BIRD 6150-ALM-02 User manual

6150-ALM-02
Operation Manual
©
Copyright 2021
by Bird Technologies Inc.
Instruction Book Part Number 920-6150-ALM-02 Rev. A


Safety Precautions
i
Safety Precautions
The following are general safety precautions that are not necessarily related to
any specific part or procedure, and do not necessarily appear elsewhere in this
publication. These precautions must be thoroughly understood and apply to all
phases of operation and maintenance.
WARNING
Keep Away From Live Circuits
Operating Personnel must at all times observe general safety
precautions. Do not replace components or make adjustments to
the inside of the test equipment with the high voltage supply
turned on. To avoid casualties, always remove power.
WARNING
Do Not Service Or Adjust Alone
Under no circumstances should any person reach into an enclosure
for the purpose of service or adjustment of equipment except in the
presence of someone who is capable of rendering aid.
WARNING
Safety Earth Ground
An uninterruptible earth safety ground must be supplied from the
main power source to test instruments. Grounding one conductor of
a two conductor power cable is not sufficient protection. Serious
injury or death can occur if this grounding is not properly supplied.
WARNING
Resuscitation
Personnel working with or near high voltages should be familiar with
modern methods of resuscitation.
WARNING
Remove Power
Observe general safety precautions. Do not open the instrument
with the power applied.

NFPA Alarm Panel 6150-ALM-02
ii
Safety Symbols
Note: Calls attention to supplemental information.
Safety Statements
USAGE
ANY USE OF THIS INSTRUMENT IN A MANNER NOT SPECIFIED BY
THE MANUFACTURER MAY IMPAIR THE INSTRUMENT’S SAFETY
PROTECTION.
USO
EL USO DE ESTE INSTRUMENTO DE MANERA NO ESPECIFICADA
POR EL FABRICANTE, PUEDE ANULAR LA PROTECCIÓN DE
SEGURIDAD DEL INSTRUMENTO.
BENUTZUNG
WIRD DAS GERÄT AUF ANDERE WEISE VERWENDET ALS VOM
HERSTELLER BESCHRIEBEN, KANN DIE GERÄTESICHERHEIT
BEEINTRÄCHTIGT WERDEN.
UTILISATION
TOUTE UTILISATION DE CET INSTRUMENT QUI N’EST PAS
EXPLICITEMENT PRÉVUE PAR LE FABRICANT PEUT
ENDOMMAGER LE DISPOSITIF DE PROTECTION DE
L’INSTRUMENT.
IMPIEGO
QUALORA QUESTO STRUMENTO VENISSE UTILIZZATO IN MODO
DIVERSO DA COME SPECIFICATO DAL PRODUTTORE LA
PROZIONE DI SICUREZZA POTREBBE VENIRNE COMPROMESSA.
WARNING
Warning notes call attention to a procedure, which if not correctly
performed, could result in personal injury.
CAUTION
Caution notes call attention to a procedure, which if not correctly
performed, could result in damage to the instrument.

Safety Precautions
iii
SERVICE
SERVICING INSTRUCTIONS ARE FOR USE BY SERVICE - TRAINED
PERSONNEL ONLY. TO AVOID DANGEROUS ELECTRIC SHOCK, DO
NOT PERFORM ANY SERVICING UNLESS QUALIFIED TO DO SO.
SERVICIO
LAS INSTRUCCIONES DE SERVICIO SON PARA USO EXCLUSIVO
DEL PERSONAL DE SERVICIO CAPACITADO. PARA EVITAR EL
PELIGRO DE DESCARGAS ELÉCTRICAS, NO REALICE NINGÚN
SERVICIO A MENOS QUE ESTÉ CAPACITADO PARA HACERIO.
WARTUNG
ANWEISUNGEN FÜR DIE WARTUNG DES GERÄTES GELTEN NUR
FÜR GESCHULTES FACHPERSONAL.
ZUR VERMEIDUNG GEFÄHRLICHE, ELEKTRISCHE SCHOCKS, SIND
WARTUNGSARBEITEN AUSSCHLIEßLICH VON QUALIFIZIERTEM
SERVICEPERSONAL DURCHZUFÜHREN.
ENTRENTIEN
L’EMPLOI DES INSTRUCTIONS D’ENTRETIEN DOIT ÊTRE RÉSERVÉ
AU PERSONNEL FORMÉ AUX OPÉRATIONS D’ENTRETIEN. POUR
PRÉVENIR UN CHOC ÉLECTRIQUE DANGEREUX, NE PAS
EFFECTUER D’ENTRETIEN SI L’ON N’A PAS ÉTÉ QUALIFIÉ POUR
CE FAIRE.
ASSISTENZA TECNICA
LE ISTRUZIONI RELATIVE ALL’ASSISTENZA SONO PREVISTE
ESCLUSIVAMENTE PER IL PERSONALE OPPORTUNAMENTE
ADDESTRATO. PER EVITARE PERICOLOSE SCOSSE ELETTRICHE
NON EFFETTUARRE ALCUNA RIPARAZIONE A MENO CHE
QUALIFICATI A FARLA.

NFPA Alarm Panel 6150-ALM-02
iv
About This Manual
This manual covers the installation, operating & maintenance instructions for:
Changes to this Manual
We have made every effort to ensure this manual is accurate. If you discover any
errors, or if you have suggestions for improving this manual, please send your
comments to our Solon, Ohio factory. This manual may be periodically updated.
When inquiring about updates to this manual refer to the part number and
revision on the title page.
6150-ALM-02

v
Table of Contents
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . i
Safety Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ii
Safety Statements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ii
About This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iv
Changes to this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iv
Chapter 1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Monitored Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Other Monitored Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Alarm Reporting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Link Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Cable Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Chapter 2 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Installing the Alarm Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Booster - Alarm Panel Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Alarm Panel Output Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Chapter 3 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Normal Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Alarm Condition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Communication Lost . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Alarm Panel Display’s Offline Message . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
No Alarm Panel Display, Power LED On . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
No Alarm Panel Display, Power LED Off. . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Customer Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Chapter 4 Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Limited Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

1
Chapter 1 Introduction
The Bird NFPA Alarm Panel is an SBII+ Fiber-DAS alarm status annunciator that
provides a convenient means of monitoring your Fiber-DAS alarms from a
reasonably nearby location such as a security desk or main lobby desk located in
the same building as the Fiber-DAS system.
Figure 1 Alarm Panel
Monitored Alarms
The alarm panel is capable of monitoring the five alarms required for NFPA
compliance including:
Signal Booster Failure — This is a summed alarm that is active when any
number of fault conditions arise within the booster unit such as when an over
current or high temperature event occurs.
Loss of AC Power — Indicates that AC power to the booster unit has failed.
Antenna Malfunction — Indicates there is a loss of RF cable integrity
between the signal booster unit and the remote antenna line sensor. In order to
detect an antenna malfunction an antenna line sensor must be installed as close
to the Donor antenna as possible. This sensor works with the Bias-T assembly
inside the booster cabinet to verify the continuity of the antenna line
Low Battery Condition — The source of this alarm is the battery backup unit
and it indicates that the battery backup voltage level has dropped significantly.
Charger Failure — The source of this alarm is the battery backup unit and it
indicates failure of the battery charger. If the battery charger looses AC power
this alarm will be active.

NFPA Alarm Panel 6150-ALM-02
2
Other Monitored Parameters
In addition to the NFPA alarms, the Alarm Panel displays the status following
parameters:
Power — when illuminated indicates the alarm panel is connected to/and
receiving power from a Head-End unit.
Status — Link and alarm status is displayed in the upper right corner of the
display, see
Figure 2
.
Figure 2 Status Indicator
Alarm Reporting
When an alarm condition is detected, the corresponding indicator will change to
RED. The status indicator in the top right of the display will indicate the booster’s
alarmed status, see
Figure 3
.
Link Status
Link status during normal operation is indicated by no alarm (green) or alarms
reported (red).
If communication is lost with the Head-End Unit, a disconnected icon (yellow) is
displayed. The Alarm panel will automatically attempt to reconnect with the
Head-End unit. If the Alarm Panel remains disconnected for approximately one
minute, the offline message is displayed indicating the connection could not be
reestablished, see
Figure 3
.
Figure 3 Link Status Indicator
$ODUP6XPPDU\
XSGDWHLQV
1R
$ODUPV
$ODUP6XPPDU\
XSGDWHLQV
$ODUPV
5HSRUWHG
$ODUP6XPPDU\
XSGDWHLQVU
&RPPXQLFDWLRQV
/RVW
+HDGHQG1DPH
%RRVWHU)DLOXUH
$QW)DLOXUH
&KDUJH)DLOXUH
$&)DLOXUH
%DWW
6SDUH
6SDUH
6SDUH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH 1DPH
$ODUP6XPPDU\
XSGDWHLQV
+HDGHQG1DPH
%RRVWHU)DLOXUH
$QW)DLOXUH
&KDUJH)DLOXUH
$&)DLOXUH
%DWW
6SDUH
6SDUH
6SDUH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH 1DPH
$ODUP6XPPDU\
XSGDWHLQV
+HDGHQG1DPH
%RRVWHU)DLOXUH
$QW)DLOXUH
&KDUJH)DLOXUH
$&)DLOXUH
%DWW
6SDUH
6SDUH
6SDUH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH 1DPH
$ODUP6XPPDU\
XSGDWHLQVU
RႉLQH
YEXLOG7
UHWU\
ZDLWLQJIRULS
VHFRQGVVLQFHODVWFRQWDFW
KWWSDSLYDODUPV
1RUPDO
2SHUDWLRQ
$ODUP
3UHVHQW
&RPPXQLFDWLRQ
/RVW

Introduction
3
Cable Connections
Fiber-DAS Head-End Unit — The Alarm Panel connects to the Head-End
unit using a standard Ethernet cable with RJ-45 connectors. The Ethernet cable
provides operating voltage for the Alarm Panel and carries the Fiber-DAS system
status.
Facility Panel — Optionally, the NPFA alarm status may be extended from the
Alarm Panel (25-pin connector) to an existing facility alarm panel.
Figure 4 Alarm Panel Connections
)LEHU'$6
+HDG(QG8QLW
$ODUP3DQHO
)DFLOLW\
$ODUP3DQHO
6WDQGDUG
(WKHUQHW&DEOH
7ZLVWHG3DLU
&DEOH
¥
5IFNJ®&YQFSUT
32:(5
02'(/12
$/0
+HDGHQG1DPH
%RRVWHU)DLOXUH
$QW)DLOXUH
&KDUJH)DLOXUH
$&)DLOXUH
%DWW
6SDUH
6SDUH
6SDUH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
$ODUP6XPPDU\
XSGDWHLQV

4
Chapter 2 Installation
Installing the Alarm Panel
The alarm panel is designed to be wall mounted and has a built-in mounting
flange on the top and bottom of the enclosure. Each flange has two 5/16 screw
holes and all four holes should be used during installation to insure the box is
fastened firmly.
Place the panel in a convenient viewable location. The cable connections are on
the bottom of the enclosure, so the bottom should be accessible.
Figure 5
shows the location of the mounting brackets on the alarm panel
enclosure.
Figure 5 Alarm Panel Mounting
0RXQWLQJ
%UDFNHWV
¥
5IFNJ®&YQFSUT
32:(5
02'(/12
$/0
+HDGHQG1DPH
%RRVWHU)DLOXUH
$QW)DLOXUH
&KDUJH)DLOXUH
$&)DLOXUH
%DWW
6SDUH
6SDUH
6SDUH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
$ODUP6XPPDU\
XSGDWHLQV
´ ´

Installation
5
Booster - Alarm Panel Connection
The Alarm Panel is equipped with one RJ-45 Alarm input connector. This
connector is used to connect a Bird Fiber-DAS Head-End Unit to the alarm panel.
The RJ-45 connector is used for alarm panel power and alarm data. See
Figure 6
.
Bird Boosters with an RJ-45 Alarm Panel output (data + POE) can connect
directly to the RJ-45 connector on the bottom of the alarm panel. A standard
Ethernet cable is used for the connection, the maximum length for this cable is
300 feet (100 meters). The RJ-45 connection supplies power for the alarm panel
and interfaces the boosters NFPA alarms.
Figure 6 Alarm Input connections
Alarm Panel Output Connection
An alarm output connector is provided to allow the NFPA alarms to be extended
to a facility alarm panel. The Alarm Output connector is a standard D-sub 25-pin
receptacle. See
Figure 6
.
One of the important considerations when installing the alarm panel wiring is
noise on the lines which may cause false alarm indications at the alarm panel.
Using good quality cable with sufficient shielding is important. When laying the
cable run avoid running it next to the building’s AC wiring or near strong noise
sources like motors.
If your installation requires the distance between the alarm panels to be greater
than several thousand feet consult with the factory before running the signal
cable. The wire gauge and shielding used for the signal lines will determine the
workable distance, thicker wire gives greater distance but can be cost
prohibitive.
The alarm can be connected as normally open or normally closed circuits.
Normally closed is defined as a contact pair that is normally closed when the
booster is powered-up, operating normally, with no alarm conditions.
The pinout for the Alarm Connector are shown in
Table 1 on page 6
.

NFPA Alarm Panel 6150-ALM-02
6
Table 1 Alarm 25-Pin Connector Output Pinout
3LQ
$VVLJQPHQW
&RQWDFW
ϭ
^&Ăŝů
EŽƌŵĂůůLJůŽƐĞĚ
Ϯ
^&Ăŝů
ŽŵŵŽŶ
ϯ
^&Ăŝů
EŽƌŵĂůůLJKƉĞŶ
ϰ
>ŽƐƐŽĨ
EŽƌŵĂůůLJůŽƐĞĚ
ϱ
>ŽƐƐŽĨ
ŽŵŵŽŶ
ϲ
>ŽƐƐŽĨ
EŽƌŵĂůůLJKƉĞŶ
ϳ
ŚĂƌŐĞ&ĂŝůƵƌĞ
EŽƌŵĂůůLJůŽƐĞĚ
ϴ
ŚĂƌŐĞ&ĂŝůƵƌĞ
ŽŵŵŽŶ
ϵ
ŚĂƌŐĞ&ĂŝůƵƌĞ
EŽƌŵĂůůLJKƉĞŶ
ϭϬ
ŶƚĞŶŶĂDĂůĨƵŶĐƟŽŶ
EŽƌŵĂůůLJůŽƐĞĚ
ϭϭ
ŶƚĞŶŶĂDĂůĨƵŶĐƟŽŶ
ŽŵŵŽŶ
ϭϮ
ŶƚĞŶŶĂDĂůĨƵŶĐƟŽŶ
EŽƌŵĂůůLJKƉĞŶ
ϭϯ
>ŽǁĂƩĞƌLJ
EŽƌŵĂůůLJůŽƐĞĚ
3LQ
$VVLJQPHQW
&RQWDFW
ϭϰ
>ŽǁĂƩĞƌLJ
ŽŵŵŽŶ
ϭϱ
>ŽǁĂƩĞƌLJ
EŽƌŵĂůůLJKƉĞŶ
ϭϲ
^ƉĂƌĞϭ
EŽƌŵĂůůLJůŽƐĞĚ
ϭϳ
^ƉĂƌĞϭ
EŽƌŵĂůůLJKƉĞŶ
ϭϴ
^ƉĂƌĞϭ
ŽŵŵŽŶ
ϭϵ
^ƉĂƌĞϮ
EŽƌŵĂůůLJůŽƐĞĚ
ϮϬ
^ƉĂƌĞϮ
EŽƌŵĂůůLJKƉĞŶ
Ϯϭ
^ƉĂƌĞϮ
ŽŵŵŽŶ
ϮϮ
^ƉĂƌĞϯ
EŽƌŵĂůůLJůŽƐĞĚ
Ϯϯ
^ƉĂƌĞϯ
EŽƌŵĂůůLJKƉĞŶ
Ϯϰ
^ƉĂƌĞϯ
ŽŵŵŽŶ
Ϯϱ
EŽƚŽŶŶĞĐƚĞĚ
E

7
Chapter 3 Operation
Normal Operation
The LCD alarm panel connects to the head-end unit of the SBII+ Fiber-DAS and
will display alarms for the head end unit as well as each remote that is
connected to the head-end through fiber-optic cable.
When the Alarm Panel is connected to a head-end unit and the unit is powered
up, the alarm panel will display Power (green) and the alarm status of the head-
end unit.
When the alarm panel is powered-up and the head-end unit and remote units
are operating normally (no faults) the status lights will be green for the
monitored NFPA alarm parameters for each unit.
Alarm Condition
When a unit detects a malfunction for one of the monitored NFPA parameters,
the associated indicator will change to red. The status indicator will also change
to an alarm condition.
Figure 7 Alarm Panel Display
Communication Lost
If communication between the Fiber-DAS system and the Alarm panel is lost, see
Figure 7
, and does not reconnect, indicated by the offline message,
troubleshoot the connection. See
"Troubleshooting" on page 8
.
+HDGHQG1DPH
%RRVWHU)DLOXUH
$QW)DLOXUH
&KDUJH)DLOXUH
$&)DLOXUH
%DWW
6SDUH
6SDUH
6SDUH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
$ODUP6XPPDU\
XSGDWHLQV
+HDGHQG1DPH
%RRVWHU)DLOXUH
$QW)DLOXUH
&KDUJH)DLOXUH
$&)DLOXUH
%DWW
6SDUH
6SDUH
6SDUH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
$ODUP6XPPDU\
XSGDWHLQV
+HDGHQG1DPH
%RRVWHU)DLOXUH
$QW)DLOXUH
&KDUJH)DLOXUH
$&)DLOXUH
%DWW
6SDUH
6SDUH
6SDUH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
5HPRWH1DPH
$ODUP6XPPDU\
XSGDWHLQVU
RႉLQH
YEXLOG7
UHWU\
ZDLWLQJIRULS
VHFRQGVVLQFHODVWFRQWDFW
KWWSDSLYDODUPV
1RUPDO
2SHUDWLRQ
$ODUP
3UHVHQW
&RPPXQLFDWLRQ
/RVW

NFPA Alarm Panel 6150-ALM-02
8
Troubleshooting
If Alarm panel is malfunctioning find the symptoms in the following paragraphs
for the steps to isolate the cause.
Alarm Panel Display’s Offline Message
Recheck systems after each step.
No Alarm Panel Display, Power LED On
No Alarm Panel Display, Power LED Off.
Recheck systems after each step.
1. Disconnect Ethernet cable from alarm panel, inspect connector, then
reinsert.
If Ethernet connector is damaged, replace connector.
2. Disconnect Ethernet cable from Head-end unit, inspect connector, then
reinsert.
If Ethernet connector is damaged, replace connector.
3. Inspect Ethernet cable for damage.
If Ethernet cable is damaged, repair or replace the cable.
4. Cycle power on the Head-End unit.
If Offline message is still displayed, contact
Customer
Service
.
1. Perform the steps in
Alarm Panel Display’s Offline Message
.
If symptoms persist, contact
Customer Service
.
1. Verify power is applied to the Head-End unit.
If power to Head-End is off, determine case and restore power
to the Head-End
2. Disconnect Ethernet cable from alarm panel, inspect connector, then
reinsert.
If Ethernet connector is damaged, replace connector.
3. Disconnect Ethernet cable from Head-end unit, inspect connector, then
reinsert.
If Ethernet connector is damaged, replace connector.
4. Inspect Ethernet cable for damage.
If Ethernet cable is damaged, repair or replace the cable.
5. If symptoms persist, contact
Customer Service
.

Operation
9
Customer Service
Any maintenance or service procedure beyond the scope of those in this chapter
should be referred to a qualified service center.
If the unit needs to be returned for any reason, request an Return Material
Authorization (RMA) through the Bird Technologies website. All instruments
returned must be shipped prepaid and to the attention of the RMA number.
Bird Service Center
30303 Aurora Road
Cleveland (Solon), Ohio 44139-2794
Fax: (440) 248-5426
E-mail: bsc@birdrf.com
For the location of the Sales Office nearest you, visit our Web site at:
http://www.birdrf.com

10
Chapter 4 Specifications
Specification Value
Alarms Monitored
Signal Booster Failure,
Loss of AC Power,
Antenna Malfunction,
Low Battery Condition,
Charger Failure.
Display 7” LCD
Alarm Indications
Virtual LED Red
Alarm Input
Alarm Input Ethernet
Alarm Input Connector RJ-45
Alarm Output
Alarm Output Connector D-sub 25-pin
Alarm Types Normally Open,
Normally Closed
Max Allowable Voltage 30 VDC
Max Current 1 A
Wire Size 18 to 26 AWG
Enclosure Rating NEMA 4
Operating Temperature 32 °F to 122 °F (0 °C to 50 °C)
Enclosure Dimensions
8.5” x 8.7” x 5.2”
(21.6 cm x 22.1 cm x 13.2 cm)
H x W x D
Enclosure Weight 7 lbs (3.18 kg)

11
Limited Warranty
All products manufactured by Seller are warranted to be free from defects in
material and workmanship for a period of one (1) year, unless otherwise
specified, from date of shipment and to conform to applicable specifications,
drawings, blueprints and/or samples. Seller’s sole obligation under these
warranties shall be to issue credit, repair or replace any item or part thereof
which is proved to be other than as warranted; no allowance shall be made for
any labor charges of Buyer for replacement of parts, adjustment or repairs, or
any other work, unless such charges are authorized in advance by Seller.
If Seller’s products are claimed to be defective in material or workmanship or
not to conform to specifications, drawings, blueprints and/or samples, Seller
shall, upon prompt notice thereof, either examine the products where they are
located or issue shipping instructions for return to Seller (transportation-charges
prepaid by Buyer). In the event any of our products are proved to be other than
as warranted, transportation costs (cheapest way) to and from Seller’s plant, will
be borne by Seller and reimbursement or credit will be made for amounts so
expended by Buyer. Every such claim for breach of these warranties shall be
deemed to be waived by Buyer unless made in writing within ten (10) days from
the date of discovery of the defect.
The above warranties shall not extend to any products or parts thereof which
have been subjected to any misuse or neglect, damaged by accident, rendered
defective by reason of improper installation or by the performance of repairs or
alterations outside of our plant, and shall not apply to any goods or parts
thereof furnished by Buyer or acquired from others at Buyer’s request and/or to
Buyer’s specifications. Routine (regularly required) calibration is not covered
under this limited warranty. In addition, Seller’s warranties do not extend to the
failure of tubes, transistors, fuses and batteries, or to other equipment and parts
manufactured by others except to the extent of the original manufacturer’s
warranty to Seller.
The obligations under the foregoing warranties are limited to the precise terms
thereof. These warranties provide exclusive remedies, expressly in lieu of all other
remedies including claims for special or consequential damages. SELLER NEITHER
MAKES NOR ASSUMES ANY OTHER WARRANTY WHATSOEVER, WHETHER EXPRESS,
STATUTORY, OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY AND
FITNESS, AND NO PERSON IS AUTHORIZED TO ASSUME FOR SELLER ANY
OBLIGATION OR LIABILITY NOT STRICTLY IN ACCORDANCE WITH THE FOREGOING.
Table of contents
Other BIRD Security System manuals
Popular Security System manuals by other brands

Telstra
Telstra MX65W installation guide

Honeywell
Honeywell ADEMCO VISTA SERIES Programming guide

Directed
Directed Power Sports Installer and owner guide

Federal Signal Corporation
Federal Signal Corporation 400HMK-AC instruction sheet

Eaton
Eaton i-onEX Series Administrator's and user guide

Risco
Risco LightSYS user manual