manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Bosch
  6. •
  7. Boiler
  8. •
  9. Bosch Worcester 240 Combi OF User guide

Bosch Worcester 240 Combi OF User guide

....--~~~ORCESTER-----.
BOSCH
240
Combi OF
WALL
MOUNTED
COMBINATION
BOILER
FOR
CENTRAL
HEATING
AND
MAINS
FED
DOMESTIC
HOT
WATER
INSTALLATION AND
SERVICING INSTRUCTIONS
GC
NUMBER
47
311
09
BOILER
OUTPUT
Automatic Modulating Control
To
Domestic
Hot
Water and Central Heating
Minimum
9.2 kW
(31
,400
Btu/h)
Maximum 24.0 kW (82,000 Btu/
h)
IMPORTANT:
THIS
APPUANCE
IS
FOR
USE
WITH
NATURAL
GAS
ONLY
THESE
INSTRUCTIONS
APPLY
IN
THE
UK
ONLY
THESE
INSTRUCTIONS
ARE
TO
BE
LEFT
WITH
THE
USER
OR
AT
THE
GAS
METER
Contents
1. Installation Requirements
....
.....
........
.
.................
.
.........
Page
2
2.
General
Information
....
.
..
........
...
..................................
..
Page
2
3.
Technical
Data
................
..
.
......
...........
.....
..................
.....
Page
4
4.
Siting
the Appliance
..............................
.
.......................
Page
5
5.
Siting
the
Flue
Terminal
..................
..
......
.............
....
.
....
Page
6
6.
Air
Supply
....
........................................................
..
...
..
....
Page
6
7.
Sealed
System
....................................
..
......
..
......
..
....
......
Page
7
8.
Open
Ven
t
Pr
im
ary
Water
System
......
...............
.........
Page
8
9.
Domestic
Hot
Water
..............................
.
..
..
....
...............
Page
8
1. Installation Regulations
1.1
Gas
Safety (Installation and
Use)
Regulations 1984
All
gas appliances must
be
installed
by
a competent person
in
accordance
with
the above regulations.
Failure
to
install appli·
ances correctly could lead to prosecution.
1.2
The
manufacturers notes must
no
t
be
taken
,i
n any
way
,as
overrid
ing
statutory obligations.
1.3
The
compliance
with
a
British
Standard does
not.
of
itself.
con
·
fer
immunity
from
legal
obligations.
In
particular the installation
of
this
appliance must
be
in
accordance
with
the
relevant
require
·
ments
of
the
Gas
Safety
(Install
ati
on
and
Use)
Regulations
1984 as
amended, current
lEE
Wiring
Regulations,
local
Building
Regu
la
·
tions,
Building
Standards (
ScotlandXConsolidation)
and
byel
a
ws
of
the
local
Water
Company
.
Health
and Safety Document
No
. 635
(
Electridty
at
Work
Regulat
ions
).
!t
should
be
in
accordance w
ith
the
relevant
recommendations
of
the f
ollowing
B
ritish
Standards.
BS
6798:1987
Specifi
cati
on
for
installati
on
ofgas
fired
hot water
b
oilers
of
rated input
no
t exceeding 60
kW.
BS
5449
:19
90
Centra
l
Hea
t
ing
for Domestic Premises.
BS
5546:1990 Installation of gas hot water supp
li
es
for
domes·
tic
purposes.
BS
5440
:1
:1990
Flues
and
Ven
tilati
on
for
gas appliances
of
rated
in
put not exceedi
ng
60
kW:
Flues
.
BS
5440:2:1989 Flues and
Ventilation
for
gas appliances
of
rated
input not exceeding
60kW
:
Air
Supply.
BS
6891
:1988 Installa
ti
on
of
l
ow
pressure gas pipework installa·
t
ions
up
to
28
mm
(R
1).
1
.4
To
ensure that the installation
will
perform to the highest
standards, t
he
system and components should conform to any
other relevant
Br
itish Standards
in
addition
to
those mentioned
in the instructions.
2. General Information
2.1
This
appliance is
not
suitable
for
external installation.
2.2
The
appliance controls are set to provide a maximum
output
for
the domestic hot water
of
24
kW
and a central
heating load
of
up
to
16
.1
kW
.
2.3
The
appliance has a permanent
pilot.
2.4
PRINCIPLE APPLIANCE COMPONENTS See
Fig
. 1.
A
low
thermal capacity
Gas
to
Water
heat exchanger.
A
Water
to
Water
heat exchanger
to
provide domest
ic
hot
water.
Fully
modulating controls
in
the central heating and domes
tic
ho
t water modes
of
operation.
An
expansion vessel, pressure gauge and pressure
relief
valve
.
A
by
·pass
for
the central heati
ng
system.
Temperature safety cut·out controls.
Awater
flow
regulator.
2
10.
Electrical
..........
..
.....
...
.......
....
.
......
..
....
.....................
........
Page 10
11
. Installation
........
..
......
....
....
..
......
.
......
................
....
..
..
......
Page 13
12
.
Commissioning
..
....
..
...............
..
..................
......
..
....
..
.....
Page 15
13.
Instructions
to
the
User
...........................................
...
..
Page 16
14
. Inspection and Servidng
..........
..........................
........
..Page 17
15
. Replacement
of
Parts
.....
.
..
..
.
...........................
...
..
....
.
....
Page 19
16
. Short Parts List
...
...............
....
..........................
....
.
....
.....Page 25
17
. Operational
Flow
Diagram
.
..
.........
..
....
..
..
...
..............
.
....
Page 26
18.
Fault
Finding
.
..
.
...
.
...
.
........
.....
.....................
..
..............
..
...
Page
28
An
optional
facia
mounted programmer instead
of
the standard
Operating
Switch
.
2.5 ELECTRICAL SUPPlY
Mains supply:
240V
-,
50
Hz,
150 watts. External fuse
3A.
Internal fuses:
T2A
(F1)
and
T315mA
(F
2).
2.6
GAS
SUPPLY
The
boiler requires 2.
82
m'
/h
(9
6.8
ft
'/hr)
of
gas.
The
gas meter
and supply pipes must be capable
of
supplying this quantity
of
gas in addition
to
the demand
from
an
y other appliances being
served.
The
table below gi
ves
an
i
nd
icati
on
of
limiting
gas pipe
lengths and the allowance to be made for fittings.
Refer
to
BS6891
f
or
further information.
The
meter
gov
ernor should deliver a dynamic pressure
of
20
mbar (B
in
wg
.)
at the appliance.
The
complete installation,
includ
i
ng
the gas meter, must
be
test·
ed
for
soundness and purged.
Refer
to
BS
6891
.
TOTAL
LENGTH
OF
GAS
SUPPLY
PIPE
(metres) Pipe
Diamet
er
3 6 9
(mm)
Gas
Discharge Rate
(m3
/h)
2.9 - - 15
8.7
5.8 4.6
22
18.G 12.0 9.4
28
Note:
Each
fitting
used in the gas
line
from
the meter
is
equivalent to a
length
of
straight p
ipe
which
mus
t
be
added
to
the straight
pipe
length to
give
the total
length
.
ie
:
Elbow
= 0.5 metres,
Tee
= 0.5 metres,
90
°
Bend
= 0.3 metres.
2.7 GENERAL INSTALLATION
The
appliance:
is
supplied
for
connec
tion
to a sea
led
system but
is
suitable
for
use
with
an
open vent system.
The
connections
are suppl
ied
as an option
al
kit.
The
spec
ified
vent
il
a
ti
on openings must
not
be
ob
st
ruc
te
d.
Do
not
pla
ce anything
on
top
of
the appliance.
The
clearances specified
for
servici
ng
must
be
maintai
ned
.
2.8
FLUE
The
flue
mu
st
be
generally
verti
cal
and have
no
horizontal runs.
The
flue
must end
with
a
British
Gas
approved
term
i
nal.
2.9 CONTROLS
T
he
electronic control system and gas
valve
modulate the heat
input
in
response to t
he
central heati
ng
and domestic hot water
temperature settings between minimum and
max
imum.
The
Operating
Switch
provides
for
the selecti
on
of
domestic hot
Fig.
1. Appliance
water
flow diagram.
Automat
ic
air
vent
Gas
to
Water
heat
exchanger
Waterflow
man
i
fold
L_
Ce
n
tra
l
hea
ri
ng
by
·
pass
ad
j
uster
t__
- -
..
Boile
r
- -
--
-
Water
div
erter
v
alve
---,--
-:
I
I
Pr
ess
u
re
reli
ef
v
al
ve
-
Oo
mes
t
oe
hot
wate
rout
--
Ma
i
ns
col
d
water
in
-
Ce
nt
ra
l
he
at
i
ng
retu
rn
--
Cen
tra
l
he
at
i
ng
flow
water
only
(WATER)
or central heating and domestic hot water
(HEATING
&
WATER)
or
OFF
.
A
fac
ia mounted programmer
is
ava
ilable as an optional extra. A
remote mounted
prog
rammer may be connected
to
the appli-
ance.
The
integral
fac
ia displays i
nd
icate the status
of
the appliance.
There is
prov
ision
for
the connection
of
a mains voltage
room
thermostat and/or a
frost
thermostat.
The
electronic controls prevent rapid
cycling
of
the appliance
in
the central heating mode.
2.1 0
SYSTEM
NOTES
WARNING
Check that no dirt is left
in
either the
gas
and water pipework
as this could cause
damage
to the appliance. Thoroughly flush
the heating system and the cold water mains supply. Purge
the gas supply before
finally
connecting theappliance
..
The
water pipe connections throughout a sealed system must
be capable
of
sustaining a pressure
of
upto 3 bar.
Radiator valves must conform
to
the requirements
of
BS2767
(10)
:
1972
.
The
relief
valve
discharge must be directed
away
from
any
elec
-
trical components or where
it
would
cause a hazard to the
user.
Adrain
cock
to
BS
2879 must
be
fitted
to
the lowest point
of
the
system.
For
circu
it design purposes
it
is
important that due note
is
taken
of the informati
on
gi
ven
in
Table
3 relating
to
the available
pump head.
3
2.11
SHOWERS,
BIDETS,
TAPS
AND
MIXING
VALVES
Hot
and
cold
taps and
mixing
valves used
in
the system must
be
suitable
for
operating at a mains pressure of up
to
10 bar.
Thermostatically controlled or pressure equalising shower
valves will guard against the
flow
of
water at too
higb
a temper-
ature. I
Hot
and
cold
mains
fed
water can be supplied direct to an
over-
rim
flushing
bidet subject
to
local
Water
Company requirements.
With
all
mains
fed
systems the
flow
of water
from
the individual
taps will vary with the number
of
outlets operated simultane-
ously and the
cold
water mai
ns
supply pressure
to
the property.
Flow
balancing
using
'Ball
-
o-Fix'
type valves
is
recommended
to
avoid
an excessive reduction
in
flow
or
even
starvation
to
indi
-
vidual outlets.
For
further information contact Worcester Heat
Systems
Ltd
.
2.12
SAFETY
CONSIDERATIONS
The
appliance must not be operated
in
a waterless condit
ion
.
The
appliance must not be operated wi
th
the boiler inner casing
cover removed.
Work
must not
be
carried out
on
the appliance without the gas
and electricity supplies
be
i
ng
switched
off
.
Checks
must be made
to
ensure that the ventilation openings
made into
walls
and partitions
are
of
the correct size and
are
not
obstructed.
2.13
OPERATION
Domestic Hot Water:
With
a demand
for
hot
wa
ter the burner
will
light
at its maximum setting and then automatically adjust
its output to maintain the temperature rise of the delivered
water.
When
hot water
is
no
longer required, the burner
will
extinguish.
The
pump
will
continue
to
run
for
a short period
to
dissipate the residual heat
from
the appliance.
Central Heating:
With
a demand
for
heating the burner
will
light
at its
min
i
mum
setting and gradually increase
to
give
the
maxi
-
mum
output.
The
output
of
the appliance
is
then automatically
adjusted to maintain the temperature
of
the system.
The
output
can reduce down to a minimum of ?.2
kW.
If
the system
no
longer requires even the minimum output to maintain the
desired
room
temperature the burner
will
extinguish.
The
pump
will
continue
to
run
to
dissipate the residual heat
from
the
appli
-
ance.
The
appliance
will
remain
off
for
a
fixed
period
of
two
min
-
utes
before
re
-lighting
to
automatically meet the system
require-
ments.
Domestic Hot Water
and
Central Heating:
The
·appliance
will
supply
heat
to the central heating system as required. A
demand
for
domestic hot water at a tap or shower
will
override
the central heating requirement
for
the period
of
the domestic
hot water demand.
When
hot water
is
no
longer required the
burner
will
extinguish and the appliance
will
return to the
cen
-
tral heating state and its normal mode
of
operation.
The
pump
will
continue
to
run to dissipate the residual heat
from
the appli·
ance
as
necessary.
3. Technical Data
The
Data Plate is
fixed
to
the control box casing.
TABLE
1
TABLE
5
NOMINAL
BOILER
RATINGS
OUtput
Input
Burner
Setting
Gas
Rate
Pressure
Flue
Di
ameter
125mm
kW
Btu/h
kW
Btu
/h
mbar.
in
.
wg
. m3/h
tt
3/h
9.2
31
,
400
12
.6
43,000
2.7 1.1
1.17
40.2
Flue
Pipe
BS
4543
16
.1
54
,
900
212
72,300
73
2.9 2.
03
69
.6
24
.0
82,000
30
.1
102,700
15
.0 6.0 2.
82
96
.8
TABLE2
AVAILABLE PUMP HEAD
Boiler
Output
Head
Min.
Flow
Rate
Temp
.
rise
across
kW
Btu
/h
metres
feet
litres/min
gal
/
min
heating
flow
and
return
9.2
31
,
400
4.9
15
Q
120
2.
64
11
•c
(
20"FJ
16
.1
54
,9
00
2.
54
8.
25
23.0
5.
07
11
•c
(20"FJ
24
.0
82
,
000
2.0 6.5
23.0
5.
07
15
°C
{
28
°F)
TABLE
3
SPECIFICATIONS
CENTRAL
HEATING
FLOW
FriTING 22
mm
Compression
CENTRAL
HEATING
RETURN
FmiNG 22
mm
Compression
COLD
WATER
MAINS
INLET
FrrnNG 15
mm
Compression
DOMESTIC
HOT
WATER
OUTLET
FmiNG
15
mm
Compression
GAS
INLET
FrrnNG
Rc
1'2
PRESSURE
RELIEF
VALVE
DISCHARGE
FriTING 15
mm
Compression
CASING
HEIGHT
900
mm
(35.4 in.)
CASING
WIDTH
450
mm
(17
.7 in.)
CASING
DEPTH
360
mm
(14.2 in.)
WEIGHT
(including water) 48
kg
(10Sib)
INSTALLATI
ON
WE
IGHT
46
kg
(101
lb)
PACKAGED
WEIGHT
49
kg
(1
08 lb)
TABLE4
SPECIFICATIONS
PRIMARY
WATER
CAPACITY
2.7 litres
(0
.6 galls.)
MAXIMUM
COLD
SUPPLY
PRESSURE
10 Bar
(1
50 psi)
MINIMUM
COLD
SUPPLY
PRESSURE
(WORKING)
FOR
MAXIMUM
HOT
WATER
FLOW
1.6 Bar (23.5 psi)
MINIMUM
COLD
SUPPLY
PRESSURE
(WORKI
NG
)
TO
OPERATE
THE
APPLIANCE
0.6 Bar
(9
psi)
MAXIMUM
CENTRAL
HEATING
FLOW
TEMPERATURE
Nominally 82°C (180°F)
MAXIMUM
STATIC
HEAD
(PRIMARY)
25 metres (
81
ft)
MIMIMUM
STATIC
HEAD
(PRIMARY)
0.3 me
tr
es
(1
ft)
OUTPUT
TO
DOMESTIC
HOT
WATER
Modulating 9.
2-24
.0 kW
(31
,40Q-82,000 Btu
/h)
OUTPUT
TO
CENTRAL
HEATING
Modulating 9.2
-24
.0 kW
(31
,400-82,000 Btu
/h)
MAXIMUM
DOMESTIC
HOT
WATER
FLOW
RATE
FROM
THE
APPLIANCE
Nominally 8.51itres
/min
(±
15%)
(1
.87 gallons/min)
EQUIVALENT
DOMESTIC
HOT
WATER
FL
OW
RATE
Nominally 9.
8litres
/min
TO
GIVE
A
TEMPERATURE
RISE
OF
35°C (2.16 gallons
/min)
4
4. Siting The Appliance
4.1 The appliance
must
not
be installed
in
any room contain-
ing a
bath
or
shower
or
in a
bedroom,
bed-sitting
room
or
garage. Particularattention is drawn to
the
requirements of
the
current
I.E.E.
Wiring Regulations and,
in
Scotland,
the
electrical
provisions of
the
Building Regulations applicable
in
Scotland.
4.2
The
appliance
is
not suitable
for
external installation.
4.3
The
appliance does not require any special
wall
protection.
4.4
The
wall must be capable of supporting the weight of the
appliance. See
Table
3.
4.5
If
the appliance
is
to be fitted
in
a timber framed building,
refer to the British
Gas
publication "Guide
for
Gas
Installations
in
Timber Framed Housi
ng
".
4.6
The
following clearances must be available
for
installation
and
for
servicing. See Fig. 2.
Installation Servicing
Above
300mm 300mm
In
front
600mm 600mm
Below*
900mm
230mm
Right hand side
100mm 100mm
Left
hand side
100mm 100mm
4.7
No
combustible surface must be within 75 mm of the cas·
ing
. See BS476:4.
4.8 Always consider the possible need to disconnect the pipes
from the appliance after installation.
4.9 Boilers in roof
spaces
or
in
understair
locations require
special conditions.
Refer
to
BS
6798.
* 4.
10
The appliance must have a minimum clearance of900 mm
between the bottom
ofthe
appliance and the floor.
Fig.
2.
Appliance casing dimensions
and
required clearances.
106mm
SlOE
VIEW
Space
required
above
for
i
nstallalion
and
servicing
.
f-----
-----------~
Space
requ
i
red
in
front
fo
r
installat
i
on
and
servicing
.
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
:----
__
f
_________
_j
////~/////J/~
I I
I I
I I
I :
I
~--~
I
I
I
I
I
I
I
I
I
I
I
I
I
I
------~-
-
~----
~225mm
FRONT
VIEW
~-----4~mm----~
Fixing
holes
~413mm
CAS
.
___,
I
I
II
900mm
~
I
Space
required
below
/).
1
for
installation
and
serv
ici
ng
.
/)~
____
____
j t 1 I
Space
required
at
left
hand
side
-+1
I+-
-+1
il
,,,
...
, • •M
..
,......
. i
L_
______________
j! I
5
Space
required
at
right
hand
side
for
installa
tion
and
servicing
.
Fig.
3. Appliance pipework connections.
-·
·
-· "'
"":
rr-;J
__
,_::D
Centra
l
heating
flow
55
mm
Jj
Central
hearing
return
i
08
mm
Ma
i
ns
cold
water
in --114--
--
161mm
Domest
ic
hot
water
out
-1--
----
216
mm
-----<
~
Pressure
relief
valve
discharge
-1--
-------
306
mm
--
~
tt\·r:!\
-w·o
_,....,..YI.III_
Gas
cock
-
1--
-----------
405mm
------
-~
5. Siting
the
Flue Terminal
The
flue
diameter
is
125
mm
Refer
to
BS
4543.
5.1
The
flue
must
be
installed as
specified
in
BS
5440:
Part
1.
5.2 A means
of
dis
-connection
of
the
flue
should
be
provided
and positioned immediately above the appliance draught divert·
er
.
5.3
Horizontal
flue
runs should be
avoided
and the
flue
should
terminate
in
accordance with the requirements
of
BS
5440
:1.
The
terminal must be
of
a type approved
by
Br
itish
Gas
and
must not be
within
600
mm
(24
in)
of
an
openable
window.
air
vent
or
other ventilation opening.
5.4
If
the
flue
is
to
be taken through the
wall
behind the
appli·
ance t
hen
adequate space must
be
available
to
allow
the
fitting
of
a suitable
flue
bend. A right·
angle
bend
is
not
acceptable. A
minimum
of
600
mm
of
verti
cal
flue
pipe
is
required
before
the
introduction
of
a bend.
If
the
flue
is
taken through the
ceiling
and i
nto
the
roof
·space
or
room
above then a
sleeve
of
non
·
com
·
bustible material allowing an air-space of at least 25
mm
between the
flue
and the
sleeve
must
be
provided.
The
flue
pipe
must
be
held
in the centre
of
the
sleeve
.
6.
Air
Supply
6.1
The
room
in
which
an
appliance
is
installed must
have
a
per
·
manent
air
vent
to
outside air or
to
a
room
which itse
lf
ha
s
6
direct access
to
outside air.
The
minimum
effect
i
ve
area
of
t
he
air
vent(s)
must
be
104
cm
2.
6.2
There
must
be
sufficient
clearance around the appliance
to
allow proper circulation
of
ventilation air.
The
clearances
required
for
Installat
ion
and
Servicing
will
normally
be
adequate
for
ventilation.
See
Section
4.6.
6.3
The
minimum
free
areas
required
are g
iven
below
.
Position
of
Air
from
Air direct
air vents the room
from
outside
High
Level
271
cm
2•
135
.5
cm
2.
(42
in
2.)
(21
.5 in2)
Low
Level
542
cm
2•
271
cm
2•
(
84
in
2.)
(42
in
2.)
6.4
Refer
to
BS
6798 and
BS
5440:2
for
additional information.
6.5 A
spillage
test, as detailed
in
855440:1, must
be
carried out
and any remedial acti
on
taken
to
ensure that the installation
meets the standard.
The
effect
of
any
type
of
extract
fan
in the
premises must
be
considered and
an
additional air
inlet
may be
needed
from
outside
to
counter the
effect
of
the
fan
.
7. Sealed System
7.1
The
system must comply with the requirements of
BS
6798
and
BS
5449:
1.
7.2 The appliance
must
not be operated without the system
being
full
of
water, properly vented and pressurised.
7.3 The pressure relief valve operates
at
3 bar (45lb/in").The dis-
charge must be directed away from electrical components or
where it might be a hazard to the user.
7.4 The pressure gauge indicates the system pressure which
must be maintained.
7.5
The
10 litre expansion vessel
is
charged to 0.5 bar and
is
suitable
for
a static head
of
5 metres
(17
.
5ft)
. The pressure can
be increased
if
the static head
is
greater than 5 metres
(17
.Sft)
.
7.6
With
an initial system pressure of 0.5 bar, a system capacity
of
about 104litres can be accommodated.
Refer
to
BS
7074 Pt. 1
for
more information.
The
charge pressure can be increased but
with a decrease
in
system volume.
7.7
The
filling
point must be at
low
level.
See
Fig. 4.
Fig.
4 Sealed primary water system.
L
ocl<shield
valve
.
Radiator
valve
.
l
11111
111
J IIIIIllI
Note
.A
dtm
c:oc:1t
should
be
installed
at
the
lowest
point
of
the
heating
cir
cuit
and
beneath
the
appliance
.
Fig.
5. System filling
and
make-up.
Heating
Return
Non
return
valve
....
Worcester
Combi-Fill
System
Non
return
va~
~
Hose
union
l
1-----t..•-
...
-t..•-""
:
=:
zr,
::u
I 1
~
~
!l
i~
Stop
cock
II
II
Test
cock
·
:
~==•.]
:
Temporary
hose
7
7.8 Water loss
must
be
r~placed
.
See
Fig
6. The connection
should
be
made in the central heating return
as
close to
the
appliance as possible.
7.9 The make-up vessel,
if
fitted,
mus
t
be
fitted with a non-
return valve.
7.
10
Repeated venting loses water from the system. it
is
essen·
tial
that
this water is replaced and the system pressure main-
tained.
7.11 Connections
to
the mains water supply must not be made
without the authority of the local Water Company.
7.12 The pump
is
set
at
maximum and must not be adjusted.
7.13 Connections
in
the system must resist a pressure of up to 3
bar.
7.14
Radiator valves must conform to
BS
2767(10):1972.
7.1
5 Other valves used should conform to the requirements of
BS
1010.
7.
16
To
make use
of
the extra heating available
from
the appli-
ance
at
the end of any demand,
it
is
recommended
that
a single
small radiator be left permanently open.
Central
heat
i
ng
Suled
system
--expansion
vessel
-·
Water
to
Wa
t
er
heat
excltlnger
by-pass
ad
j
uster
-
~+----l-+--+----J
Fill
po
i
nt
----
Heamg
return
Heating
flow
.
Heating
Return
'
I
I
l
Nola
.
The
mains
cold
i
nlet
connection
to
the
app
li
ance
must
come
before
any
other
connection
from
the
cold
supply
.
Auto
air
vent
....
....,..__
FiiiPoint
'
Heating
Return
Domestic
cold
water
.
._
British
Standard
stop
valve
.
Fi
xed
spindle
type.
-
Wa
t
er
mai
n.
JOOmm
(
12
inl
min
.
above
the
hi
ghest
po
i
nt
of
the
system
.
8. Open Vent Primary Water System
See
Fig
. 7
8.1
The
size of the
flow
and return pipework
is
given
in
Section
3 -
Thble
4.
The
components required to connect the appliance
to an open vent system are available as an optional extra
kit.
8.2
The
feed and expansion cistern should be arranged
so
that
there
is
a minimum static head of 0.3 metres (12in.) above the
top of the appliance
or
above the highest point
in
the heating
circuit, whichever
is
the higher. See F
ig
. 6.
8.3 The feed and vent pipe should be 22 mm diameter
and
rise
continuously
from
the appliance to the feed and expansion cis·
tern.
Fig.
6. Open ventwater system.
Feed
and
expansion
tank
8.4 Apressure relief valve is not required on an open vented sys·
tern.
If
the
pressure relief valve
is
left
in
position then a discharge
pipe must be fitted which terminates
in
a position such
that
any
water or steam discharge does not cause a hazard to the occu·
pants or damage electrical components.
8.5 Air w
it
hin the appliance
will
be expelled via the feed
and
vent connection or dissipated into the rest of the system which
must be fitted with manual air vents
at
any high point.
8.6 The pump is set to maximum and must not be reset.
8.7
To
make use of the extra heating ava
il
able from the appli·
ance
at
the end of any demand,
it
is
recommended
that
a single
small radiator be left permanently open.
-
Overflow
.
S.H
.-
Mnmum
statiC
hud
300
mm
11
2
111
.1
me85Uied
from
the
top
surface
of
the
appliance
or
t.ghest
point
in
the
heattng
system
to
the
wat
er
level
in
the
feed
ill1d
expansiOn
tank
.
-r
·- ·- ·- ·
:-_-:_-==:
-·- ·r
S
.H
.
j
Primary
feed
ill1d
vent
S.H.
;~-;--;jj
1
-
1
jl
r-
--
-
----,
pipel22mmlmustrise-
l " " I • I I I : I I :
II
: : I I
contiooously
.
I I I I I I I I I I
::I
I
I'
I
I
I:
I I I I I I I J I I I I I I I I I
I
::
I I I I I I I :I I I I I I I I :
,tl
.
I'!
I I
I
~
.!.,
I I
II
I'
I I .
...
\'
-
----
---~
~---------'~
'T
• I I
-----
- - -
t-
-
--
- - -
_;
- - -
~
-
--
-
--
-
~
---
-
...,
0 I
- -
--L
-
_________
.:.
__
-
---
-
---,
lockstoeld
v...,•
.
Radllltor
valvt.
l
tlll
llll
J
llllllll
Nott
.A
dr0111
cock
should
be
InStalled
at
the
lo
west
poont
of
the
heat
tng
c1r
cut
ill1d
beneath
the
appliance
.
9. Domestic Hot Water
9.1 The following are gener
al
requirements and,
if
necessary,
reference should be made to the local Water Company before
fit
·
ti
ng the appliance.
9.2
MAINS
COLD
WATER
INLET
. Devices capable of preventing
the
flow
of expansion water must not be fitted unless separate
arrangements have been made.
An
expansion vessel connection
point
is
provided within the appliance.
A 15mm connection is provided on the domestic
water
inlet
elbow. A Zilmet Z160 is the preferred type. A thread
sealant
compatible with potable water must be used.
9.3
The
final
600 mm ofthe mains cold water connection to the
appliance should be made
in
copper tube only.
9.4
The
appliance is suitable
for
a mains pressure of up to 10
bar (150 lb/
in
").
I
I
8
Central
h
ea
un
g
-·
Water
to
Wate
r
h
eat
ex
changer
by
-
pass
ad
ju
ste
r-
~±--t+-1----'
,
F
ill
point
--
---'
Heating
return
Heat
ing
f
low
.
'
Nota
.
The
ma.ns
cold
1
nle1
connection
to
the
appfta
nce
must
come
before
any
other
connection
from
the
cold
supp
ly
.
Domest
ic
cold
water
.
._.
B
rinsn
St
andard
stop
valve
.
Fixed
spindle
type
.
....
Waterma
111
.
9.5 The appliance is fitted with a mains supply isolating valve.
9.6
The
maximum
domestic
hot
water
flow
rate
is 8.5
litres/min (±15
%)
(1
.87 gallons/min).
9.7
In
winter (when the mains inlet water temperature is lower)
a reduced
flow
rate at the taps
will
be required to achieve the
maximum hot water delivery temperature available
in
warmer
weather.
9.8
It
is
a requirement
that
long pipe runs
to
the taps
or
shower
should be insulated to prevent the rapid cooling of domestic hot
water
after
a
tap
or
shower
has
been
turned
off. Refer
to
BS5546:1990.
Pipe diameter: up
to
12mm. Max.length 20 metres.
Pipe
diameter: up to
22mm
. Max. length 12 metres.
9.9 Hot and cold taps
and
mixing valves used with this appli·
ance must be suitable
for
operating at a pressure of
up
to 10
bar
(150
lb/in
').
9.10
No
anti·syphonage arrangements are necessary except
for
someloose head showers.
See
also Section 9.12 following.
9.11 Thermostatically controlled or pressure equalising shower
valves
will
guard against the
flow
of water
at
too high a temper·
ature.
9.
12
The
head of a loose head shower must not
fall
doser
than
25mm
(1
in)
above the top edge ofthe bath to prevent its immer·
sion
in
bath water. Alternatively the shower must be fitted with
an anti·syphonage device at the point of the
flexible
hose con·
nections.
9.
13
The
supply of hot and cold mains water direct to a bidet is
permitted, (subject to local Water Company requirements), pro-
vided that the bidet is of the over-rim flushing type.
The
outlet(s)
9
should be shroucded and unable to have any temporary hand
held spray attached.
No
anti-syphonage arrangements are nee·
essary.
9.14
As the maximum temperature of the Water to Water heat
exchanger is limited by the control drcuit, there
is
normally no
need for
water
treatment
to prevent scale accumulation.
In
exceptional drcumstances a device to prevent scale formation
can be fitted.
Installation of a scale inhibitor assembly should be
in
accor·
dance with the requirements of the local Water Company.
An
isolating valve should be fitted
to
allow servidng. The water
hardness can be determined using a standard test paper or by
reference to the local Water Company.
1
0.
Electrical
See
Figs
.
7,
8, 9,
10
and
11
.
1
0.1
MAINS
SUPPlY
240 V - ,
50
Hz,
150
watts.
External
Fuse
3A
Internal
Fuses
:
T2A
(F1)
and
T315mA
(F2)
.
10.2
It
must
be
possible
to
completely isolate the appliance.
1
0.3 Connection
to
the mains supply should be
via
a double
pole isolator
with
a contact separation
of
3mm
in
all
poles
and
supplying the appliance and controls
only.
10.4
The
appliance must
be
earthed.
10.5 Mains Cable. 0.
75
mm
•
(24
x 0.
20
mm)
to
BS
6500
Thble
16
.
If
a
new
cable
is
needed it must
be
connected
into
the terminals
marked L
(Brown
or
Red
lead), N
(Blue
or
Black
lead) and -t
(Green/'rellow
or
Green)
and
be
held
securely
in
the
cable
clamp.
Fig.
7. Wiring Diagram -Control
panel
and
facia.
For
access
refer
to Section
14
.
NOTE
:
Ensure
the earth lead
is
longer than the
live
and neutral leads.
1
0.6
The
wiring
between the appliance and the
electrical
supply
shall
comply
with
current
lEE
Wiring
Regulations
and
any
local
regulations
which
apply
.
1
0.7
If
a
room
and/
or frost thermostat
is
to be fitted
refer
to
Figs.
10
and
11
.
The
thermostats must be suitable
for
use
on
mains
voltage
.
1
0.8 A
facia
mounted programmer
is
available as an extra.
Instructions
are
supplied
with
the programmer kit.
10.9 Atime
switch
or
programmer can be
fitted
externally
to
the
appliance.
10.10
SAFETY
CHECK.
After
installation or
in
the event of
an
electrical
fault
the electrical system shall
be
checked
for
short
circuits,
fuse
failure
, incorrect polarity of connections, earth
continuity and resistance
to
earth.
(All
components
shown
viewed from front of appliance.)
A
TO
CASVAI.Vl
IIAII
AIIO
OOIIESTlC
HOT
WATER
TltEAIIOST
AT
COLOUR
CODE
br
-
brown
bl
-
blue
gy
-
green
and
yellow
bk-black
or-orange
r-red w-
wh
i
te
y-
yellow
g-
grey
v- vi
olet
pk
- pi
nk
10
...,
Fig.
8. Wiring Diagram -Components outside control
panel
(All
components shown viewed
from
front
of
appliance.)
r-------------
-------
----
-------l
,r------------
-------
-----~
I
/ ' I
/ ' I
r i 1
l I I
I
I
I
I
I
I
I
I
I
I
I
COLOUR
CODE
~
br-brown bl-blue
gy-green
and
yellow
bk-black
or-orange
J-
r-red w-white y-yellow g
-g
rey
v-violet pk-pink
I ·- ·- ·- ·.
-::::
·.=;!
I · - .
--
·
.---
· - ·
-·-
.
L.--
·-
-
~
-
-
-----
·
--
L-.
----
'T ·- ·- ·
I I
I I
I I
I I
I
~
I
I
Pump
Overrun
Thermostat
-----1
_____
_J
I
_ .
...J...-1...
.
-=
·.
-::::.
·.
::=:
.- -
Tj
·
II
I I
I I
I I
I I
/)
I
-----//
I
I
I
I
-------------
----
-------
-i
Diverter
Valve
Micro-Switch
br
gy~--..
bl
11
Main
Valve
Modureg
Regulator
Gas
Valve
Domestic
Hot
I
I
I
I
I
I
I
I
I
I
I
-
...J...
Water
'-...!...
1
Thermostat
1
~
Domestic
Hot
Water
Sensor
-
N
/ N
'
lli
POWER
ON
r=;_[.
DEMAND
I
~
INDICATOR
I
Q3D
INDICATOR
bla
ck
black
L
r---
--------------------
-
------------------.,
' I
X11
i
PIN1
1
X111PI
N1
1
~ONVtRIOARD
I
I I
Xl
i
PIN
" I
~-----C,.._,H
FROST
THERMOSTAT
IIF
FITTED
!
RELAY
RY1
I
~
FUSE
f1
_r:::::::]
XI
/PIN
11
l2A
X4
1
PIN
~
~
-
U -
~4
1
PIN
11
TRANSFORMER
fl®Ot------------,
UIPI
NJI
~
;~~~M
!
Ill
~or.~=---,.._,-----TE-ST~:r---t
ELECTRONICS
:
THERMOSTAT
WATEROIVERTERVAlVE
~II
1 -
XIO
X4
nl
MtCRO
SW1TCH
L----..J
FUSE
F2
- I
PI
N11
i
PIN
11
X4
1
PIN1
1
T315mA
r
CH
gr
ev
T- - T u
ye11ow
CH
grey
brown I I !PIN11
Xl
i
PI
N"
XIO
I
PI
NJl I
O+IW
Of'TlONAll!Nit
' i
OHW
Xl
!
PIN
Jl
h l
~
- w lie
XII
I
PIN
11
Xl
I
PIN
11
white ' I _/
CH
r
OPERATING
SWITCH
'-
-! a
ed
ElECTRONICS
l
OR
PROGRAMMER
! I .•
D+IW
Xl
i
PI
NSl
.
W4TER
OMRTER
V4LVE
I
L--
-
-
·
-
·
-
-->-·--
-
-~~-_j
XS
!
PI
NJl
C£NTR4l
H£4TING
SENSOR
-
red
XS
I
PIN
11
.--a
DOMES11C
HOT
WATI:R
SENSOR
-
brown T
Tl:MI'ERATURE
CONTROt.I'OTI:NTIOMETtR
-
~
L
brown
GAS
PUMP
OVERRUN
THERMOSTAT
Oflnge
I
VALVES.__,.
N
XI
I
PIN
11 I
.......__
L
----------------------
~
~
PI~
I
--
----
-
-----
--
_____
_j
btOWI'l
Fig
. 9. Functional flow diagram.
PUMP
0 -:
' )
Fig.
10. Room thermostat
connections.
Remove
link
.
1 2 3 4 5
Terminal
X4
on
main
driver
board
.
Honeywell
room
thermostat
T60608
(or
similar
.)
Fig.
11
. Frost thermostat
connections.
Terminal
X4
on
main
driver
board.
Honeywell
frost
thermostat
T
41
60A
(or
similar
.)
'
11
. Installation
11
.1
The
appliance
is
supplied suitable
for
fitting
to a sealed
system. If
it
is
to
be
fitted
to
an open vent system
refer
to
Sec
·
tion
11
.2
following
and
Section
8.
The
flue
must
be
installed as
specified
in
BS
5440 Part 1.
Note
READ
THIS
SECTION
FULLY
BEFORE
COMMENCING
INSTALLATION
11
.2
GENERAL
FlmNG.
Check
that the appliance carton contains
:·
Appliance
Installers
Instruction
Pack
Appliance
Mounting
Plate
Users
Information
Pack
Installer
Hardware
Pack
Check
that the position chosen
for
the appliance is in accor·
dance w
it
h the instruct
ions
given
in Sections 4 and 5.
The
distance
from
the bottom
of
the mounti
ng
plate
to
the top
of
the appliance casing
is
1
06
mm
.
Hold
the appliance mounti
ng
plate to the
wall
.
Check
that the
plate
is
horizontal.
See
Fig.
12
.
Sealed System:
Unscrew
and discard the
!lUtomatic
air
vent cap.
See
Fig
13
.
Open
Vent
System:
Remove
and discard the automatic a
ir
vent.
Fit
the preformed
pipe
(optional
extra)
.
Connect
the
feed
and expansion
tank.
See
Fig
14
.
Connect
the
flue
pipe
to the appliance and seal the gap between
the
pipe
and the spigot.
The
flue
must be supported
so
that
its
weight
is
not put upon the appliance.
Connect
and make
good
the
flue
system and terminal as
specified
in
BS
5440:1.
11
.3
FINAL
INSTALLATION
Check
that
all
the water connections and the gas connection
have
been tightened.
If
a facia mounted programmer
is
to be fitted, unscrew the
upper
two
screws
holding
the
facia
panel
in
place and carefully
lower
the
facia
.
See
Fig
.
15
.
Unplug
the
Operating
Switch
from
the terminal
X1
0
on
the main
driver board.
See
Fig
. 7.
Unscrew
the
four
screws
hold
i
ng
the
switch plate and
remove
the complete Operating
Switch
assem·
bly
.
Fit
the programmer and tighten the
four
screws.
Plug
the
Fig.
12. Appliance mounting plate
and
flue position.
-
App
li
ance
cas
i
ng
REAR
FLUE
POSmON
Mark
the position
of
the
fixing
holes
and the position
of
the
flue
hole
centre
line
onto the
wall
.
Drill
the
fixing
holes
60
mm
deep
for
No
.
12
size
plugs and
fix
the appliance mounting plate, and check that
it
is
horizontal
before
tighten
ing
the screws.
The
gas and water pipes
ca
n
be
l
ed
towards the appliance at
this stage.
See
Fig
3.
It
is
recommended that temporary connec·
tions
be
made
to
thoroughly
flush
the central heati
ng
syst
em
.
Al
so
flush
the
prima
ry
cold
water supply
pipe
before
the
appli
·
ance
is
fitted
to
the
wall
.
Prepare
the opening
in
the
wall
or
ceiling
for
the
flue
pipe
.
Hang
the appliance onto the
wall
.
Drill
(at
a slight
rising
angle)
thro
ugh
the
two
appliance
fi
xing
holes
at the bottom
of
the casi
ng
.
Plug
and
fix
the
casing
bottom.
Connect
the gas, water and pressure
relief
valve
connections
to
t
he
appliance.A
15
mm
shut-off
valve
(supplied
with
the
Installer
Pack)
must
be
fitted
to
the
cold
water
supply connection.
See
Fig
3.
Remove
the cab
inet
front
panel.
Refer
to
Section
14
.3
(a)
.
13
265mm
nom
.
SIDE
FLUE
POSmON
programmer
into
terminal
X10
on
the main
driver
board.
Lower
the control
box
as described
in
Section
14
.
3(d).
Connect the mains electrical supply to the appliance and
con
·
nect any
room
and/
or
frost
thermostats.
The
electrical leads
to
the
room
and
frost
thermostats must pass through the appropri·
ate holes
in
the control panel and be
fixed
with
the cable clamps
provided.
See
Fig
.
16
.
Refit
the control
box
and
facia
panel.
Test
the gas supply
pipework
up
to
the appliance
for
soundness
as indicated
in
BS
6891
.
Refer
to
Section 12
for
a
full
description
of
the
filling,
venting
and,
with
a sealed system, the pressurising
of
the system.
If
the appliance
is
not
to
be commissioned immediately, replace
the cabinet
front
panel.
Check
that the gas supply, the electrical
supply and the water connections are
all
turned
off
.
If
the premises are
to
be
left
unoccupied during frosty condi·
tions, then commission the appliance
as
described
in
Section
12
and
leave
it
under the control
of
the
frost
thermostat
or
leave
operating continuously
with
the
room
thermostat set at 6°C.
If
the unoccupation
is
to
be
of
a
long
duration then drain the
appliance and system and commission the appliance upon
re
·
occupation.
Fig.
13.
Automatic
air
vent
.
Unscrew
and
discard
the
cap
Automatic
air
vent
(
Sealed
systems
only
I
llllllllll
Jnlllll
Feed
and
vent
connection
_:::_l
~~r
I
Open
vent
water
system
only
) -
Gas
to
Water
heat
exchange
r
Fig. 14.
Pipe
connection
for
open vent
systems.
To
Gas
to
Water
heat
exchanger
14
Fig
. 15.
Appliance
casing
and
control
equipment
fixings.
r
f \
I I
Inner
casing
co
ver
Cabilet
side
panel
fixing
screws
(2)
~\
.
) 0
~
'I!:
Control
box
fixing
screws
(2)
Upper
fac
1a
panel
fixi
ng
screws
(2)
~
I
--·
__
_
::301
-me
-·
Low
er
facia
pane
l
fixing
screws
(2)
Fi
g.
16. Electrical cable exits from control box.
12. Commissioning
TO
GAS
VALVE
IWIAIIO
OOIIEST1C
HOTWATtR
Th"Ef!IIOSTAT
12.1 The appliance is despatched with the controls set to pro-
vide a
max
i
mum
ou
t
put
for
domestic
hot
water
of
24
kW
(82,
000
B
tu/h)
and satisfy a central heating load of 16.1
kW
(54,900
Btu
/ h
).
Domestic Hot Water System. Check
that
the mains water sup·
ply has been
fully
flushed out
at
installation.
Central Heating System. Check
that
the central heating system
has been
fully
flushed
out
at
installation.
Gas Service .
The
complete system,
in
clud,ing the meter, must be
inspected and tested
for
soundness and purged
as
indicated
in
BS
6891 .
12.2
APPLIANCE AND CENTRAL H
EATIN
G SYSTEM
PREPARATION
Remo
ve
the cabinet front pane
l.
Check
that
the electrical supply and the gas service to the appli·
ance are off. See F
ig
3. ·
Check
that
all
the water connections throughout the system are
tight.
Open the system valves
at
the appliance. See
Fig
3. Open
all
the
radiator valves,
fill
the system and vent each radiator
in
tum.
On
sealed systems the automatic air vent,
(fixed
to the
flow
man-
ifold) will vent the appliance. Check
that
the
air vent
cap
has
been removed.See
Figs
13.
Check
that
the pressure relief valve operates by turning the knob
anti-clockwise until
it
releases. Water should be expelled from
the discharge pipe. See
Fig
. 17. Lower the control box to gain
access.
Refer
to Section 14.3(
d)
.
S
EALE
DS
YSTEMS
O
NLY
Set
the
Expansi
on
V
es
se
l Pre
ssure
The charge pressure of the expansion vessel
as
despatched
is
0.5
bar, which
is
equivalent to a static head of 5 metres
(17
ft)
. The
charge eressure
must
not
be less
than
the static head
at
the
point of connection. See
Fig
. 4. A Schraider type tyre valve
is
fitted to the expansion vessel to allow the charge pressure to be
increased if necessary.
Set
the
S
ystem
Pres
sure
Fill
the
system
until
the
pressure
gauge
shows
2.5
bar
(37
lblins
')and check
for
water soundness. Release water from the
system using the relief valve test knob until the System Design
15
MA
ll
DIIVER
BOARD
TO
WA
TIII
OMIDIIl
VAI.Vf
IIICJIO.IWITCM
Pressure
is
obtained,
up
to a maximum of1.5 bar.
System Design Pressure
in
bar
= Static Head of the System
in
bar+
0.3
Note: 1 bar
is
equivalent to 10.2 metres
(33
.5 ft) of water.
Set the movable pointer on the pressure gauge to coincide with
the
indicating
pointer
giving a
permanent
record of
the
set
system pressure.
If the pressure indicated on the pressure gauge
is
greater
than
2.5
bar
when operating
at
the maximum central heating tern·
perature, an extra expansion vessel must be fitted to the system
as
close as possible to
the
appliance central heating return con·
nection.
The
appliance
(as
despatched)
can
accommo~ate
a
system
volume of about 104litres.
Refer
to
B~
7074 Part 1.
If
the system
volume is
in
excess of
that
accommodated
by the expansion
vessei fitted to the appliance then an extra vessel must be fitted
as
close as possible to the central heating return connection of
~he
appliance.
Any
extra vessel fitted must be pressurised to the
same
figure
as
the integral vessel. If the expansion vessel fails then the speci·
fied
replacement
must
be fitted.
12.3 PROGRAMMER
Any
programmer fitted on the appliance should be set up
at
this
stage following the instructions sent with the programmer. The
Fig. 17. Pressure relief valve.
Pressure
relief
valve
di
scharge
pipe
plug-
in
programmer
will
retain the setting
for
up
to four weeks
following an interruption
in
the electricity supply.
12.4
APPLIANCE OPERATION
Check
that
the gas supply to the appliance
is
off. Switch
the
elec·
tricity supply on at the mains. Put the Operating Switch to Heat·
ing and Water. Leave the system to operate
in
a cold
state
for
about 20 minutes, venting as necessary to remove air from the
system.
Set the Operating Switch to
OFF.
Switch off the electrical supply
to the appliance.
1\.lrn
on the gas supply. Check
for
gas sound·
ness around the gas valve.
Light the pilot by pressing in the grey button on the gas valve
and operating the red spark igniter button. When the pilot has
lit
continue to hold the grey button
in
for
a further 20 seconds
and then release
it
slowly.
If the pilot does not stay alight, twist the gas valve button anti·
clockwise.
Wa
it
for
3 minutes and repeat the operation until the
pilot
has
lit. Continue to hold
the
gas
valve
button
for
30
seconds then release
it
slowly.
Tes
t
for
gas soundness at the joint between the pilot pipe and
the burner with leak detection
flu
id
.
Observe the pilot flame. It should be about 18·20 mm long and
envelope the thermocoup
le
tip.
If
not. refer to Section 14.4. See
Fig
. 23.
Loosen
the
burner
pressure
test
point screw
and
connect
a
pressu
re
gauge. See
Fig
. 18.
Domestic Hot Water.
Set the Operating Switch
(or
Programmer) to
WATER
and
fully
open a hot water tap.
The
boiler should light
at
a burner pressure of 2·3 mb
(0
.8·1.2
in
.
wg.) rising immediately to 14 and 14.5
mbar
(5
.6
and
5.8
in
.
wg.).
If
the burner pressure
is
low,
check
that
the supply pres·
sure
at
the
gas valve inlet with the appliance operating
is
at
least 19 mbar
(7
.6
in.
wg)
.
Note: The burner pressure
is
factory set and
if
(after checking
that
the supply pressure
is
sufficient) the correct pressure
is
not
obtained
then
Wo
rcester Heat Systems Service
Department
should be contacted.
With the main burner alight test the integral gas supplies and
joints
for
soundness using leak detection
fluid
.
Gradually close the hot tap and check
that
the burner pressure
drops.
Fully
open the tap and check
that
the burner pressure
rises. After 10
minutes
operation
check for spillage
at
the
diverter outlet as described in
BS
5440:
1.
Fully
close the tap and
check
that
the burner goes
off
.
The
pump
will
continue running
until the appliance has cooled to a preset temperature.
Set the Operating Switch
(or
Programmer) to
OFF
.
Central Heating
Check that
all
the radiator valves are open. Set the room thermo·
stat and the Central Heating Temperature Control to maximum.
On
sealed systems check
that
the system
is
pressurised and set
to the required pressure as indicated on the gauge.
Set
the
Operat
ing Switch (
or
Programmer)
to
HEATING
&
WATER
.
The burner
will
light.
The appliance
will
modulate its
output
from 9.2
kW
(31
,400
Btu
/ h) to
the
set output of 16.1
kW
(5
4,900
Btu
/
h)
over a peri·
od of about two minutes.
Check the system to ensure
that
all
the radiators are heating up
evenly.
Shut down
all
but
one of the radiators and observe the burner
pressure
fall
. Open
all
of the radiator valves
and
check
that
the
burner pressure rises.
If
a greater heat
output
up
to a maximum of 24
kW
(82,000
Btu/h)
is
required, then the burner pressure must be adjusted at
the potentiometer located at the rear of the control box. Adjust
the potentiometer to give a burner pressure of 14.S mbar.
This
16
figure can only be achieved
if
the burner pressures are correctly
set
in
the domestic hot water mode.
Balance the system so
that
the required temperature difference
across the central heating
flow
and return pipes
is
obtained. See
lable
3.
Adjust the central heating by-pass valve until the same tempera-
ture difference
is
obtained. See
Fig
19.
This
should be carried
out
with only a single radiator operating.
If
thermostatic radiator
valves are fitted then one radiator should be left uncontrolled.
The bypass valve should never be
fully
closed.
Set
the
room thermostat to minimum and check
that
the burner
goes out. Reset the room thermostat to maximum and the burn·
er
will
relight and
follow
the normal operating procedure.
Set the Operating Switch
(or
Programmer) to
OFF
.
1\.lrn
off the gas service cock
and
the electrical supply to
the
appliance. After about 60 seconds the flame failure device can
be heard to operate. Check
for
its correct operation by turning
the gas back on
at
the gas cock and attempting to light the pilot
w
it
hout depressing the gas valve button.
If
the pilot can be lit
in
this way, turn off the gas supply
and
contact Worcester Heat
Systems.
Disconnect
the
pressure gauge
and
re-tighten
the
test
point
screw.
Test
for
gas soundness at the screw.
Drain the system while the appliance
is
still hot.
Refill
, vent and, with a sealed system.
re
-pressurise as described
in
Section 12.2.
Domestic Hot Water
and
Central Heating
Light the pilot as described
in
the preceding notes.
Set
the
Operat
ing Switch (or
Programmer)
to
HEATING
&
WATER.
If
a programmer
is
fitted, set the domestic hot water to
Continuous or 24Hrs
and
the central heating to
ON
. The burner
will
light and heat
will
pass into the system.
1\.lrn
on a hot water
tap and check that
fully
heated hot water
is
discharged from the
tap
.
Close
the tap and the burner
will
go
off
.
The
appliance
will
then
return to the central heating mode and automatically
ba
lance
with the system requ
ir
ements.
Se
t the Operating Switch (or Programmer) to
OFF
and
the
burner
will
go out.
12
. 5 COMPLETION OF COMMISSIONING
Disconnect the pressure gauge and tighten the test point.screw.
Restart the appliance and check
for
gas soundness around
the
test point screw.
Refit
the cabinet front panel.
If
the appliance
is
being passed over to
the
user immediately,
refer to Section 13 -Instructions to the User
and
set
the controls
to the user's requirements.
If
the appliance
is
to be left inoperative, check
that
the Operating
Switch
is
set to
OFF
.
1\.lrn
off the gas service cock and switch
off
the electricity supply.
If
there
is
any possibility of the appliance
and
system being left
inoperative during frosty conditions, drain
the
appliance
and
system.
For
short inoperative periods leave
the
boiler under the
control of a frost thermostat
or
operating continuously under
the control of a room thermostat set
at
6°C.
13. Instructions
To
The User
13
.1
Tell
the user how to operate the appliance and hand over
the Users Instructions leaflet.
13
.2
Tell
the user what to do
if
the the heating system
is
not to
be used
in
frosty weather.
13.3
Tell
the user the sealed system set pressure
if
applicable.
13.4
Tell
the user of the importance of regular servicing. Worces·
ter Heat Systems
Ltd
offer a comprehensive maintenance con·
tract.
Fig.
18.
Gas
valve.
Note
E
lec
trocal
co
nnect
rons-
Marn
valve
-----.._
!
brown
·
blue
•
green/yellow)
axrmum
pressure
ad1ur:er
-----....
Mrnrm
um
pressure
adjuster
Turn
the
nuts
ctockwrse
to
rnc
rease
and
a
rlli
-
clockwrse
to
decrease
the
pressure
~
odureg
c
ap
Mod
u
reg
•~gul
ator
he
ad
Fig.
19. Central heating by-pass adjuster.
13.5
Se
t the system controls to the user's requirements.
13.6
If
an external programmer has been fitted
wh
ich has a pro·
grammable domes
ti
c
ho
t water facility then
it
is
suggested that
t
his
be set to Continuous or the equivalent.
14
. Inspection
and
Servicing
14
.1
To
ensure
continued
efficient
operation
of
the
appli·
ance it
must
be
checked
and
serviced
as
necessary
at
regular
intervals. The frequency of servicing will
depend
upon
the
particular installation conditions
and
usage,
but
once
per
year should generally
be
adequate
. The extent of
the
service
required by
the
appliance is
determined
by
the
operating
condition of
the
appliance
when
tested
by fully qualified
engineers.
Any service work
must
be
carried
out
by
competent
engi·
neers
such
as
British
Gas
or Corgi registered personnel.
14
. 2 PRE-
SERVICE
INSPECTION
Check
that the
flue
terminal
is
clear.
Check
that
the
ventilation and combustion air openings are
clear.
See
Section 6 -
Air
Supply.
17
::r-'=-___;;~-:::-----
Pi
lo
t
pi
pe
connect
i
on
ECO
lead
comection
Check the system and remake any joints or fittings which show
signs
of
leakage.
Refill,
vent and, with a sealed system, re·pressurise
as
described
in
Section 12. 2.
Operate the appliance and the system taking note
of
any faults.
Warning
Disconnect the electrical supply at the mains and turn
off
the
gas supply
at
the
gas service cock on
the
appliance before
servicing.
See
Fig
. 3.
After completing the service always test
for
gas soundness
as
indicated
in
BS
6891 .
14.
3 DISMANTLE THE APPUANCE
To
carry out a
full
and comprehensive service of the appliance
remove the following parts to gain access to the components
which need to be checked or serviced.
(a)
Cabinet Panels. Remove the front panel by lifting off
the
supports.
Lower
the control box
as
described
in
Section 14.
3(d)
.
Pull
off the lead from the spark generator. Unscrew the screw
fixing
each of the cabinet side panels and remove the panels.
See
Fig
. 15.
(b)
Inner
Casing Cover. Remove
the
cabinet front panel.
Un·
screw
the
two screws securing
the
cover to
the
casing
and
remove. See
Fig
15.
(c)
Facia Panel. Check
that
the electricity supply to the appli·
ance
is
turned
off
. Remove the cabinet front panel. Unscrew the
two screws and lower the facia assembly. See
Fig
. 15.
(d)
Control
Box
. Remove the cabinet front panel. Unscrew the
two screws
as
shown
in
Fig
. 15. Support the assembly and allow
it to hinge down into the servicing position.
(e)
Diverter.
It
is
not necessary, nor possible to remove
the
diverter assembly when servicing the appliance.
(f)
Combustion Chamber
Cover.
Remove the the inner casing
cover. Unscrew
the
four screws securing
the
cover
and
pull
downwards to remove the cover.
See
Fig
20.
(g)
Main Burner Assembly. Remove the combustion chamber
cover. Unscrew the pilot
fixing
screws. Unscrew the two screws
and
remove
the
burner
assembly by lifting
the
front of
the
burner and pulling forward. See
Fig
. 22.
(h)
Flue Clean·
OUt
Cover. Unscrew the four screws and remove
the cover.
(i)
Thermostat Cover. Unscrew the two screws and move the
cover to oneside (electrical leads still attached). See
Fig
. 20.
14.
4
SERVICE
OF COMPONENTS
Clean
the
Main Burner. Brush the blade tops and mixing tube
with a soft non-metallic brush and check
that
all
the flame ports
are clear. Inspect the injector
and
clean with a soft
brush
.
Replace the injector
if
it appears damaged.
Do
not use a wire
Fig.
20.
Appliance
components
and
fixings
(upper
assembly).
Combust
i
on
chamber
cover
fixing
screws
(4)
Combust
i
on
chamber
cover
Diverter
baffle
Access
cover
Fig.
21
.
Pilot
burner
assembly.
2mm
Thermocouple
0
18
brush or anything likely to cause damage.
The burner
is
fitted with a lint filter which can be removed by
unscrewing the nut
at
the end
of
the burner and removing the
endcap. Brush or wash
in
soapy water and carefully
refit.
Check
that
the endcap
is
fitted correctly before tightening the nut.
Clean
the
Pilot
Burner
Assembly
. Brush with a soft brush.
Remove the pilot injector and clean by rinsing it
in
warm water.
Replace the thermocouple
if
it appears damaged. Replace the
spark
electrode
if
it appears
damaged
.
Fit
the
electrode lead
before replacing the electrode.
Clean
the
Gas
to
Water Heat Exchanger.
Cover
the main burner
manifold with a cloth. Clean
the
heat
exchanger using a soft
brush.
Remove
the deposits
from
the bottom of the combustion
Fig.
22. Main
burner
fixings.
Ma
in
burner
fix
i
ng
screws
(2)
chamber.
Do
not distort any of the blades.
Combustion
Chamber
Insulation. Examine and replace any
pads
that
are damaged.
See
Section 15.7.
Controls.
Remove
any dust or deposits using a soft non·metallic
brush. lake care not to mishandle any component connections.
Reassemble the appliance
in
the reverse order.
Check
that
ALL
components are
in
place
and
correctly fixed.
Leave
the cabinet front panel to be fitted after checking the oper·
ation of the appliance.
14. 5
TEST
THE
APPUANCE
On
completion
of
the serv
ice
and reassembly of the appliance,
check
for
gas soundness and the correct operation of the appli·
ance as described
in
Section 12 -Commissioning.
Refit
the cabinet
fron
t panel and reset the controls to the users
requ
ir
ements.
15. Replacement of Parts
15
.1
WARNING.
Switch off the electricity and gas supplies before replacing any
components.
After
the replacement
of
any components, check
for
gas
soundness
where relevant
and
carry
out
functional
checks as described in Section 12 -Commissioning
15.2
COMPONENT
ACCESS
To
replace components it
is
necessary to remove one or more
sections of the cabinet and cover plates within the appliance as
described
in
Section 14.3.
The
facia panel and control box may
also need to be lowered as described
in
Section 14.3
15.3 DRAINING
THE
APPLIANCE
Check that the electricity supply to the appliance
is
turned
off
.
19
Before
removing any component holding water it
is
important
that
as much water as possible
is
removed from the appliance.
(a)
Appliance.
1\un
off
the
central heating flow
and
return
valves at the appliance. See
Fig
3.
Fit
a tube to the drain tap on
the Water to Water heat exchanger and open the tap about one
turn. See
Fig
26.
Close
the drain tap when the
flow
has stopped.
Extra water can be removed by operating the relief valve knob.
Some
water
will
remain
in
the
expansion
vessel,
pump,
diverter valve
and
Gas
to
Water
heat
exchanger
and
extra
care
must
be
taken
when
removing
these
components
.
(b)
Domestic Hot Water Circuit. lllrn off the mains cold supply
valve at the appliance using a flat-bladed screwdriver and open
the lowest hot water tap. See
Fig
3. A
quantity
of
water
will
Fig.
23. Pilot
burner
settings.
remain in
the
Water to Water
heat
exchanger
and
the
diverter
valve
and
extra care
must
be
taken
when
removing
these
components.
15
.4
COMPONENT
REPLACEMENT
1. Automatic Air Vent. (Sealed system installation only.)See
Fig
13.
Remove the cabinet front panel
and
left-
hand
side panel
as
described in Section 14.
3(a)
.
Dra
in the appliance as described
in
Section 15
.3(a)
.
Unscrew the assembly.Take care not to distort the pipework.
Fit
the replacement assembly.
Open
the
valves
and
fill
and
re·
pressurise
the
system
as
described
in
Section 12.2.
2. Overheat Thermostat
See
Fig
20.
Check
that the electricity supply to the appliance is turned
off
.
Remove the cabinet front panel, the right-hand side panel and
the thermostat cover as described
in
Section 14.
3(a)
and
(i)
.
Unscrew the two screws to release the thermostat head. Release
the thermostat connections at the gas valve. See F
ig
.8.
Fit
the replacement thermostat
in
reverse order
ensur
in
g
that
some heat sink compound
is
on the mounting plate.
3. Gas
to
Water Heat Exchanger. See
Figs
13, 24 and 25.
Check that the electricity supply to the appliance
is
turned
off
.
Remove the combustion chamber cover as described
in
Section
14.3tn.
Drain the appliance as described
in
Section 15.
3(a)
.
Remove
the screw securing the control box
at
the left-hand side
and
lift
off
the left-hand side panel.
Remove the pump overrun thermostat, overheat
thermostat
,
and main burner as described
in
Sections 14.
3(g),
15.
.4
.6 and
15.4.
2.
Remove
the side panels
of
the combustion chamber
by
carefully
removing
the insulation
and
removing
the
four
screws.
See
Fig
.
25
.
Unscrew
t
he
flow
pi
pe
at the
hea
t exchanger and at the bottom
left
of
the inner casing
and
remove
the
pipe
.
Unscrew
the return connection at the bottom
left
of
the inner
casing
and manoeuvre the heat exchanger
from
the casing.
Transfer
the return pi
pe
to
the
new
heat exchanger.
Fit
the replacement heat exchanger
in
the
reverse
order ensuring
all
the
fibre
washers
are
in
place
and a
layer
of
heat
sink
com
·
pound
is
on
each thermostat pad.
Align
the return pipe and
tighten the connection.
Refit
the combustion chamber side
plates and insulation pads.
Re
-assemble the appliance
in
t
he
reverse
order.
Open
the
valves
and
fill
and
re
·pressurise the system as
described
in
Section
12
.2.
4. Pump Overrun Thermostat. See
Figs
8 and
20
.
Check
that the
electric
i
ty
supply
to
t
he
appliance
is
turned
off
.
Remove the cabinet front panel, right·hand side panel and
thermostat
cover
as described
in
Section
14
.
3(a)
and
(i)
.
Unscrew
and loosen the access cover
on
the
baffle.
See
Fig
.
20
.
Use
a
long
screwdriver,
from
above,to loosen the rear
M4
screw
securi
ng
the thermostat to its mounting place
on
the
Gas
to
Water
heat exchanger.
Remove
the
front
screw
and
thermostat.
Carefully
remove the three wires
from
their connections and
make note
of
their positions.
Fit
the leads to the
new
thermostat.
Fit
the replacement thermostat ensuri
ng
a layer
of
heat
sink
compound
is
between t
he
faces
.
5. Combustion Chamber Insulation.
See
Fig
25
.
Check
that the
elec
t
ric
i
ty
supply
to
t
he
appliance
is
turned
off
.
Remove
the combustion chamber
cover
as described
in
Sect
i
on
14
.3(
f).
Remove
the
fibr
e insulation pads
from
the combusti
on
chamber si
de
, rear.and
fron
t.
F
it
the replacement
pad
s in the
reverse
order
tak
i
ng
care
not
to
damage them.
6.
Main
Burner.
See
Fig
.
22
.
Check
that the electricity supply
to
the appliance
is
turned
off
.
Remove
the burner assembly
as
descri
bed
in
Sect
i
on
14
.
3(g)
.
Fit the replacement burner
in
t
he
reverse
order taking care
not
to bend the
pilo
t bracket
on
the
main
burner.
7. Thermocouple.
See
Figs.
21
,
26
.
Remove
the inner casi
ng
cover
as descri
bed
in 14.
3(b)
.
Unscrew
the
two
screws
and
remove
t
he
pilot
burner
from
the
main
burner.
Unscrew
the ther
mocouple
at t
he
pi
lot
burner and t
he
gas
valve
and
remove
.
Fit
t
he
replacement thermocouple
in
t
he
reverse
order and
ref
it
the
pilot
burner.
8. Pilot Burner.
See
Fi
gs
.
21
and
23
.
Remove
the inner casing
cover
as described
in
14
.
3(b)
.
Unscrew
the
two
screws
and
remove
the
pilot
burner
from
the
ma
in
burner.
Undo
the
pilot
pipe
.
Unscrew
and
remove
the ther·
mocouple
.
Remove
the spark electrode
cable
and
pull
out the electrode.
Fit
the replacement burner
in
the
reverse
order ensuring that the
pilot
injector
is
in
place
. F
it
the electrode
lead
before
replacing
the electrode.
Check
the
pilot
burner settings as shown
in
Fig
.
23
.
9.
Main
Burner
Injector.
See
Fig
.
22
Remove
f
he
main
burner as described
in
Section
15
.
4.6
.
Unscrew
the brass
injector
at the
back
of
the combustion cham·
ber
.
Fi
t the replacement
injector
in
the
reverse
order.
1
0.
Spark Electrode.
See
Figs
.
21
and
23
Check
that the electricity supply
to
the appliance
is
turned
off
.
20
Remove
the pilot burner assembly as described
in
Sections
14
.3(b)and
15
.7.
Pull
the spark electrode out
of
the
clip
.
Fit
the replacement electrode in the
reverse
order,
check
i
ng
that
the spark gap
is
4 to 5
mm.
Fit
the electrode
lead
before
replac
·
ing
the electrode.
11. Pilot Burner Injector. See
Fig
21
Remove
the inner casing cover and pilot burner assembly as
described
in
Sections
14
.
3(b)
and
15.4
.8.
Remove
the injector
(a
push
fit
inside
the pilot
assembly)
.
Fit
the replacement injector in the
reverse
order.
12
. Spark Electrode
Lead.
See
Fig
.
21
Check
that the electricity supply
to
the appliance
is
turned
off
.
Remove
the inner casing
cover
as described
in
Section
14
.
3(b)
.
Carefully
pull
the lead
from
the spark electrode and
from
the
spark
generator.
Fit
the replacement lead in the
reverse
order.
Loosen
the pilot
assembly
to
refit
the
lead
to
the electrode.
13. Piezo Spark Generator.
See
Fig.
26
Remove
the
cab
i
net
front
panel
as
desc
ri
bed
in
Section
14
.
3(a
).
Pull
off
the electrode
lead
.
Unscrew
the
two
screws
and
remove
the generator.
Fit
the replacement generator in the
reverse
order.
14
.
Gas
Valve.
See
Fig
.
18
.
Check
that the electricity and
gas
supplies
to
the appliance are
turned
off
.
Hang the control box assembly in the servici
ng
positi
on
as
described
in
Section
14
.3(
d)
.
Disconnect
the pilot pipe.
Unscrew
and
remove
the
black
plastic
plugs.
Carefully
pull
off
the
two
yellow
wires
from
their term
i·
nals. Disconnect the thermocouple and the overheat thermostat
lead
at the
valve
.
Remove
the eight
screws
securing the
valve
to
the pipework and
remove
the
valve
from
the appliance.
Fit
the replacement gas
valve
in
the
reverse
order ensuring the
sealing washers are correctly fitted.
ll.lrn
on
the gas supply and check
for
soundness.
To
replace the Modureg head only.
Pull
off the electrical connections. Unscrew the two screws
securing the
Modureg
head
to
the
main
body and
remove
.
Fit
the
new
Modureg
head
(Honeywell3061)
in the
reverse
order
ensuring that the gasket
is
in
the correct position.
To
setthe burner pressure.
See
Fig.
18.
The
minimum and maximum burner pressures must
be
set after
a
new
gas control has been
fitted
.
Follow
the procedure described
in
Section
12
.4 - Appliance
Operation.
Fig.
24.
Gas
to Water
heat
exchanger
connections.
Bo
i
ler
ret
u
rn
i
Bo
i
le
r
fl
ow
co
n
nector
screws

Other manuals for Worcester 240 Combi OF

1

Other Bosch Boiler manuals

Bosch Worcester 24CDi User manual

Bosch

Bosch Worcester 24CDi User manual

Bosch Greenstar ZWBR 7-25 A 23 User guide

Bosch

Bosch Greenstar ZWBR 7-25 A 23 User guide

Bosch Gaz 6000 W User manual

Bosch

Bosch Gaz 6000 W User manual

Bosch Worcester 2000 GC2000iW C Series User manual

Bosch

Bosch Worcester 2000 GC2000iW C Series User manual

Bosch Uni 3000 F User manual

Bosch

Bosch Uni 3000 F User manual

Bosch Worcester Greenstar Si Series User manual

Bosch

Bosch Worcester Greenstar Si Series User manual

Bosch CONDENS 5000W User manual

Bosch

Bosch CONDENS 5000W User manual

Bosch WORCESTER Greenstar Heatslave II 12/18 User guide

Bosch

Bosch WORCESTER Greenstar Heatslave II 12/18 User guide

Bosch Jungers ELAFLUX ED 18-1 HE User manual

Bosch

Bosch Jungers ELAFLUX ED 18-1 HE User manual

Bosch WST50 EL User manual

Bosch

Bosch WST50 EL User manual

Bosch Buderus SB625WS User manual

Bosch

Bosch Buderus SB625WS User manual

Bosch WORCESTER DANESMOOR UTILITY 12/14 User guide

Bosch

Bosch WORCESTER DANESMOOR UTILITY 12/14 User guide

Bosch ZWB 37-2 A User manual

Bosch

Bosch ZWB 37-2 A User manual

Bosch W 500-5 Series Instruction Manual

Bosch

Bosch W 500-5 Series Instruction Manual

Bosch 47 311 67 User manual

Bosch

Bosch 47 311 67 User manual

Bosch Worcester Greenstar Danesmoor 18/25 User guide

Bosch

Bosch Worcester Greenstar Danesmoor 18/25 User guide

Bosch Greenstar FS Series Instruction Manual

Bosch

Bosch Greenstar FS Series Instruction Manual

Bosch Danesmoor 12-14 User manual

Bosch

Bosch Danesmoor 12-14 User manual

Bosch Worcester Greenstar 27i System Compact User manual

Bosch

Bosch Worcester Greenstar 27i System Compact User manual

Bosch Condens 7000 F Instruction Manual

Bosch

Bosch Condens 7000 F Instruction Manual

Bosch Worcester 15SBi User guide

Bosch

Bosch Worcester 15SBi User guide

Bosch Condens 7000 F Instruction Manual

Bosch

Bosch Condens 7000 F Instruction Manual

Bosch WORCESTER GREENSTAR Ri ErP Series User guide

Bosch

Bosch WORCESTER GREENSTAR Ri ErP Series User guide

Bosch Worcester Greenstar Ri ErP + Series User manual

Bosch

Bosch Worcester Greenstar Ri ErP + Series User manual

Popular Boiler manuals by other brands

Vaillant ecoTEC VC 406/5 installation instructions

Vaillant

Vaillant ecoTEC VC 406/5 installation instructions

Viessmann Vitodens 222-F Installation and service instructions for contractors

Viessmann

Viessmann Vitodens 222-F Installation and service instructions for contractors

LPGTECH KRS TECH-DUO Operation and maintenance manual

LPGTECH

LPGTECH KRS TECH-DUO Operation and maintenance manual

YATO YG-04311 Original instructions

YATO

YATO YG-04311 Original instructions

Vaillant ecoMAX SERIES Instructions for installation and servicing

Vaillant

Vaillant ecoMAX SERIES Instructions for installation and servicing

Rinnai Q175S Specifications

Rinnai

Rinnai Q175S Specifications

Sigmar marine TERMOINOX B0 20 UT user manual

Sigmar marine

Sigmar marine TERMOINOX B0 20 UT user manual

REMEHA GAS 460 S Technical instructions

REMEHA

REMEHA GAS 460 S Technical instructions

elco TRIGON L operating manual

elco

elco TRIGON L operating manual

Vaillant ecoTEC plus SERIES Instructions for installation and servicing

Vaillant

Vaillant ecoTEC plus SERIES Instructions for installation and servicing

Ferroli BLUEHELIX B S 45 Instructions for use

Ferroli

Ferroli BLUEHELIX B S 45 Instructions for use

Viessmann VITODENS 050-W operating instructions

Viessmann

Viessmann VITODENS 050-W operating instructions

Hamworthy 65he Installation, comissioning and servicing instructions

Hamworthy

Hamworthy 65he Installation, comissioning and servicing instructions

Lamborghini Caloreclima BSF HP 1C Use, installation and maintenance instructions

Lamborghini Caloreclima

Lamborghini Caloreclima BSF HP 1C Use, installation and maintenance instructions

ZMM Haskovo PELLETHERM V.4 LT SERIES manual

ZMM Haskovo

ZMM Haskovo PELLETHERM V.4 LT SERIES manual

Froling P4 Pellet 8-60 installation manual

Froling

Froling P4 Pellet 8-60 installation manual

Ideal Boilers Imax xtra F320 user guide

Ideal Boilers

Ideal Boilers Imax xtra F320 user guide

AER Benchmark BMK 1500 user manual

AER

AER Benchmark BMK 1500 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.