Blaze B600 User manual

Contemporary Styled Wood Heaters
INSTALLATION INSTRUCTIONS

BLAZE B605/B905
BLAZE B600/B900
Glen Dimplex Australia proudly supports the
activities of Landcare Australia through its
membership of the AHHA.
VERSION 1.0

1
TABLE OF CONTENTS
1. Important Information.................. 2
2. Assembling the heater ................. 3
2.1. B600/B900 ....................... 3
2.2. B605/B905 ...................... 3
3. Installing the Heater ................... 3
3.1. Positioning the Heater ............. 3
3.2. Floor Protector (Hearth) ........... 7
4. Reducing Clearances to Combustibles ... 8
5. Installing the Flue...................... 8
5.1. Fitting Flue Seal .................. 9
6. Installing the Ash Plate ................. 9
7. InstallingtheBafePlate ............... 10
8. Installing the Fire Bricks ................. 10
9. Relocating the Fan Assembly............ 11
10. Relocating the Blanking Plates. . . . . . . . . . . 11
11. Installing the Glass Panels............... 12
12. Technical Drawings .................... 14
12.1. B600 ........................... 14
12.2. B605 ........................... 15
12.3. B900 ........................... 16
12.4. B905 ........................... 17
THE INSTALLATION INSTRUCTIONS IN THIS MANUAL APPLY TO THE BLAZE B600/B900
& B605/B905.
IT HAS BEEN TESTED FOR EMISSIONS AND EFFICIENCY AND COMPLIES
ACCORDING TO AS/NZS 4012:2014 & AS/NZS 4013:2014.
INSTALLATION CLEARANCES WERE DETERMINED BY TESTING IN ACCORDANCE
WITH AS/NZS 2918.

2
1. IMPORTANT INFORMATION
Most building regulatory authorities in Australia
require any wood heater installation to comply
with Installation Standard AS/NZS 2918:2018.
Different states and councils may have varying
regulations. Check local building regulations
before installing the appliance.
All Blaze wood heaters have been tested to
ensure that they will meet the appropriate safety
Standard requirements if the instructions in this
manual are followed. As the safety and emissions
performance can be affected by altering the
appliance,nomodicationsareallowedwithout
written permission from the manufacturer.
WE RECOMMEND THAT THE INSTALLATION OF
YOUR BLAZE WOOD HEATER BE CARRIED OUT BY A
QUALIFIED INSTALLER.
WARNING: THE APPLIANCE AND FLUE SYSTEM SHALL
BE INSTALLED IN ACCORDANCE WITH AS/NZS
2918:2018 AND THE APPROPRIATE REQUIREMENTS
OF THE RELEVANT BUILDING CODE OR CODES.
WARNING: APPLIANCES INSTALLED IN
ACCORDANCE WITH THIS STANDARD SHALL
COMPLY WITH THE REQUIREMENTS OF AS/NZS
4012 & AS/NZS 4013 WHERE REQUIRED BY THE
REGULATORY AUTHORITY, I.E. THE APPLIANCE SHALL
BE IDENTIFIABLE BY A COMPLIANCE PLATE WITH THE
MARKING ‘TESTED TO AS/NZS 4012 & AS/NZS 4013’.
ANY MODIFICATION OF THE APPLIANCE THAT HAS
NOT BEEN APPROVED IN WRITING BY THE TESTING
AUTHORITY IS CONSIDERED TO BE IN BREACH OF
THE APPROVAL GRANTED FOR COMPLIANCE WITH
AS/NZS 4012 & AS/NZS 4013.
Caution:Mixingofapplianceorue-system
components from different sources or modifying
thedimensionalspecicationofcomponents
may result in hazardous conditions. Where such
action is considered, the manufacturer should be
consultedintherstinstance.
Caution: Cracked and broken components, e.g.
glass panels or ceramic tiles, may render the
installation unsafe.
WARNING: KEEP BATTERIES OUT OF REACH OF
CHILDREN
Swallowing may lead to serious injury in as little
as 2 hours or death, due to chemical burns and
potential perforation of the oesophagus.
If you suspect your child has swallowed or
inserted a button battery immediately call the
24-hourPoisonsInformationCentreon131126
(in Australia) or 0800 764 766 (in New Zealand) for
fast, expert advice.
Examine devices and make sure the battery
compartment is correctly secured, e.g. that the
screw or other mechanical fastener is tightened.
Do not use if the compartment is not secure.
Dispose of used button batteries immediately and
safely. Flat batteries can still be dangerous.

3
2. ASSEMBLING THE HEATER
ThisBlazeheaterwillarriveintwoparts,therebox
body and the base unit representing the B600/
B900 or the B605/B905.
2.1. B600/B900
Thereboxbodyhasfourlocatingpinsonthe
bottom. Place the body on to the base so that the
pins fall into the four holes in the base unit. There
is a small amount of movement between the pins
and the holes, adjust the body so that it is lined up
vertically with the base unit.
A black toughened glass panel will be wrapped
with the base unit. Unwrap it, position on the base
of the unit, lined up with the sides of the base and
pushed up against the rear wall of the base unit.
(refer to section “11. Installing the Glass Panels” for
more detail).
Connect the power lead from the rear of the
heater to a power point for the fan to work.
2.2. B605/B905
WiththeB605/B905models,thereboxbodycan
be located in one of three positions on the base
unit-inthecentre,ontheleft,orontherightside
of the base.
Thereboxbodyhasfourlocatingpinsonthe
bottom. Place the body on to the base so that the
pins fall into the four holes in the base unit. There
is a small amount of movement between the pins
and the holes, adjust the body so that it is lined up
vertically with the base unit.
Thedefaultassumesthereboxwillbepositioned
in the centre. If wanting to install the heater with
thereboxontheleftortherightsideofthebase,
the fan will need to be relocated to line up with
thelocationoftherebox,aswellasrelocating
the blanking plates. Depending on which side, the
fan controller box may also need to be relocated.
To relocate the fan, refer to section “9. Relocating
the Fan Assembly” for details.
To relocate the blanking plates, refer to section
“10. Relocating the Blanking Plates” for details.
Tottheglasspanelsontopofthebase,referto
section “11. Installing the Glass Panels” for details.
3. INSTALLING THE HEATER
3.1. POSITIONING THE HEATER
First review the necessary minimum clearances
speciedonthefollowingpagebefore
considering where to position the heater. These
clearances can be greater if desired.
The heater can be installed with a choice of three
differentuecongurations.Clearancesspecic
to each are listed in the associated tables. Also
checkthepracticabilityofinstallingtheue
system in relation to any obstructing roof beams
before positioning the heater.
These clearance distances can only be
reduced if the surrounding walls are made of
non-combustiblematerial,e.g.stone,brick,or
concrete. In this circumstance, distance can be
reduced to 100 mm. Alternatively, shielding of
the wall(s) can reduce clearances (refer to next
section for more detail).

4
3.1.1. B600/B900 STANDARD INSTALLATION
R2R1
S1
S2
COMBUSTIBLE WALL
COMBUSTIBLE WALL
F
B600
STANDARD INSTALLATION
SINGLE REAR
FLUE SHIELD
SOLID CASING/
DECROMESH
Side-S1 425mm 425mm
Side – S2 756mm 756mm
Rear – R1 150mm 225mm
Rear – R2 333mm 408mm
Floor-F 300mm 300mm
B900
STANDARD INSTALLATION
SINGLE REAR FLUE SHIELD/SOLID
CASING/DECROMESH
Side-S1 375mm
Side – S2 756mm
Rear – R1 175mm
Rear – R2 357mm
Floor-F 300mm
3.1.2. B600/B900 CORNER INSTALLATION
C2 C1
F
COMBUSTIBLE WALL
COMBUSTIBLE WALL
C2
C1
B600
CORNER INSTALLATION
SINGLE REAR FLUE SHIELD/
SOLID CASING/DECROMESH
Corner-C1 150mm
Corner – C2 511mm
Floor-F 300mm
B900
CORNER INSTALLATION
SINGLE REAR FLUE SHIELD/
SOLID CASING/DECROMESH
Corner-C1 150mm
Corner – C2 545mm
Floor-F 300mm

5
3.1.3. B605/B905 (MIDDLE) STANDARD INSTALLATION
F
R2R1
S1
S2
COMBUSTIBLE WALL
COMBUSTIBLE WALL
B605 (MIDDLE)
STANDARD INSTALLATION
SINGLE REAR
FLUE SHIELD
SOLID CASING/
DECROMESH
Side-S1 171mm 171mm
Side – S2 756mm 756mm
Rear – R1 150mm 225mm
Rear – R2 333mm 408mm
Floor-F 300mm 300mm
B905 (MIDDLE)
STANDARD INSTALLATION
SINGLE REAR FLUE SHIELD/SOLID
CASING/DECROMESH
Side-S1 96mm
Side – S2 756mm
Rear – R1 175mm
Rear – R2 357mm
Floor-F 300mm
3.1.4. B600/B905 (MIDDLE) CORNER INSTALLATION
C
COMBUSTIBLE WALL
COMBUSTIBLE WALL
C
F
B605 (MIDDLE)
CORNER INSTALLATION
SINGLE REAR FLUE SHIELD/
SOLID CASING/DECROMESH
Corner-C 150mm
Floor-F 300mm
B905 (MIDDLE)
CORNER INSTALLATION
SINGLE REAR FLUE SHIELD/
SOLID CASING/DECROMESH
Corner-C 150mm
Floor-F 300mm

6
3.1.5. B605/B905 (LEFT) STANDARD INSTALLATION
F
R2R1
S1
S2
COMBUSTIBLE WALL
COMBUSTIBLE WALL
B605 (LEFT)
STANDARD INSTALLATION
SINGLE REAR
FLUE SHIELD
SOLID CASING/
DECROMESH
Side-S1 425mm 425mm
Side – S2 756mm 756mm
Rear – R1 150mm 225mm
Rear – R2 333mm 408mm
Floor-F 300mm 300mm
B905 (LEFT)
STANDARD INSTALLATION
SINGLE REAR FLUE SHIELD/SOLID
CASING/DECROMESH
Side-S1 375mm
Side – S2 756mm
Rear – R1 175mm
Rear – R2 357mm
Floor-F 300mm
3.1.6. B605/B905 (RIGHT) STANDARD INSTALLATION
F
R2R1
S1
S2
COMBUSTIBLE WALL
COMBUSTIBLE WALL
B605 (RIGHT)
STANDARD INSTALLATION
SINGLE REAR
FLUE SHIELD
SOLID CASING/
DECROMESH
Side-S1 0mm 0mm
Side – S2 838mm 838mm
Rear – R1 150mm 225mm
Rear – R2 333mm 408mm
Floor-F 300mm 300mm
B905 (RIGHT)
STANDARD INSTALLATION
SINGLE REAR FLUE SHIELD/SOLID
CASING/DECROMESH
Side-S1 0mm
Side – S2 939mm
Rear – R1 175mm
Rear – R2 357mm
Floor-F 300mm

7
3.1.8. B600/B905 (L/R) CORNER INSTALLATION
COMBUSTIBLE WALL
COMBUSTIBLE WALL
C
F
B605 (LEFT/RIGHT)
CORNER INSTALLATION
SINGLE REAR FLUE SHIELD/
SOLID CASING/DECROMESH
Corner-C 150mm
Floor-F 300mm
B905 (LEFT/RIGHT)
CORNER INSTALLATION
SINGLE REAR FLUE SHIELD/
SOLID CASING/DECROMESH
Corner-C 150mm
Floor-F 300mm
3.2. FLOOR PROTECTOR (HEARTH)
Unless the heater will be standing on a heat
resistantoorsuchasconcreteslabwithslate
ortiles,itwillbenecessarytoprovideaoor
protector (hearth).
The dimensions given on the previous pages
(“3.1. Positioning the Heater”) are the minimum
requiredfortheoorprotectortoextendbeyond
thereboxdooropening.Itmustextendnoless
than 300mm in front of the door opening, no less
than 200mm either side of the door opening, and
extend under the heater.
MEASUREMENT B600/
B605
B900/
B905
Door opening
width 500mm 600mm
Minimumoor
protector width 900mm 1000mm
It may be desirable, e.g. for aesthetic reasons,
fortheoorprotectortobelargerthanthese
minimum dimensions.
Theoorprotectormustbeconstructedofnon-
combustible material no less than 7.5mm thick
and with a thermal conductivity not greater than
0.33W/m °K, e.g. compressed cement sheet.
Theoorprotectormaybelaiddirectlyonthe
combustibleoor.
Formoredetailsandvariationsonoorprotectors
refer to AS/NZS 2918:2018 Clause 2.2, 3.3.1, & 3.3.2.

8
4. REDUCING CLEARANCES TO
COMBUSTIBLES
If it is necessary to install a heater closer to a
combustible surface than the stated requirements
in Section 3 of this Installation Guide, it must be
done in accordance with Australian Standard AS/
NZS 2918:2018 Section 3, Tables 3.1 & 3.2.
Shield Construction: The shield shall be
constructed from a heat resistant material. The
shieldmustbexedtothesurfacethatrequires
protection and NOT the heater.
The Standard allows three options to reduce
stated clearances.
Single layer of continuous material with Minimum
Air Gap of 12mm—Clearance Factor = 0.40
Single layer of continuous material with Minimum
Air Gap of 25mm—Clearance Factor = 0.30
Two spaced layers of continuous material with
Minimum Air Gaps of 12mm + 12mm—Clearance
Factor = 0.20
The shielding must be open at the top and bottom
(vented)toallowacontinuousairow.Itisthisair
owthatkeepsthesurfacerequiringprotection
cool.Fixingsshouldnotimpedethisairow.
The shielding needs to go far enough along and
up the wall so that the original side and rear
required clearances are not compromised. As the
ueisnowclosertothewalltheshieldingshould
alsoprotectthewallfromtheuepipe.
For example:
Side wall clearance for the B600 is 425 mm.
A 12mm gapped shield on the wall with a factor
of 0.40.
Calculate:-425mmx0.40=170mm.Thisisthe
new side wall minimum clearance.
The shielding needs to be large enough so that
none of the original clearances of 425 mm are
compromised.
5. INSTALLING THE FLUE
Theuesystemusedwheninstallingtheheater
MUST comply with the current installation standard
AS/NZS 2918.
Fullinstructionsontheinstallationoftheuewillbe
suppliedwiththeuekit.TheseMUSTbefollowed
closely, including the minimum exit height from
thetopoftheoorprotectorbeingnotlessthan
4.6m, and the minimum exit height above the roof
line of roof ridge as detailed in the instructions.
Theuemustbettedwithoneofthefollowing:
1. Rear Flue Shield:
a. 900 mm long, minimum 160° arc,
stainlesssteelpaintedblackrearue
shield with 25mm gap between it and
the150mmdiameteractiveue,and
25mm above the top of the heater.
2. Decro-mesh/SolidFlueShield:
Note: MUST be installed with the manufacturer’s
490mmtallinnerueshieldANDventilateddecro-
mesh locating ring.
a. A full length, half radius perforated
decro-meshueshieldextending
from the heater through into the drop
box penetrating the ceiling with the
perforated surface facing the front,
ORequivalentinsolidouterueshield
casing (7.75” diameter)
b. The 490 mm half round stainless steel
innerreectorsuppliedwithheater
mustbettedinsidethedecro-mesh
orsolidouterueshield.
c. Themanufacturer’sdecro-mesh
‘locating ring’ must be used to
supporttheueshieldingandinner
shield up off the heater top. It is
important that air can be drawn
intothebaseandrearoftheue
shielding.

9
d. Placethelocatingringabovetheue
spigot (resting on the top plate) and
thenplacetherstlengthof150mm
activeueintothespigot.Withthe
490mminnershieldttedinsidethe
decro-meshorsolidoutershield,slide
theshieldingovertheactiveue.
Locate the bottom of the decromesh
or solid outer shield and inner shield
inside the locating ring.
DECROMESH/
SOLID FLUE SHIELD
INNER REFLECTOR
ACTIVE FLUE
LOCATING RING
e. Dependingonthesupplier,theue
shielding can be one of three sizes –
200 mm, 7 ¾ inch, or 8 inch diameter.
Thedecro-meshringwilltthetwo
smaller diameters but not the 8 inch.
In this scenario, snip through the outer
ringwithtin-snipsasshowninthe
drawing below. Bend the two “arms”
in a little so they ends don’t project
outwhenttedtothedecro-mesh.
Ensure that the snipped section is at
therearoftheue,outofsight.
BEND IN SLIGHTLY AFTER
SNIPPING IN CENTRE
OUTER CASING NO
LESS THAN 25MM
CLEARANCE TO
COMBUSTIBLES
SECURING ANGLES
CEILING RING
REAR FLUE SHIELD,
DECROMESH OR
SOLID OUTER
CASING
STAINLESS STEEL
INNER FLUE SHIELD
INSIDE THE REAR
OF DECROMESH
OR SOLID OUTER
FLUE SHIELD
FLOOR
PROTECTOR
STAINLESS
STEEL COWL
FLASHING
CEILING
5.1. FITTING FLUE SEAL
Anygapsbetweentheinsideoftheuespigot
andtheactiveueshouldbesealed.Thiscanbe
donebywrappingthebottomoftheuewiththe
lengthofbreglasstapesupplied.Alternatively,
high temperature stove cement can also be used.
6. INSTALLING THE ASH PLATE
The ash plate acts to protect the front of the
reboxbelowthedooropeningfromthehotcoal
bedandre.
When positioning the ash plate, ensure that the
frontfaceisushwiththedooropeningface,as
shown in the diagram on the following page.

10
7. INSTALLING THE BAFFLE PLATE
Thebafeplateshouldbeinstalledbefore
installingtherebricks.
1. Placethebafeinsidethereboxwiththe
slotted fold directed downwards and at
therearoftherebox(refertofollowing
diagram for correct orientation).
2. Raisethefrontofthebafe,tiltingitbackso
that it clears and rests on the front support
rods.
3. Raisetherearofthebafe,bringingit
forward enough to clear the rear support
rods.
4. Once clear of the rear support rods, push
thebafebacksothatitisrestinghardup
againsttherearoftherebox.
5. Centralisethebafesothatgapsbetween
eachsideandreboxareequal.
BAFFLE
NOTE: B900/B905
HAS ADDITIONAL
FOLD HERE
ASH PLAT
E
8. INSTALLING THE FIRE BRICKS
Placethebricksintothereboxasshowninthe
diagrams below for the B600/B605 and B900/B905.
Oncebricksarein,ttheretaineroverthetopto
hold them in place.
B600/B605:
●Two full size (220 x 175 x 25) and one (220 x
140 x 25) along the back.
●One full size and one half size (220 x 85 x 25)
along each side.
●Two full size and one half size in the base.
B900/B905:
●Three full size (270 x 175 x 25) along the
back.
●Two full size along each side.
●Three full size in the base.

11
9. RELOCATING THE FAN ASSEMBLY
In the B605 & B905 models, the fan assembly is
located in the centre of the base unit by default.
If choosing to install the body on either side of the
base, the fan assembly will need to be relocated
to the same side.
1. To relocate the fan remove the M12 screw
with the Allen key supplied.
M12 SCREW
2. Slide the fan across to the relevant side
beneaththereboxbodyandrettheM12
screw in the new location (note, depending
on which side, this may require moving the
controllerunitrst).
3. To relocate the controller unit remove the
M6 screws with the Allen key supplied.
4. Relocate the controller unit to the other side
ofthebaseandrettheM6screwsinthe
new location.
Default Fan Assembly Conguration:
M6 SCREWS
Left Body Fan Assembly Conguration:
FAN ASSEMBLY
CONTROLLER UNIT
10. RELOCATING THE BLANKING PLATES
The B605 & B905 has two blanking plates which
block out a sliver of light that can be seen
betweenthereboxbodyandtheglasspanel.
The blanking plates are located in the two outer
openings by default, as shown below. If choosing
to install the body on either side of the base unit,
both blanking plates will need to be removed and
onerettedinthecentreontheoppositesideto
thereboxbody.
Each blanking plate assembly consists of two PK10
X 0.5 inch screws and one folded piece of sheet
steel.
1. To relocate the blanking plate remove the
PK screws with a standard Phillips head
screwdriver.
2. Move the plate to the desired location,
ensuring that the fold is located at the rear
and that the holes line up.
3. RetthePKscrews.
Default Blanking Plates Conguration:
PK SCREWS
BLANKING PLATES
Left Body Blanking Plate Conguration:
PK SCREWS
BLANKING PLATE
Therightbodyblankingplatecongurationisthe
inverseoftheleftbodyconguration.

12
11. INSTALLING THE GLASS PANELS
B600 & B900 – Glass Location
1. Place glass inset 3mm from each side of the
base.
2. Slide glass back until it butts with the base
rear face.
GLASS
3m
m
3mm
3m
m
REAR FACE
B605 & B905 – Glass Location
1. Press suction cups into the small holes
underneath the desired glass location (note,
thereboxcanbelocatedinthemiddleof
the base, or to the left or right).
2. Ifthereboxbodyisinthecentre,there
will be 6 suction cups to be inserted on
eachside.Ifthereboxbodyislocatedon
one side, there will be 9 suction caps to be
inserted.
3. Locate the glass panel(s) so that the outer
edges are inset 3mm from the base outer
edges.
4. Apply light downward pressure for suction
cups to take hold.
SMALL
HOLES

13

14
12. TECHNICAL DRAWINGS
12.1. B600
751.4
662
891.1
FRONT
478
556.9
LEFT
331
183
TOP

15
12.2. B605
662
886.6
508
1170
LEFT CONFIGURATION
662
886.6
1170
508
RIGHT CONFIGURATION
662
886.6
254 254
1170
FRONT
478
556.9
LEFT

16
12.3. B900
762
851.4
941.1
FRONT
518
596.9
LEFT
381
182
TOP

17
12.4. B905
762
936.6
279
1320
279
FRONT
518
596.9
LEFT
762
936.6
558
1320
LEFT CONFIGURATION
762
936.6
1320
558
RIGHT CONFIGURATION

18
Glen Dimplex Australia Pty Ltd
8 Lakeview Drive,
Scoresby Victoria 3179
Australia
T: 1300 554 155
General&SalesEnquiries:[email protected]
TechnicalService:[email protected]
www.glendimplex.com.au
Other manuals for B600
3
This manual suits for next models
3
Table of contents
Other Blaze Indoor Fireplace manuals
Popular Indoor Fireplace manuals by other brands

Montigo
Montigo DelRay DRL3613NI Installation & maintenance manual

Empire Comfort Systems
Empire Comfort Systems MANTIS BF28(B installation instructions

Security Chimneys
Security Chimneys Bis Nova Installation and operation instructions

Infinity
Infinity 620 HD Instruction for user, Installation & Servicing

kozy heat
kozy heat PRINCETON RPC-36 Installation and optimization guide

GTI
GTI 4000TV Installation and operation instructions