
17
Model RT Energy Recovery Unit
Electrical Information
Warning: DO NOT penetrate the roof of the unit for
any reason since there are hazardous voltage circuits
located between the inner and outer roof panels.
The unit must be electrically grounded in accordance
with the current National Electrical Code, ANSI/NFPA
70. In Canada, use current CSA Standard C22.1,
Canadian Electrical Code, Part 1. In addition, the
installer should be aware of any local ordinances or
electrical company requirements that might apply.
System power wiring must be properly fused and
conform to the local and national electrical codes.
System power wiring is to the unit main disconnect
(door interlocking disconnect switch standard on most
units) or distribution block and must be compatible
with the ratings on the nameplate: supply power
voltage, phase, and amperage (Minimum Circuit Amps
- MCA, Maximum Overcurrent Protection - MOP).
All wiring beyond this point has been done by the
manufacturer and cannot be modified without affecting
the unit’s agency / safety certification.
If field installing an additional disconnect switch, it
is recommended that there is at least four feet of
service room between the switch and system access
panels. When providing or replacing fuses in a fusible
disconnect, use dual element time delay fuses and size
according to the rating plate.
Field Power Connection: The RT is designed for
simple, single-point connection (in the Control Module)
for high voltage supply. In addition to high voltage
power supply, it will be necessary to run low voltage
controller circuitry to the terminal strip in the Control
Center. In some cases, a second high voltage circuit
will be required to power a high capacity electric post
heater. Refer to unit-specific wiring diagram for further
details.
Many RT units will not have any internal circuit fuses.
Some large units may have circuit fusing and those
fuses will be present on the high voltage side of the
Control Center. Optional electric post heaters may be
fused and those fuses are located on the post heater
control panel. In all cases, refer to the unit-specific
wiring diagram.
Once high voltage power is connected to the unit it
still will not operate unless a controller is installed
on terminals R and G of the terminal strip. Do not
install any controller circuit or jumper on the R and G
terminals until ready for the Startup Procedure.
The recommended location for entry of electrical
circuits and high voltage supply wiring is through the
floor of the unit, preferably in the area of the Control
Center. Carefully select a location that does not
interfere with other controls or assemblies such as
the motorized dampers. Seal penetration in cabinet
bottom to prevent leakage.
The electric supply to the unit must meet stringent
requirements for the system to operate properly.
Voltage supply and voltage imbalance between phases
should be within the following tolerances. If the power
is not within these voltage tolerances, contact the
power company prior to operating the system.
Voltage Supply: See voltage use range on the rating
plate. Measure and record each supply leg voltage at
all line disconnect switches. Readings must fall within
the allowable range on the rating plate.
Voltage Imbalance: In a 3-phase system, excessive
voltage imbalance between phases will cause motors
to overheat and eventually fail. Maximum allowable
imbalance is 2%. To determine voltage imbalance,
use recorded voltage measurements in this formula.
Key: V1, V2, V3 = line voltages as measured
VA (average) = (V1 + V2 + V3) / 3
VD = Line voltage (V1, V2 or V3) that
deviates farthest from average (VA)
Formula: % Voltage Imbalance = [100 x (VA-VD)] / VA
CAUTION
If any of the original wire as supplied with the
appliance must be replaced, it must be replaced
with wiring material having a temperature ratings of
at least 105° C.
WARNING
• To prevent injury or death due to electrocution or
contact with moving parts, lock disconnect switch
open.
• For units with a gas furnace, if you turn off power
supply, turn off gas.
Most factory supplied electrical components are
prewired. To determine what electrical accessories
require additional field wiring, refer to the unit specific
wiring diagram located on the inside of the unit
control center access door. The low voltage control
circuit is 24 VAC and control wiring should not exceed
0.75 ohms.
Refer to Field Control Wiring Length/Gauge table for
wire length maximums for a given wire gauge.
Control wires should not be run inside the same
conduit as that carrying the supply power. Make sure
that field supplied conduit does not interfere with
access panel operation.
If wire resistance exceeds 0.75 ohms, an industrial-
style, plug-in relay should be added to the unit
control center and wired in place of the remote
switch (typically between terminal blocks R and G
on the terminal strip (refer to Typical Control Center
Components). The relay must be rated for at least
5 amps and have a 24 VAC coil. Failure to comply
with these guidelines may cause motor starters to
“chatter” or not pull in which can cause contactor
failures and/or motor failures.
Field Control Wiring Length/Gauge
Total Wire Length Minimum Wire Gauge
125 ft. 18
200 ft. 16
300 ft. 14
450 ft. 12