-  do not leave inammable products in the room where the boiler is installed
- heat sensitive walls (for example, wooden walls) must be protected with 
proper insulation.
IMPORTANT
Before installation, wash all system piping carefully in order to remove any 
residues that may impair the operation of the appliance.
Connect the drain manifold to a suitable drainage system (for details, refer to 
chapter 3.5). The domestic hot water circuit does not need a safety valve, but 
make sure that the pressure of waterworks does not exceed 6 bar. In case of 
doubts, install a pressure reducer. Prior to ignition, make sure that the boiler 
is designed to operate with the gas available; this can be checked by the 
message on the packaging and the adhesive label indicating the gas type. It 
is very important to highlight that in some cases the smoke pipes are under 
pressure and therefore, the connections of several elements must be airtight.
3.2 Cleaning the system and characteristics of the 
heating circuit water
In the case of a new installation or replacement of the boiler, it is necessary 
to clean the heating system. 
To ensure the device works well, top up the additives and/or chemical treat-
ments (e.g. antifreeze liquids, lming agents, etc.) and check the param-
eters in the table are within the values indicated.
Parameters Unit of 
measurement Hot water
circuit Filling
water
pH value 7–8 -
Hardness °F -15–20
Appearance
- clear
3.3 Securing the boiler to the wall and hydraulic 
connections
To secure the boiler to the wall, use the crossbar (g. 10) provided in the box. 
The position and size of the hydraulic connections are indicated below:
M Heating outlet    3/4”
MB Water tank delivery 1/2”
GGas connection 3/4”
RB Water tank return 1/2”
R Heating return line    3/4”
3.4Installationoftheexternalsensor(g.11)
The correct operation of the external sensor is fundamental for the good 
operation of the climate control.
INSTALLING AND CONNECTING THE EXTERNAL SENSOR
The sensor must be installed on an external wall of the building to be heat-
ed, observing the following indications:
it must be mounted on the side of the building most often exposed to winds 
(the NORTH or NORTHWEST facing wall), avoiding direct sunlight; it must 
be mounted about two thirds of the way up the wall; it must not be mount-
ed near doors, windows or air outlet points, and must be kept away from 
smoke pipes or other heat sources.
The electrical wiring to the external sensor is made with a bipolar cable 
with a section from 0.5 to 1 mm2 (not supplied), with a maximum length 
of 30 metres. It is not necessary to respect the polarity of the cable when 
connecting it to the external sensor. Avoid making any joints on this cable 
however; if joints are absolutely necessary, they must be watertight and well 
protected. Any ducting of the connection cable must be separated from live 
cables (230V AC).
FIXING THE EXTERNAL SENSOR TO THE WALL
The sensor must be xed on a smooth part of the wall; in the case of ex-
posed brickwork or an uneven wall, look for the smoothest possible area. 
Loosen the plastic upper protective cover by turning it anticlockwise. 
After deciding on the best xing area of the wall, drill the holes for the 5x25 
wall plug.
Insert the plug in the hole. Remove the board from its seat.
Fix the box to the wall, using the screw supplied. 
Attach the bracket, then tighten the screw.
Loosen the nut of the cable grommet, then insert the sensor connection 
cable and connect it to the electric clamp. 
To make the electrical connection between the external sensor and the 
boiler, refer to the “Electrical wiring” chapter.
 Remember to close the cable grommet properly, to prevent any 
humidity in the air getting in through the opening.
Put the board back in its seat.
Close the plastic upper protective cover by turning it clockwise. Tighten the 
cable grommet securely.
3.5 Condensate collection
The system must be set up so as to avoid any freezing of the condensate 
produced by the boiler (e.g. by insulating it). You are advised to install a 
special drainage collection basin in polypropylene (widely available on 
the market) on the lower part of the boiler (hole Ø 42), as shown in g.12.
Position  the  exible  condensate  drainage  hose  supplied  with  the  boiler, 
connecting it to the manifold (or another connection device which allows 
inspection) avoiding creating any bends where the condensate could col-
lect and possibly freeze.
The manufacturer will not be liable for any damage resulting from the failure 
to channel the condensate, or from its freezing.
The drainage connection line must be perfectly sealed, and well protected 
from the risk of freezing.
Before the initial start-up of the appliance, check the condensate will be 
properly drained off.
3.6 Gas connection
Before connecting the appliance to the gas supply, check that:
- national and local installation regulations are complied with
- the gas type is the one suitable for the appliance
- the piping is clean.
The gas pipe must be installed outdoors. If the pipe goes through the wall, 
it must go through the central opening, in the lower part of the template.
It is advisable to install a lter of suitable dimensions on the gas line if the 
distribution network contains solid particles.
Once the appliance has been installed, check the connections are sealed 
according to current installation regulations.
3.7 Electrical wiring
To access the electrical wiring, proceed as follows:
To access the terminal board:
- turn off the main switch on the system
-  undo the xing screws (D) on the housing (g. 13)
- move the base of the housing forwards and then upwards to unhook it 
from the chassis
-  undo the xing screws (E) from the instrument panel (g. 14)
-  lift then turn the instrument panel towards you (g. 15)
-  detach the cover on the board casing (g. 16)
-  insert the cable of any room thermostat to be tted.  
The room thermostat must be connected as indicated in the wiring diagram.
 Lowvoltageroomthermostatinput(24VDC).
It must be connected to the mains power supply via a double-pole isolating 
switch with minimum contact gap of 3.5 mm (EN 60335/1 - category 3). 
The appliance operates with an alternating current of 230 Volt/50 Hz and 
complies with the standard EN 60335-1.
It is obligatory to ensure the earth connection is safe, in compliance with 
the current directives.
 The installer is responsible for ensuring the appliance is correctly 
earthed; the manufacturer will not be liable for any damage resulting 
from an incorrect or missing earth connection
 It is also advisable to respect the live-neutral connection (L-N).
 The earth conductor must be a couple of cm longer than the others.
The boiler can operate with a phase-neutral or phase-phase supply.
For power supplies that are not earthed, it is necessary to use an isolating 
transformer with earthed secondary.
Do not use gas and/or water pipes to earth electrical appliances. 
Use the power cable supplied to connect the boiler to the mains power supply. 
If the power cable needs to be replaced, use a cable of the HAR H05V2V2-F 
type, 3 x 0.75 mm2, with a maximum external diameter of 7 mm.
3.8 Filling the heating system
Once the hydraulic connections have been carried out, ll the heating system. 
This operation must be carried out with cold system, according to the fol-
lowing instructions (g. 17):
- open the automatic air vent by turning the plug on the lower valve (A) two 
or three turns, to bleed the air continuously, leave valve plug Aopen
- ensure that the cold water inlet tap is open
-  open the lling tap (external to the system) until the pressure indicated by 
the water gauge is between 1 and 1.5 bar
-  close the lling tap. 
Note: the boiler is bled automatically via the two automatic bleed valves 
Aand E, positioned on the circulator and inside the air distribution box 
respectively. If you encounter problems bleeding the boiler, proceed as de-
scribed in paragraph 3.10.
3.9 Draining the heating system
Before starting to drain the system, switch off the electrical supply by turn-
ing off the main switch of the system.
Close the shut-off devices on the heating system.
Manually loosen the system drain valve (D).
3.10 Bleeding the air from the heating circuit and boiler
During the initial installation phase, or in the event of extraordinary main-
tenance, you are advised to perform the following sequence of operations:
1. Open the automatic air vent by turning the plug on the lower valve (A, 
g. 18) two or three turns, to bleed the air continuously, leave valve 
plug Aopen.