small division is 10%. The speed potenti-
ometer is 10K, 20 turn.
6.1.2 Setthesmalldipswitch,S1,forthecorrectengine.(See
paragraph6.4) SetswitchS2inthe"OFF"positionforactuator
DYNA 8000 or in the "ON" position for DYNA 8200 and 8400.
6.1.3 If a remote speed potentiometer is used for narrow
range, set to mid range.
6.2 INITIAL POTENTIOMETER SETTINGS
GAIN 20%
I 20%
D 30%
DROOP Zero
6.2.1 For isochronous operation, set DROOP counterclock-
wisetominimumposition as shown inparagraphs 3.5 and 3.6.
6.2.2 ForDROOPoperation,setDROOPpotentiometerclock-
wise to obtain desired amount of DROOP from no-load to full
load. Turning potentiometer clockwise increases DROOP.
6.3 START ENGINE (NO LOAD)
6.3.1 Adjust the controller speed potentiometer for desired
engine speed.
6.3.2 Adjust the GAIN potentiometer clockwise until the en-
gine begins to hunt. (If the engine remains stable at 100%
GAIN, physically disrupt the actuator linkage by hand.) With
theenginehunting,turntheGAINpotentiometercounterclock-
wise until stable.
6.3.3 Repeat step 6.3.2 for the "D" setting.
6.3.4 Repeat step 6.3.2 for the "I" setting.
]
]
]
]
NOTE
SeeStep6.4forproperproceduresforsettingswitchesS1
and S2, if you have a controller that has the two switches
located on top of the controller.
11
6.3.5 After calibration, it may be necessary to readjust the
speed.
6.3.6 Following the above calibration, conduct the following
test. Withtheengineoperatingatratedspeed,turntheelectric
governor off. When engine speed slows to approximately half
ofratedspeed,turntheelectricgovernorbackon.Observethe
overshoot. If there is a small hunt at steady state, slightly turn
the "I" potentiometer counterclockwise until stable. In some
cases, 2 to 3 Hz overshoot may be acceptable.
If possible, operate the unit through various load ranges up to
100% to ensure stability.
6.4 CONTROLLERS HAVE SWITCHES S1 AND S2
These units have two new features now added to the DYN1
1068X series controllers. They are:
6.4.1 Two response ranges for matching either the diesel or
gas engine dynamics.
•Set S1 to the OFF position for diesel engine applications.
•Set S1 to the ON position for gas/gasoline engine
applications.
6.4.2 Two actuator selections, so the same controller can be
usedontheDYNA8000,DYNA8200orDYNA8400actuator.*
•Set S2 to the OFF position when using a DYNA 8000
actuator.
•SetS2totheONpositionwhenusingaDYNA8200orDYNA
8400 actuator.
*

Side View
"On"
ON OFF
Side View
"Off"
OFFON
O
N
O
F
F
Top View
S1 S2
12
6.5 GENERAL INFORMATION ON S1 AND S2
•Switch S1 selects one of two integrating rate ranges. The
dieselversion integrates at twice therateofthegasversion.
•Switch S2 selects the point at which actuator coil current
level causes the integrator limit to be actuated. This level is
nominally6.3amperesfortheDYNA 8000and7.3amperes
for the DYNA 8200 and 8400 actuator.
6.6 PROPERPROCEDURESFORSETTINGSWITCHESS1
AND S2
Question: How do I know if the switches in the dual-in-line
packages are correctly set as far as being in the OFF position
or the ON position?
Answer: The drawings above should clarify any confusion
aboutswitchsettings.Theeasiestwaytosettheswitchesisto
apply pressure with a small pointed object until the switch
clicks into position.
*DYNA 8000 -- DYNC 11020 Series
DYNA 8200 -- DYNC 12000 Series
DYNA 8400 -- DYNC 14800 Series
These actuators do not have a potentiometer feedback
transducer.
NOTE
A warm engine is normally more stable than a cold one. If the
governor is adjusted on a warm engine, turn the adjustment
potentiometers counterclockwise 5% (1/2 div.) to ensure a
stable engine when started cold.
CAUTION
As a safety measure, the engine should be equipped with an
independentoverspeedshutdowndeviceintheeventoffailure
which may render the governor inoperative.

7. DYNA 8000 SERIES TROUBLESHOOTING CHART
7.1 PROBLEM: GOVERNOR IS COMPLETELY DEAD AND ACTUATOR LEVER STAYS AT MINIMUM POSITION
WHEN POWER IS APPLIED TO GOVERNOR.
Check battery connections and contacts for turning power
ON to the controller.
Correct and free linkage.
Check pole tip gap over gear tooth. Should be
.037 mm ±0.127 mm (0.015" ±0.005").
If there is an open or shorted coil, replace the magnetic
pickup.
If there is continuity to case, replace the magnetic pickup.
If the actuator still does not move to full stroke, continue
with steps below.
If actuator coil is open or shorted to case, replace actuator.
If governor still does not operate, continue with steps below.
If continuity is detected, replace the actuator.
If 8 VDC is not present, replace the controller.
If 4 VDC is not present, replace the controller.
7.1.1 Check battery voltage at terminals 1 and 2 on
controller. Terminal 1 is positive.
7.1.2 Check for proper linkage setup.
7.1.3 Magnetic pickup signal absent or too low.
Measure AC voltage across terminals 10 and 11
while cranking the engine. Voltage should be
min. 2.5 VAC. Note: The voltmeter should have
an impedance of 5000 ohms/volts or higher.
7.1.4 Measure the resistance of the magnetic pickup
coil. This should be above 150 ohms.
7.1.5 Measure the resistance of each pin to the metal
case of the magnetic pickup. No continuity
should be evident.
7.1.6 DC SUPPLY OFF. Place an insulated jumper
between terminals 2 and 3 (TP1 & TP2). With DC
ON, the actuator should go to full stroke. DC
voltage at terminals 4 and 5 should be within 3
volts of the supply.
7.1.7 Measure actuator coil resistance:
DYNA 8000
12 VDC unit. Coil resistance 0.75 ±0.2 ohms.
24 VDC unit. Coil resistance 2.3 ±0.4 ohms.
DYNA 8200
12 VDC unit. Coil resistance .710 ±0.2 ohms.
24 VDC unit. Coil resistance 1.600 ±0.4 ohms.
DYNA 8400
24 VDC unit. Coil resistance 1.630 ±0.4 ohms.
7.1.8 Measuring the resistance of each coil lead to
the actuator case should indicate an open circuit
on a low scale of the ohm meter.
7.1.9 With the DC to the governor ON and the engine
OFF, measure the DC voltage from terminal 6 (+)
to terminal 2 (-). This should be approx. 8 VDC.
7.1.10 Between terminal 7 (+) to terminal 2 (-), the
voltage should be approx. 4 VDC.
Corrective Action
Means of Detection
13

Means of Detection Corrective Action
Verify and correct wiring as necessary.
Verify and correct wiring as necessary.
Replace controller.
If continuity is detected, replace the controller.
Turn DC power ON to the governor if the actuator is now
normal. Proceed to step 7.3.1.
Means of Detection
Check wiring.
Correct wiring.
Verify that the drain shield wire is isolated from ground
at the potentiometer.
Correct the wiring.
Verify and correct wiring.
Corrective Action
If nominal voltage is present, wiring is correct.
Check battery and charging system.
Correct wiring.
Connect power leads directly to the battery.
14
7.3 PROBLEM: IMPROPER OPERATION FROM REMOTE SPEED POTENTIOMETER
7.4 PROBLEM: ERRATIC GOVERNOR OPERATION
7.4.1 Measure DC voltage at 1 and 2 on controller
terminal strip. Normal battery voltage should
be indicated.
7.4.2 Low battery voltage 20% below rated can
cause erratic operation.
7.4.3 RFI noise due to incorrect shielding.
7.4.4 RFI noise fed through power supply leads.
7.3.1 Investigate wiring to remote speed
potentiometer for open or shorted circuits.
7.3.2 If the leads at terminals 6 and 7 to the remote
speed potentiometer are reversed, speed
control by the remote speed potentiometer
will be reversed.
7.3.3 Lead wire to remote speed setting potentiometer
should be 3-wire shielded cable.
7.3.4 If terminal 7 lead to the remote speed
potentiometer is open, engine speed will go high.
7.3.5 If lead 9 (wiper lead to remote potentiometer) is
open, there will be no control by the remote
speed potentiometer.
7.3.6 If lead 6 to the clockwise terminal of the remote
speed potentiometer is open, speed will remain
at the value set in the controller.
7.2.1 Check magnetic pickup leads for proper
shielded wire or open shield.
7.2.2 Be sure there is no jumper between terminals
2 and 3.
7.2.3 Failsafe circuit in the controller may be
damaged or defective.
7.2.4 With DC power OFF remove leads at actuator.
Check continuity of each terminal to case.
There should be no continuity between any
terminal and case of the controller.
7.2.5 If remote speed potentiometer has been
connected to terminals 6, 7 and 9 of the
controller, DISCONNECT THESE LEADS.
7.2 PROBLEM: ACTUATOR GOES TO FULL STROKE WHEN DC POWER IS TURNED ON
(ENGINE IS NOT OPERATING).
Corrective Action
Means of Detection

7.5 PROBLEM: SLOW, SMALL AMPLITUDE HUNTING OF SPEED OR FREQUENCY
Means of Detection
7.5.1 Sticking or very loose linkage.
Corrective Action
Correct Linkage.
Means of Detection
7.6.1 Verify calibration settings of the controller.
Corrective Action
Readjust settings as necessary.
7.6 PROBLEM: FAST OSCILLATION OF GOVERNOR LINKAGE
Means of Detection Corrective Action
Check fuel to engine. Check for correct wiring to the
automatic shutdown circuits.
Check fuel lines for leaks.
7.7.1 Make sure fuel is available.
7.7.2 Air may be trapped in fuel line.
7.7.3 Try to operate engine manually.
7.7 PROBLEM: ENGINE WILL NOT START -- ACTUATOR GOES TO FULL FUEL DURING CRANKING
8. ACTUATOR INSTALLATION DIMENSIONS
15
DYNC-11020-000
STANDARD
ACTUATOR —
CLOCKWISE
ROTATION
DYNC-11020-300
SIDE MOUNTED
ACTUATOR —
CLOCKWISE
ROTATION

16
DYNC-11024-000
ACTUATOR —
COUNTERCLOCKWISE
ROTATION
DYNC-11024-300
SIDE MOUNTED
ACTUATOR —
COUNTERCLOCKWISE
ROTATION
DYNC-12000-000

DYNC-14800-000
TERMINAL STRIP CONNECTION
DYNC-14801-000
2-PIN MS CONNECTOR CONNECTION
17
DYNC-11020-401
UL APPROVAL, HAZARDOUS DUTY, CLASS 1, DIVISION 2, GROUP D
CLOCKWISE UNIT

DYNC-11024-400
UL APPROVAL, HAZARDOUS DUTY, CLASS 1, DIVISION 2, GROUP D
COUNTERCLOCKWISE UNIT
DYNC-14800-400
UL APPROVAL, HAZARDOUS DUTY, CLASS 1, DIVISION 2, GROUP D
F-23721-5
An Invensys company
Barber-Colman DYNA Products
1354 Clifford Avenue (Zip 61111) Telephone (815) 637-3000
P.O. Box 2940 Facsimile (815) 877-0150
Loves Park, IL 61132-2940 www.dynaproducts.com
United States of America
In Europe contact: Barber-Colman GmbH
Am Neuen Rheinhafen 4, D-67346 Speyer, Germany
Telephone (49) 6232 29903, Facsimile (49) 6232 299155
In Japan contact: Ranco Japan Ltd.
Shiozaki Bldg. 7-1, 2-chome, Hirakawa-Cho, Chiyoda-Ku
Tokyo 102, Japan
Telephone (81) 3 3261 4293, Facsimile (81) 3 3264 4691
This manual suits for next models
2
Table of contents
Other Barber-Colman Controllers manuals
Popular Controllers manuals by other brands

Texas Instruments
Texas Instruments MSP430x5 series user guide

Gossen MetraWatt
Gossen MetraWatt R6000 installation instructions

Intermatic
Intermatic FREEZE SENTRY PF1103 Installation, operation & service manual

Balmar
Balmar Max Charge MC-612 Installation and operation manual

Samson
Samson 5821 manual

Ibiza
Ibiza LC12DMX user manual

Danfoss
Danfoss AMV 410 installation guide

HEIDENHAIN
HEIDENHAIN TNC 320 operating instructions

Emerson
Emerson Dixell XR20-30-60-70T Quick reference guide

Votronic
Votronic 1247 Installation and operating manual

Tekram Technology
Tekram Technology HOYA IrWave 520UK USB-IrDA installation guide

Panasonic
Panasonic AFP7CPS Series user manual