Note: Perform settings on the auxiliary switch only in deenergised state.
1Manual adjusting
Connect the actuator and move it into the desired position.
2Auxiliary switch 1
Turn rotary knob until the arrow points to the vertical line.
The arrow direction always indicates the switching position (S1-S2 or S1-S3).
If the auxiliary switch should switch in the opposite direction, rotate the auxiliary switch rotary
knob by 180°. Alternatively the switching position can be checked with a continuity tester
on the cable of the auxiliary switch.
3Auxiliary switch 2
Turn rotary knob until the arrow points to the vertical line.
Turn the spindle clamp 2and consider the arrow direction of the auxiliary switch rotary knob at
the same time.
The arrow direction always indicates the switching position (S1-S2 or S1-S3).
If the auxiliary switch should switch in the opposite direction, rotate the auxiliary switch rotary
knob by 180°. Alternatively the switching position can be checked with a continuity tester
on the cable of the auxiliary switch.
Release (or disengage) button 1.
4Auxiliary switch - 2
Same procedure as for auxiliary switch 1 (step 1to 2).
1
2 3
Note: Perform settings on the auxiliary switch only in deenergised state.
1Manual override control
Turn the hand crank until the desired switching position is set.
2Fasten the locking device
Turn the locking switch to the «Locked padlock» symbol.
3Auxiliary switch 1
Turn rotary knob until the arrow points to the vertical line.
The arrow direction always indicates the switching position (S1-S2 or S1-S3).
If the auxiliary switch should switch in the opposite direction, rotate the auxiliary switch rotary
knob by 180°. Alternatively the switching position can be checked with a continuity tester
on the cable of the auxiliary switch.
4Unlock the locking device
Turn the locking switch to the «Unlocked padlock» symbol or unlock with the hand crank.
5Auxiliary switch 2
Same procedure as for auxiliary switch 1 (step 1to 4).
3 5
1
42
S2A-F Auxiliary switch unit, suitable for the spring return
actuators NF..A.., SF..A.., LF..
Operating controls and indicators
www.belimo.com S2A-F • en-gb • 2019-04-12 • subject to changes 3