SELF-TESTING MAINTAINED EMERGENCY ILLUMINATION SIGNS WITH WHITE LEDs
ZLD-34 ZLD-44
ZLD-28
TECHNICAL CHARACTERISTICS
Operation temperature range
Relative humidity
Construction materials
External dimensions
Typical weight
Guarantee
Mains voltage
Maximum power consumption
Batteries (Ni-MH)
Recharging time
Battery protection
Indications
Minimum emergency duration
Degrees of cover protection
Produced in accordance with
Light source intensity (230V) / (emerg.)
220-240V AC/50-60Hz
3h
24h
Overcharging and full discharging protection
Charge LED, Lamp Fault LED, Fault LED
IP 40
3.6V/1.5Ah
125lm / 125lm 170lm / 125lm 145lm / 125lm
4.3W / 6.9VA4W / 6.7VA3.8W / 6.5VA
EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3, EN 1838
0 40 C
o
to
up to 95%
Aluminum, plexiglas
290x152x38mm
3 years (1 year for the battery)
350x222x38mm 450x275x38mm
922504450_09_018
Page 1 from 4
Thank you for purchasing this product of Olympia operation test is initiated. During this test period
Electronics. A European manufacturer. all indication LEDs are OFF.
GENERAL Automatic test
oThis test includes all the operations that provide
These luminaires are used indoors (ta 40 C)
the manual test and is conducted automatically
where emergency light is needed.
every 15 days. In order to be performed, the
Each luminaire must be permanently connected
main power supply and the battery should be
to mains power supply.
connected.
In normal operation the led strip lights and the
Automatic Autonomous Test
battery is charging.
The Automatic Autonomous Test is conducted
In case of a mains power supply failure the
and measures the luminaire`s back up
luminaire will light the led strip automatically in
operation. This test is conducted automatically
emergency mode (powered by its battery). When
every six months. In order to be performed, the
the mains power supply is restored the device
main power supply and the battery should be
turns to normal operation.
connected (the battery should be charged). If
Installation
the battery is not charged, the test is postponed
To install the illumination sign you must follow
until the battery is completely charged. If during
the installation instructions on pages 2 and 3.
the Automatic Autonomous Test the luminaire’s
Battery Cut-off
duration is lower than the named, then the
The luminaire enters in this operation when the
battery must be replaced.
mains power supply fails and battery has lost its
Back Up Operation
energy. During this operation the luminaire
The autonomous duration of battery during
enters the idle state and battery consumption is
emergency mode is at least the one that is
negligible, in order to be protected from deep
stated in the list of the first page. During
discharge.
emergency mode, a LED strip test is also
Battery charging
performed.
The battery charging is completely controled. In
Resetting Errors
this case, is achieved the perfect battery
Push the Test button for 5 seconds, to
maintenance , as well as the elongation of its
extinguish all the indicated LED errors. Then
duration. When the
the luminaire enters regular operation mode.
battery has completely charged, it charges with
Changing the operating mode
a maintenance current.
Press and hold the TEST button for more than 5
Manual Test
seconds, the luminaire will erase first the errors (3
The manual test can be conducted only if the
LED indicators will light in succession) and after 2
main power supply and the battery is
seconds the LED Lamp Fault will remain lit
connected.By pressing the test button briefly an
High Quality European based Manufacturers
700gr. 1060gr. 1570gr.
Page 2 from 4
steadily. When the TEST button is released, the Blink (With AC Charge LED ON): Autonomy or
luminaire will change between maintained or no- low battery problem
maintained mode. The change is recorded (the battery must be replaced).
permanently in it’s memory. Blink (With AC Charge LED Off):
Indication LED status (with connected mains No charging current or disconnected battery.
power supply).
AC Charge
On: Good charge current.
Οff: No battery (No charging current or
disconnected battery).
Lamp fault
Οn: faulty LED strip (must be
checked by an authorized personel).
Off: Good LED strip.
Fault
Οff: Battery OK.
Ceiling mounting
Mounting methods
Recessed mounted installation
on suspended ceilings using
the base type Α-1018,
Α-1020, Α-1021
Electric connection and dimensions (in mm)
ZLD-28 : 290(α) x 95(β)
ZLD-34 : 350(α) x 165(β)
ZLD-44 : 450(α) x 215(β)
Suspended ceiling
mounting bases
β
60mm
α
Hanging installation on
suspended ceilings using the special
mounting brackets contained
in the package. 2.Tighten the screw
1. Place the plastic part
3. Pass the cable thru the knock out
and connect the wires to the terminal block
4. Place the mounting accessories on the wall
and tighten the mounting screw
5. Place the plastic cover
TEST
BUTTON
CHARGE
LED
FAULT
LED
LAMP
FAULT
LED
INDICATION LEDs
L N
220-240V AC/50-60Hz
A-101 8
280
A-102 0
342
75
Ø6
75
A-102 1
440
75
Ø6
Ø6
922504450_09_018
Page 3 from 4
Alternative mounting method
Wall mounting
3. Pass the cable thru the nut and the
extension pipe and tighten it
6. Hang the luminaire and adjust the
metall cover by the screw of the
metall ring
2. Tighten the screw
1. Place the plastic part
4. Pass the cable thru the knock out
and connect the wires to the terminal block
5. Place the plastic cover
ATTENTION!!!
All metall parts must be connected to ground
A limited number of extensions can be used in order to
maintain the stability of the luminaire
2. the screwTighten
1. Place the plastic part
3. Pass the cable thru the knock out
and connect the wires to the terminal block
4. Place the mounting accessories in the wall
and tighten the mounting screw
5. Place the plastic cover
Wall in bottom view
Hanging installation
using the special
mounting sets
Flag mounted installation on
a wall using the special
mounting bracket
contained in the package. 2. Tighten the screw
4. Place the mounting accessories in the wall
and screw the mounting screws
3. Connect the wires to the terminal block and pass
the cable thru the knock out
1. Place the single mounting plastic part
Wall mounted installation
using the special mounting
brackets contained in the
package.
Extension ability
In recess mounting in suspended ceiling or in external ceiling
mounting, we can use the Α-1022 extension set (20 cm), the Α-1025
extension set (40 cm), and the Α-1026 (60 cm)extension set after
request.
A-1026
A-1022
A-1025
TYPE
DESCRIPTION
Extension set 20 cm.
Extension set 40 cm.
Extension set 60 cm.
922504450_09_018
Battery replacement process
12
922504450_09_018
Page 4 from 4
3
4
(*) Maintained operation: The luminaire lights its illumination source, when it is powered by the
mains power supply or not.
Non-Maintained operation: The luminaire lights its illumination source, only in power supply’s
failure.
In case that the led strip must be replaced to ensure lumen output LED module can be replaced
only by a competent personnel.
NOTE:
LED= Light Emitting Diode
LABELING EXPLANATION:
X: Self contained
1: Maintained (*)
A: Including test device
180: 3 hour duration
1 Unfasten the 4 screws without moving the marking panel.
2 Unfasten the 4 screws and remove the marking panel.
3 Slide out carefully the electronic parts and the battery.
4 Install the battery’s connector to the appropriate P.C.B connector.
5 Slide in carefully the electronic parts and the battery.
6 Refit the marking panel and fasten the removed screws in steps 1 and 2.
WARNING!! Use a maximum torque of 0,25Νm to tighten the screws.
ΝΟΤΕ!! In case of battery replacement the used battery must be replaced with a new one of
the same type, by the manufacturer or by a competent person.
NOTE!!
After finishing the installation you must power the luminaire at least for 24 hours for battery
charging to perform the named autonomy.
General:
1. Operations for installation, maintainance or testing must be done by authorized personel only.
2. The device must be connected to the mains power supply thru a fuse dependent by the total
amount of the line’s power load.
t i
in battery recycling points. Do not incinerate.
3. In case of inactive use for a period greater than 2 months, disconnect the battery by pulling out
the battery’s connector.
4. I s not allowed to discard batteries in to common trash bins, they must be discarded
only

This manual suits for next models

2

Other Olympia Security Sensor manuals

Olympia 6105 User manual

Olympia

Olympia 6105 User manual

Olympia 5993 User manual

Olympia

Olympia 5993 User manual

Olympia SECURE Series User manual

Olympia

Olympia SECURE Series User manual

Popular Security Sensor manuals by other brands

Master Vega BT quick start guide

Master

Master Vega BT quick start guide

Lazer Safe SENTINEL PLUS Operation manual

Lazer Safe

Lazer Safe SENTINEL PLUS Operation manual

TRIGA TR-PC2RL Installation and maintenance instructions

TRIGA

TRIGA TR-PC2RL Installation and maintenance instructions

DINUY DM KNT 002 quick start guide

DINUY

DINUY DM KNT 002 quick start guide

Datalogic IO-Link S65-PA-5-M53 instruction manual

Datalogic

Datalogic IO-Link S65-PA-5-M53 instruction manual

IMI SENSORS 682B05 operating guide

IMI SENSORS

IMI SENSORS 682B05 operating guide

Renkforce 1289331 operating instructions

Renkforce

Renkforce 1289331 operating instructions

Hewall Safety 7102-4000 user manual

Hewall Safety

Hewall Safety 7102-4000 user manual

Optoelectronics R506 user manual

Optoelectronics

Optoelectronics R506 user manual

SEA LOOP 23105158 manual

SEA

SEA LOOP 23105158 manual

Datasensing S3N-PR T5 Series manual

Datasensing

Datasensing S3N-PR T5 Series manual

CST/BERGER Magna-Trak Series Original instructions

CST/BERGER

CST/BERGER Magna-Trak Series Original instructions

ESYLUX EP10427404 operating instructions

ESYLUX

ESYLUX EP10427404 operating instructions

Evolveo WiFi EYE manual

Evolveo

Evolveo WiFi EYE manual

AVS Electronics JET DT manual

AVS Electronics

AVS Electronics JET DT manual

Philips CHLORIDE COMPAC CXX Series instruction sheet

Philips

Philips CHLORIDE COMPAC CXX Series instruction sheet

BuckEye Cam X80 user manual

BuckEye Cam

BuckEye Cam X80 user manual

teko Astra-5 ver.A user guide

teko

teko Astra-5 ver.A user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.