Bard WA7013 User manual

INSTALLATION INSTRUCTIONS
WALL MOUNTED
PACKAGE AIR CONDITIONERS
Model
WA7013
Manual : 2100-359B
Supersedes: 2100-359A
File: Volume III Tab 16
Date: 05-13-02
Bard Manufacturing Company
Bryan, Ohio 43506
Since 1914...Moving ahead just as
planned.
© Copyright2002

Contents
Figures
Figure 1 Unit Dimensions...................................... 3
Figure 2 Mounting Instructions.............................. 7
Figure 3 Electric Heat Clearance .......................... 8
Figure 4 Wall Mounting Instructions...................... 9
Figure 5 Wall Mounting Instructions...................... 9
Figure 6 Common Wall Mounting Installations.... 10
Figure 7 Unit 24V Terminal Board ....................... 12
Figure 8 Fan Blade Setting ................................. 15
Tables
Table 1 Electric Heat Table .................................. 2
Table 2 Electrical Specifications .......................... 4
Table 3 Thermostat Wire Size ............................11
Table 4 Wall Thermostat and Subbase
Combinations .........................................11
Table 5 Fan Blade Dimensions.......................... 15
Table 6 Indoor Blower Performance .................. 15
Table 7 Refrigerant Charge ............................... 15
Table 8 Rated CFM and Rated ESP.................. 15
Table 9 Maximum ESP of Operation
Electric Heat Only ................................. 15
Table 10 Pressure Table ...................................... 16
Table 11 Optional Accessories ............................ 16
Getting Other Information and Publications .......... 1
Wall Mount General Information ............................. 2
Air Conditioning Wall Mount Model Nomenclature .. 2
Shipping Damage .................................................... 5
General ................................................................ 5
Duct Work................................................................ 5
Condensate Drain.................................................... 5
Installation Instructions ........................................... 6
Wall Mounting Information....................................... 6
Mounting the Unit .................................................... 6
Wiring – Main Power ..............................................11
Wiring – Low Voltage Wiring ..................................11
Start Up ................................................................... 15
Important Installer Note ......................................... 13
Crankcase Heaters................................................ 13
High Pressure Switch ............................................ 13
Three Phase Scroll Compressor Start Up ............. 13
Service Hints ......................................................... 13
Sequence of Operation.......................................... 13
Compressor Control Module.................................. 13
Adjustments........................................................... 14
Phase Monitor ....................................................... 14
Pressure Service Ports .......................................... 14
Troubleshooting ..................................................... 15
Fan Blade Setting Dimensions .............................. 15
Removal of Fan Shroud......................................... 15
Refrigerant Charge ................................................ 15
Pressure Table....................................................... 16
Optional Accessories............................................. 16

Manual 2100-359
Page 1
Getting Other Information and Publications
These publications can help you install the air conditioner
or heat pump. You can usually find these at your local
library or purchase them directly from the publisher. Be
sure to consult current edition of each standard.
National Electrical Code........................ ANSI/NFPA 70
Standard for the Installation................... ANSI/NFPA
90A
of Air Conditioning and
VentilatingSystems
Standard for Warm Air .......................... ANSI/NFPA
90B
Heating and Air
ConditioningSystems
Load Calculation for .............................. ACCA Manual J
Residential Winter and
Summer Air Conditioning
Duct Design for Residential................... ACCA Manual
D Winter and Summer Air Conditioning
and Equipment Selection
For more information, contact these
publishers:
ACCA Air Conditioning Contractors of America
1712 New Hampshire Ave. N.W.
Washington, DC 20009
Telephone: (202) 483-9370
Fax: (202) 234-4721
ANSI American National Standards Institute
11 West Street, 13th Floor
New York, NY 10036
Telephone: (212) 642-4900
Fax: (212) 302-1286
ASHRAE American Society of Heating Refrigerating,
and Air Conditioning Engineers, Inc.
1791 Tullie Circle, N.E.
Atlanta, GA 30329-2305
Telephone: (404) 636-8400
Fax: (404) 321-5478
NFPA National Fire Protection Association
Batterymarch Park
P.O. Box 9101
Quincy, MA 02269-9901
Telephone: (800) 344-3555
Fax: (617) 984-7057
Manufactured under the following U.S. patent numbers:
5,485,878; 5,301,777; 5,002,116; 4,924,934;
4,875,520; 4,825,936

Manual 2100-359
Page 2
WALL MOUNT GENERAL INFORMATION
AIRCONDITIONINGWALLMOUNTMODELNOMENCLATURE
WA 70 1 3 A 10 X N X X X A
TABLE 1
ELECTRICHEATTABLE
sledoM
WK
YLNOA3107AWYLNOB3107AW
1-V0421-V8021-V0421-V802
SPMAHUTBSPMAHUTBSPMAHUTBSPMAHUTB
0.58.02050,711.81008,21------------
0.9------------7.12006,037.81030,32
0.016.14031,432.63006,52------------
MODEL NUMBER CONTROLMODULES
CAPACITY
60 - 5 Ton
VOLTS&PHASE
A - 230/208/60/1
B - 230/208/60/3
REVISIONS
KW
VENTILATIONOPTIONS
B - Blank-off Plate
FILTEROPTIONS
N - NoFilter
COLOROPTIONS
X - Beige(Standard)
1 - White
2 - Mesa Tan
4 - BuckeyeGray
COILOPTIONS
X - Standard
1 - PhenolicCoatedEvaporator
2 - Phenolic Coated Condenser
3 - PhenolicCoatedEvaporator
andCondenser
OUTLETOPTIONS
X - Front (Standard)
FEATURE CODE
3 - 3 ton air openings
on 5 ton cabinet

Manual 2100-359
Page 3
FIGURE 1
UNITDIMENSIONS
MIS-1456

Manual 2100-359
Page 4
j
k
l
Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors.
Based on 75°C copper wire. All Wiring must conform to NEC and all local codes.
These “minimum Circuit Ampacity”values are to be used for sizing the field power conductors. Refer to the National Electric Code (latest
revision), article 310 for power conductor sizing. CAUTION: When more than one field power conductor circuit is run through one conduit,
the conductors must be derated. Pay special attention to note 8 of table 310 regarding Ampacity Adjustment Factors when more than 3
conductors are in a raceway.
ledoM
TIUCRICELGNIS TIUCRICLAUD
detaR
&stloV
esahP
.oN
dleiF
rewoP
stiucriC
3
muminiM
tiucriC
yticapmA
1
mumixaM
lanretxE
roesuF
.tkC
rekaerB
2
dleiF
rewoP
eriW
eziS
2
dnuorG
eriW
eziS
3
muminiM
tiucriC
yticapmA
1
mumixaM
esuFlanretxE
ro
rekaerB.tkC
2
rewoPdleiF
eziSeriW
2
dnuorG
eziSeriW
ATKCBTKCATKCBTKCATKCBTKCATKCBTKC
Z0A3107AW
01A 1-802/032 1
1
84
95
06
06
8
6
01
01
A/N
A/N
A/N
A/N
A/N
A/N
A/N
A/N
A/N
A/N
A/N
A/N
A/N
A/N
A/N
A/N
Z0B3107W
90B 3-802/032 1
1
63
63
05
05
8
8
01
01
A/N
A/N
A/N
A/N
A/N
A/N
A/N
A/N
A/N
A/N
A/N
A/N
A/N
A/N
A/N
A/N
TABLE 2
ELECTRICALSPECIFICATIONS

Manual 2100-359
Page 5
CONDENSATE DRAIN
A plastic drain hose extends from the drain pan at the top
of the unit down to the unit base. There are openings in
the unit base for the drain hose to pass through. In the
event the drain hose is connected to a drain system of
some type, it must be an open or vented type system to
assure proper drainage.
A 1/4 inch clearance to combustible material for the first
three feet of duct attached to the outlet air frame is
required. See Wall Mounting Instructions and Figures 3
and 3A for further details.
Ducts through the walls must be insulated and all joints
taped or sealed to prevent air or moisture entering the
wallcavity.
Some installations may not require any return air duct. A
metallic return air grille is required with installations not
requiring a return air duct. The spacing between louvers
on the grille shall not be larger than 5/8 inch.
NOTE: If no return air duct is used, applicable
installation codes may limit this cabinet to
installation only in a single story structure.
Any grille that meets with 5/8 inch louver criteria may be
used. It is recommended that Bard Return Air Grille Kit
RG2 through RG5 or RFG2 through RFG5 be installed
when no return duct is used. Contact distributor or
factory for ordering information. If using a return air
filter grille, filters must be of sufficient size to allow a
maximum velocity of 400 fpm.
Design the duct work according to methods given by the
Air Conditioning Contractors of America (ACCA).
When duct runs through unheated spaces, it should be
insulated with a minimum of one inch of insulation. Use
insulation with a vapor barrier on the outside of the
insulation. Flexible joints should be used to connect the
duct work to the equipment in order to keep the noise
transmission to a minimum.
These instructions and any instructions packaged with
any separate equipment, required to make up the entire
air conditioning system should be carefully read before
beginning the installation. Note particularly any tags and/
or labels attached to the equipment.
Size of unit for a proposed installation should be based
on heat loss calculation made according to methods of
Air Conditioning Contractors of America (ACCA). The
air duct should be installed in accordance with the
Standards of the National Fire Protection Association for
the Installation of Air Conditioning and Ventilating
Systems of Other Than Residence Type, NFPA No. 90A,
and Residence Type Warm Air Heating and Air
Conditioning Systems, NFPA No. 90B. Where local
regulations are at a variance with instructions, installer
should adhere to local codes.
DUCT WORK
All duct work, supply and return, must be properly sized
for the design air flow requirement of the equipment. Air
Conditioning Contractors of America (ACCA) is an
excellent guide to proper sizing. All duct work or
portions thereof not in the conditioned space should be
properly insulated in order to both conserve energy and
prevent condensation or moisture damage.
While these instructions are intended as a general
recommended guide, they do not supersede any national
and/or local codes in any way. Authorities having
jurisdiction should be consulted before the installation is
made. See Page 1 for information on codes and
standards.
SHIPPING DAMAGE
Upon receipt of equipment, the carton should be checked
for external signs of shipping damage. If damage is
found, the receiving party must contact the last carrier
immediately, preferably in writing, requesting inspection
by the carrier’s agent.
GENERAL
The equipment covered in this manual is to be installed
by trained, experienced service and installation
technicians.
The refrigerant system is completely assembled and
charged. All internal wiring is complete.
The unit is designed for use with or without duct work.
Flanges are provided for attaching the supply and return
ducts.
These instructions explain the recommended method to
install the air cooled self-contained unit and the electrical
wiring connections to the unit.

Manual 2100-359
Page 6
INSTALLATION INSTRUCTIONS
WALL MOUNTING INFORMATION
1. Two holes for the supply and return air openings must
be cut through the wall as shown in Figure 1.
2. On wood frame walls, the wall construction must be
strong and rigid enough to carry the weight of the unit
without transmitting any unit vibration.
WARING
Fire hazard can result if 1/4 inch clearance to
combustible materials for supply air duct is not
maintained. See Figure 2.
3. Concrete block walls must be thoroughly inspected to
insure that they are capable of carrying the weight of
the installed unit.
MOUNTING THE UNIT
1. These units are secured by wall mounting brackets
which secure the unit to the outside wall surface at
both sides. A bottom mounting bracket is provided
for ease of installation, but is not required.
2. The unit itself is suitable for 0 inch clearance, but the
supply air duct flange and the first 3 feet of supply air
duct require a minimum of 1/4 inch clearance to
combustible material. If a combustible wall use a
minimum of 30-1/2” x 10-1/2” dimensions for sizing.
However it is generally recommended that a 1 inch
clearance is used for ease of installation and
maintaining the required clearance to combustible
material. The supply air opening would then be
32” x 12”. See Figures 2 and 3 for details.
WARNING
Failure to provide the 1/4 inch clearance
between the supply duct and a combustible
surface for the first 3 feet of duct can result in
fire causing damage, injury or death.
3. Locate and mark lag bolt locations and bottom
mounting bracket location. See Figure 2.
4. Mount bottom mounting bracket.
5. Hook top rain flashing under back bend of top. Top
rain flashing is shipped secured to the right side of the
back.
6. Position unit in opening and secure with 5/16 lag
bolts; use 7/8 inch diameter flat washers on the lag
bolts.
7. Secure rain flashing to wall and caulk across entire
length of top. See Figure 2.
8. For additional mounting rigidity, the return air and
supply air frames or collars can be drilled and
screwed or welded to the structural wall itself
(depending upon wall construction). Be sure to
observe required clearance if combustible wall.
9. On side by side installations, maintain a minimum of
20 inches clearance on right side to allow access to
control panel and heat strips, and to allow proper
airflow to the outdoor coil. Additional clearance may
be required to meet local or national codes.

Manual 2100-359
Page 7
FIGURE 2
MOUNTINGINSTRUCTIONS
MIS-1445

Manual 2100-359
Page 8
FIGURE 3
ELECTRICHEATCLEARANCE
SIDE SECTION VIEW OF SUPPLY AIR DUCT FOR WALL MOUNTED UNIT
SHOWING 1/4 INCH CLEARANCE TO COMBUSTIBLE SURFACES.
MIS-277
WARNING
A minimum of 1/4 inch clearance must be maintained between the
supply air duct and combustible materials. This is required for the
first 3 feet of ducting.
It is important to insure that the 1/4 inch minimum spacing is
maintained at all points.
Failure to do this could result in overheating the combustible material
and may result in a fire causing damage, injury or death.

Manual 2100-359
Page 9
FIGURE 5
WALLMOUNTINGINSTRUCTIONS
MIS-549
SEE UNIT DIMENSIONS, FIGURE 1,
FOR ACTUAL DIMENSIONS
ATTACH TO TOP
PLATE OF WALL
1.000”CLEARANCE
ALL AROUND
INTERIOR FINISHED WALL
OVER FRAME
1.000”CLEARANCE
ALL AROUND
EXTERIORFINISHED
WALL OVER FRAME
ATTACH TO BOTTOM
PLATE OF WALL
FRAMING MATERIAL
2 X 4’S, 2 X 6’S AND/OR
STRUCTURAL STEEL
THIS STRUCTURAL MEMBER LOCATED TO MATCH
STUD SPACING FOR REST OF WALL. A SECOND
MEMBER MAY BE REQUIRED FOR SOME WALLS.
RETURN DUCT
OPENING
SUPPLY DUCT
OPENING
FIGURE 4
WALLMOUNTINGINSTRUCTIONS
MIS-1548
BOTTOM MOUTING BRACKET.
MOUNT ON WALL BEFORE
INSTALLING UNIT.
RETURN AIR
OPENING
SUPPLY AIR
OPENING
WALL STRUCTURE
FACTORY SUPPLIED RAIN
FLASHING. MOUNT ON UNIT
BEFOREINSTALLATION.
SEE FIGURE 3 –MOUNTING INSTRUCTIONS
SUPPLY AIR
OPENING
RETURN AIR
OPENING
SUPPLY AIR
OPENING
RETURN AIR
OPENING

Manual 2100-359
Page 10
FIGURE 6
COMMONWALLMOUNTINGINSTALLATIONS
FREE AIR FLOW NO DUCT DUCTED SUPPLY RETURN AT UNIT
FALSE WALL INSTALLATION CLOSETINSTALLATION
MIS-550

Manual 2100-359
Page 11
WIRING – MAIN POWER
Refer to the unit rating plate for wire sizing information
and maximum fuse or “HACR” type circuit breaker size.
Each outdoor unit is marked with a “Minimum Circuit
Ampacity”. This means that the field wiring used must be
sized to carry that amount of current. Depending on the
installed KW of electric heat, there may be two field
power circuits required. If this is the case, the unit serial
plate will so indicate. All models are suitable only for
connection with copper wire. Each unit and/or wiring
diagram will be marked “Use Copper Conductors Only”.
These instructions must be adhered to. Refer to the
National Electrical Code (NEC) for complete current
carrying capacity data on the various insulation grades of
wiring material. All wiring muse conform to NEC and all
local codes.
The electrical data lists fuse and wire sizes (75° C
copper) for all models including the most commonly used
heater sizes. Also shown are the number of field power
circuits required for the various models with heaters.
The unit rating plate lists a “Maximum Time Delay Relay
Fuse” or “HACR” type circuit breaker that is to be used
with the equipment. The correct size must be used for
proper circuit protection and also to assure that there will
be no nuisance tripping due to the momentary high
starting current of the compressor motor.
The disconnect access door on this unit may be locked to
prevent unauthorized access to the disconnect. To
convert for the locking capability, bend the tab locate in
the bottom left hand corner of the disconnect opening
under the disconnect access panel straight out. This tab
will now line up with the slot in the door. When shut a
padlock may be placed through the hole in the tab
preventingentry.
Five (5) wires should be run from thermostat subbase to
the 24V terminal board in the unit. A five conductor, 18
gauge copper, color-coded thermostat cable is
recommended. The connection points are shown in
Figure 7:
See “Start Up” section for important information on three
phase scroll compressor start ups.
WIRING – LOW VOLTAGE WIRING
230 / 208V, 1 phase and 3 phase equipment dual primary
voltage transformers. All equipment leaves the factory
wired on 240V tap. For 208V operation, reconnect from
240V to 208V tap. The acceptable operating voltage
range for the 240 and 208V taps are:
TAP RANGE
240 253 –216
208 220 –187
NOTE: The voltage should be measured at the field
power connection point in the unit and while the
unit is operating at full load (maximum
amperage operating condition).
remrofsnarT AVALFeguaGeriWteeFnI
553.2
eguag02 eguag81 eguag61 egaug41 egaug21
5406 001 061 052
TABLE 3
THERMOSTATWIRESIZE
TABLE 4
WALLTHERMOSTATANDSUBBASECOMBINATIONS
tatsomrehTesabbuSserutaeFetanimoderP
200-3048
1113F78T
300-4048
0221A935Q
loocegats1,taehegats1
no-otua:naFlooc-ffo-taeh:metsyS
140-3048
C4308T
---loocegats1,taehegats1
no-otua:naFlooc-ffo-taeh:metsyS
910-3048
0671C478T
210-4048
1001A476Q
taehegats2,loocegats1
no-otua:naFlooc-otua-taeh:metsyS
120-3048
4391D478T
210-4048
1001A476Q
taehegats2,loocegats2
no-otua:naFlooc-otua-taeh:metsyS
940-3048
083-39F1
---taehegats2,loocegats2
gnimmargorpyad7cinortcelE
340-3048
002-MC --- loocegats1,taehegats1
no-otua:naFlooc-ffo-taeh:metsyS

Manual 2100-359
Page 12
FIGURE 7
UNIT24VTERMINALBOARD
MIS-1373B

Manual 2100-359
Page 13
START UP
IMPORTANT INSTALLER NOTE
For improved start up performance wash the indoor coil
with a dish washing detergent.
CRANKCASE HEATERS
These units are not provided with crankcase heat. These
units utilize scroll compressors which do not require
crankcase heat in this application.
HIGH PRESSURE SWITCH
The models are supplied with a remote reset high
pressure switch. If tripped, this pressure switch may be
reset by turning the thermostat off then back on again.
THREE PHASE SCROLL COMPRESSOR
START UP INFORMATION
Scroll compressors, like several other types of
compressors, will only compress in one rotational
direction. Direction of rotation is not an issue with single
phase compressors since they will always start and run in
the proper direction.
However, three phase compressors will rotate in either
direction depending upon phasing of the power. Since
there is a 50-50 chance of connecting power in such a
way as to cause rotation in the reverse direction,
verification of proper rotation must be made.
Verification of proper rotation direction is made by
observing that suction pressure drops and discharge
pressure rises when the compressor is energized.
Reverse rotation also results in an elevated sound level
over that with correct rotation, as well as, substantially
reduced current draw compared to tabulated values.
Verification of proper rotation must be made at the time
the equipment is put into service. If improper rotation is
corrected at this time there will be no negative impact on
the durability of the compressor. However, reverse
operation for over one hour may have a negative impact
on the bearing due to oil pump out.
NOTE: If compressor is allowed to run in reverse
rotation for several minutes, the compressor’s
internal protector will trip.
All three phase ZR3 compressors are wired identically
internally. As a result, once the correct phasing is
determined for a specific system or installation,
connecting properly phased power leads to the same
Fusite terminal should maintain proper rotation direction.
The direction of rotation of the compressor may be
changed by reversing any two line connections to the
unit.
SERVICE HINTS
1. Caution homeowner to maintain clean air filters at all
times. Also, not to needlessly close off supply and
return air registers. This reduces air flow through the
system, which shortens equipment service life as well
as increasing operating costs.
2. Switching to heating cycle at 75° F or higher outside
temperature may cause a nuisance trip of the remote
reset high pressure switch. Turn thermostat off then
on to reset the high pressure switch.
3. Check all power fuses or circuit breakers to be sure
they are the correct rating.
4. Periodic cleaning of the outdoor coil to permit full
and unrestricted airflow circulation is essential.
SEQUENCE OF OPERATION
COOLING – Circuit R-Y makes at thermostat pulling in
compressor contactor, starting the compressor and
outdoor motor. The G (indoor motor) circuit is
automatically completed on any call for cooling operation
or can be energized by manual fan switch on subbase of
constant air circulation. On all 230 volt units there is a
one minute off delay on the blower motor. 460 volt
models do not have an off delay.
COMPRESSOR CONTROL MODULE
The compressor control module is standard on the models
covered by this manual. The compressor control is an
anti-short cycle/lockout timer with high and low pressure
switch monitoring and alarm relay output.
Adjustable Delay On Make And Break Timer
On initial power up or any time power is interrupted to
the unit the delay on make period begins which will be 2
minutes plus 10% of the delay on break setting. When
the delay on make is complete and the high pressure
switch (and low pressure switch if employed) is closed,
the compressor contactor is energized. Upon shutdown
the delay or break timer starts and prevents restart until
the delay on break and delay on make periods have
expired.
During routine operation of the unit with no power
interruptions the compressor will operate on demand with
no delay.

Manual 2100-359
Page 14
PRESSURE SERVICE PORTS
High and low pressure service ports are installed on all
units so that the system operating pressures can be
observed. A pressure table can be found later in the
manual covering all models. It is imperative to match the
correct pressure table to the unit by model number.
Low Pressure Switch, Bypass, and Lockout
Sequence
If the low pressure switch opens for more than 120
seconds, the compressor contactor will de-energize and
go into a soft lockout. Regardless the state of the low
pressure switch, the contactor will reenergize after the
delay on make time delay has expired. If the low
pressure switch remains open, or opens again for longer
than 120 seconds the unit will go into manual lockout
condition and the alarm relay circuit will energize.
Recycling the wall thermostat resets the manual lockout.
Alarm Relay Output
Alarm terminal is output connection for applications
where alarm relay is employed. This terminal is powered
whenever compressor is locked out due to HPC or LPC
sequences as described.
NOTE: Both high and low pressure switch controls are
inherently automatic reset devices. The high
pressure switch and low pressure switch cut out
and cut in settings are fixed by specific air
conditioner or heat pump unit model. The
lockout features, both soft and manual, are a
function of the Compressor Control Module.
PHASE MONITOR
All units with three phase scroll compressors are
equipped with a 3 phase line monitor to prevent
compressor damage due to phase reversal.
The phase monitor in this unit is equipped with two
LEDs. If the Y signal is present at the phase monitor and
phases are correct the green LED will light.
If phases are reversed, the red fault LED will be lit and
compressor operation is inhibited.
If a fault condition occurs, reverse two of the supply
leads to the unit. Do not reverse any of the unit factory
wires as damage may occur.
High Pressure Switch and Lockout Sequence
If the high pressure switch opens, the compressor
contactor will de-energize immediately. The lockout
timer will go into a soft lockout and stay in soft lockout
until the high pressure switch closes and the delay on
break time has expired. If the high pressure switch
opens again in this same operating cycle the unit will
go into manual lockout condition and the alarm relay
circuit will energize. Recycling the wall thermostat
resets the manual lockout.
ADJUSTMENTS
Adjustable Delay on Make and Delay on Break
Timer
The potentiometer is used to select Delay on Break time
from 30 seconds to 5 minutes. Delay on Make (DOM)
timing on power-up and after power interruptions is equal
to 2 minutes plus 10% of Delay on Break (DOB) setting:
0.5 minute (30 seconds) DOB = 123 second DOM
1.0 minute (60 seconds) DOB = 126 second DOM
2.0 minute (120 seconds) DOB = 132 second DOM
3.0 minute (180 seconds) DOB = 138 second DOM
4.0 minute (240 seconds) DOB = 144 second DOM
5.0 minute (300 seconds) DOB = 150 second DOM
During routine operation of the unit with no power
interruptions the compressor will operate on demand with
no delay.
Typical Settings for Dual Unit Installation:
Unit No. 1: DOB set at 2 minutes, and DOM is 132
seconds
Unit No. 2: DOB set at 4 minutes, and DOM is 144
seconds

Manual 2100-359
Page 15
The suction line temperatures in table above are based
upon 80° F dry bulb / 67° F wet bulb (50% R.H.)
temperature and rated airflow across the evaporator
during cooling cycle.
REMOVAL OF FAN SHROUD
1. Disconnect all power to the unit.
2. Remove the screws holding both grilles, one on each
side of unit, and remove grilles.
3. Remove screws holding fan shroud to condenser and
bottom. Nine (9) screws.
4. Unwire condenser fan motor.
FIGURE 8
TROUBLESHOOTING
5. Slide complete motor, fan blade, and shroud assembly
out the left side of the unit.
6. Service motor/fan as needed.
7. Reverse steps to reinstall.
REFRIGERANT CHARGE
The correct system R-22 charge is shown on the unit
rating plate. Optimum unit performance will occur with a
refrigerant charge resulting in a suction line temperature
(6” from compressor) as shown in Table 7.
TABLE 5
ledoM noisnemiD A
3107AW52.1
TABLE 6
INDOORBLOWERPERFORMANCE
CFM
@
230V
.P.S.E HnI
2
O
3107AW
deepShgiH
lioCyrDlioCteW
0.1.2.
5771 5761 5751
0061 5251 5241
TABLE 7
REFRIGERANTCHARGE
ledoMwolfriA DO59 erutarepmeT DO28 erutarepmeT
107W007106-8585-65
TABLE 8
RATEDCFM ANDESP
ledoM detaR MFC detaR PSE dednemmoceR egnaRwolfriA
3107AW524102.05241-5771 j
jRated CFM & ESP on High Speed tap with
14 x 28 return air filter grille
TABLE 9
MAXIMUMESPOFOPERATION
ELECTRICHEATONLY
Values shown are for units equipped with
standard 1”throwaway filters or 1”washable
filters. Derate ESP by .15 for 2”pleated filters.
SLEDOMPSE
W3107A 01A 90B 3.3.
FAN BLADE SETTING DIMENSIONS
Shown in Figure 10 is the correct fan blade setting
dimension for proper air delivery across the outdoor coil.
Any service work requiring removal or adjustment in the
fan and/or motor area will require that the dimensions
below be checked and blade adjusted in or out on the
motor shaft accordingly.

Manual 2100-359
Page 16
TABLE 11
OPTIONALACCESSORIES
WA7013A
WA7013B
traP rebmuNnoitpircseD
51-CMCtiKtratSX
A90-BCMW B70-BCMW tiKrekaerBtiucriC tiKrekaerBtiucriC XX
Low side pressure ± 2 PSIG
High side pressure ± 5 PSIG
Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to
correct operating charge being in the system, the charge should be removed, system evacuated and
recharged to serial plate instructions.
COOLING
TABLE 10
PRESSURETABLE
Air Temperature Entering Outdoor Coil °F
ledoM riAnruteR erutarepmeTerusserP5708580959001501011511
A3107AW
BD.ged57 BW.ged26 ediSwoL ediShgiH 86512 86822 96242 07652 17272 27982 37503 47423 57343
BD.ged08 BW.ged76 ediSwoL ediShgiH 37022 37432 47842 57362 67972 77692 87313 97233 08253
BD.ged58 BW.ged27 ediSwoL ediShgiH 67822 67242 77752 87272 97982 08603 18423 28443 38463
B3107AW
BD.ged57 BW.ged26 ediSwoL ediShgiH 26412 36032 46742 56562 66082 76992 86613 96333 07153
BD.ged08 BW.ged76 ediSwoL ediShgiH 76022 86632 96452 07172 17782 27603 37603 37423 57063
BD.ged58 BW.ged27 ediSwoL ediShgiH 27522 37342 47162 57972 67792 77613 87533 97353 08273
Table of contents
Other Bard Air Conditioner manuals

Bard
Bard WL701 User manual

Bard
Bard W48A2PQ Quick guide

Bard
Bard WL701-B User manual

Bard
Bard Fusion-Tec User manual

Bard
Bard W38A1 User manual

Bard
Bard PA13242-A User manual

Bard
Bard P1124A3 User manual

Bard
Bard EIFM-3C User manual

Bard
Bard FUSION-TEC HR Series Operating instructions

Bard
Bard I-TEC I30A1D User manual

Bard
Bard WA121 User manual

Bard
Bard MEGA-TEC W180B Operating instructions

Bard
Bard W17A1 User manual

Bard
Bard D25A2PA Quick guide

Bard
Bard I30A1DA User manual

Bard
Bard 11EER WA Series User manual

Bard
Bard D36A2P/BLD.10304 Quick guide

Bard
Bard WA3S3 User manual

Bard
Bard WA4822 User manual

Bard
Bard Wall-Mount CT Series User manual