Route the cables to the control unit through the sealed cabled glands in the unit.
All the electric connections must be performed in compliance with external wiring diagram and wired through the terminal block X1 in the control unit. Extra control units may
be optionally connected to the unit. Extra connected control units are not included in the delivery set and must be ordered separately. Extra connections are shown in dotted
lines in the wiring diagram.
EXTERNAL WIRING DIAGRAM FOR THE UNITS WITH S14 AUTOMATION
Connection of the re alarm panel (PK) contact
While connecting the re alarm panel contact remove the jumper between the terminals 4 and 5. In this case
the connection relies on a normally closed dry contact. In case of re the normally closed dry contact opens the
control circuit from the central re alarm panel and cuts o power supply to the unit.
Connecting of the external control unit contact, such as RH/CO2/VOC sensor
(NO, C).
Connect the CO2sensor to the terminals 6 and 7. In this case connection relies on a normally open dry contact.
Once the contact is closed, the unit starts to run with the maximum speed.
The cable for connection of the control panel to the air handling unit must be of 4xAWG30 type and have the
maximum length 39 3/8inch.
11 10 9 87654321
+U Rx Tx
brown
yellow
green
white
Control
panel
GND
C NO PK PK PE N L
PE N L
QF
+U Rx Tx
GND
C NO PK PK PE N L
NO-contact of the
external control unit
(RH/CO2/VOC sensor)
PK: fire alarm panel
min. current 1 A (remove
the jumper during connection)
EXTERNAL WIRING DIAGRAM FOR THE UNITS WITH S17 AND S18 AUTOMATION
Connection of the re alarm panel (PK) contact
While connecting the re alarm panel contact remove the jumper between the terminals 4 and 5. In this case
the connection relies on a normally closed dry contact. In case of re the normally closed dry contact opens the
control circuit from the central re alarm panel and cuts o power supply to the unit.
The cable for connection of the control panel to the air handling unit must
match the following requirements:
Cable type Distance to power supply source
Telephone type max. 164 ft
Shielded cable AWG24 max. 656 ft
Control
panel
PK: fire alarm panel
min. current 1 A (remove
the jumper during connection)
1 2 3 45678910
PE N L NC NC ~24
~GND
R- R+
GND
GND
R+R-
~GND
~24
PE N L
QF
PE N L NC NC
GND
R+ R-
~GND
~24
• The unit is rated for connection to 120V / 60 Hz power mains.
• The unit must be connected to power mains using insulated electric conductors (cables, wires). The actual
wire cross section selection must be based on the maximum load current, maximum conductor temperature
depending in the wire type, insulation, length and installation method.
• The external power input must be equipped with an automatic circuit breaker built into the stationary wiring
to open the electric circuit in case of overload or short-circuit.The circuit breaker installation place must provide
quick access for emergency shutdown of the unit. The trip current of the automatic circuit breaker QF must
exceed the maximum current consumption of the unit (refer to the technical data table). The recommended trip
current of the circuit breaker is the next current in the standard trip current row following the maximum current
of the connected unit. Automatic circuit breaker is not included in the delivery set.
CONNECTION TO POWER MAINS