Electrical Connection
SENSING CABLE L1
SENSING CABLE L2
LEAK
DETECTOR
DEVICE
Supply Voltage
WARNING
Supply voltage may be connected!
Risk of electric shock!
• When using the detector device, installation
must comply with the corresponding national
standards and regulations as well as these Safety
Instructions.
Relay Output
• The relay is in Form-C configuration
(NO, NC, COM), 10 A, 277 VAC rating. 1 Auxiliary relay
option is available if needed.
• Relay terminals are isolated from the board power
supply; and relay will connect COM to either NC or
NO terminal.
• Connect the sounder or alarm digital input signal to
the output NC relay terminal as the relay is in reverse
action configuration. Test the operation a few times
and verify functionality once connected to ensure
proper operation.
Cable Specification
• Use 22 AWG wire for all connections, preferably
twisted, screened cables.
• Do not locate the device wires in the same conduit
with inductive load wiring such as motor wiring.
!
Commissioning
Start-up
Verify that the device is correctly wired according to
the wiring diagrams and all secured. Once verified,
apply power accordingly.
5.0
5.1
Operation
The Leak Detector device, once in operation, will continuously energize the relay in the circuit. In normal
condition, the output NC relay will be in open/ disconnected position and the output NO relay will be in
contact/ closed when power is supplied to the device. The device will maintain this status until leaking will be
detected from the sensing cable.
Once leaking is detected by the sensing cable, the output NC relay will be in contact or closed and the output
NO relay will be released/ disconnected. The device will maintain this status until leaking will be resolved or
the sensing cable dries out or no longer in contact with any liquid.
As the relay is in reverse action configuration, once power is interrupted in the device, the output NC relay
will be in contact or closed and the output NO relay will be released/ disconnected. Once power is supplied
again, the device will return to its normal condition.