Installation Manual
AURO CRESNET®
© 2020
basalte v4.0
Cresnet® power usage: 0.15 W
Ambient temperature:
Operation: -5°C to 45°C
Storage: -15°C to 55°C
Transport: -15°C to 55°C
Max. humidity: 93% relative humidity,
no moisture condensation
Protection class: II
Type of protection: IP 20
Certification: CE
Important advice
• Never connect the device to 110 V / 230 V or in the vicinity of. Make sure to maintain the distance to them
specified in the applicable standards and regulations.
• Do not paint over the central IR window since this will prevent Auro to operate correctly.
Installation and commissioning
• Auro is intended for ceiling mounting. In order to install Auro, an opening should be made with a diameter of
43 mm (1.7 in).
• Connect the bus line according the Crestron® installation guidelines (Red = 24, White = Y, Blue = Z, Black = G ).
• In SIMPL Windows, an Auro Cresnet Configuration’ module is used for every Auro motion detector in the
project.
• In order to identify the Auro on the Cresnet bus, the recessed button on the back is needed.
• After a bus voltage failure or a bus reset, Auro will not be ready for operation for at least 5 seconds.
• Note that the recessed button is not accessible after physical installation.
Technical data
Features:
• PIR motion sensor
• lux sensor (0180-22 only)
• temperature sensor
• monochrome white LED