Initial current
Start ramp time
Current limit
1
2
3
EMX4i
Quick Start R2.0
Remote Keypad
(1) Set Date and Time
Press:
Press to select what needs
changed. Use to change
values.
To save changes press .
Troubleshooting:
(a) If motor does not start to move as soon
as the Start is pushed, increase (2C).
(b) If motor Starts too fast, decrease (2C)
as long as motor does not stall at
startup. If still too fast decrease (2D).
(c) If motor does not reach full speed,
increase (2D).
Set Motor Full Load Amps (FLA)
*Check motor name plate for FLA and SF.
Press then to Main Menu
(2) Parameter 1B = Motor FLA
Press or to get correct value. Then to save
Exit
(3) Parameter. 1F = Motor Service Factor (S.F.)
Press or to get correct value. Then to save
(4) Parameter 2A = Start Mode: Constant Current
Press or to get correct value. Then to save
(5) Parameter 2B = Start Ramp Time: 10 -15 sec
Press or to get correct value. Then to save
(6) Parameter 2C = Initial Current: 250%
Press or to get correct value. Then to save
(7) Parameter 2D Current Limit: 400%
Press or to get correct value. Then to save
(8) Parameter 2I Stop Mode: Coast to Stop
Press or to get correct value. Then to save
Exit to main screen. You are now ready for Start/Stop.