Modes Of Operation | 17TW Series Water to Water
6720220047 (2016/02)Revised 02-16
The control will first display temperature differential
setting with the ability for the user to adjust it and then
will display “OFF” and finally water temperature.
Heating Mode
When the unit is operated in the heating mode and the
controlled water temperature is below the set point
minus the differential setting is below the set point
minus the differential setting, terminal Y1 will close and
the unit will operate (first stage compressor in a two
stage unit). When the set point is satisfied the
compressor is turned off.
In a two stage unit after the first activation if the water
temperature drops an additional two degrees below the
set point, the second stage (terminal Y2) will be
activated (if control is configured for both
compressors). Both stages will be on until the set point
is satisfied.
When the units runs after power is applied or the mode
is changed from cooling to heating, if the fluid
temperature is below set point and does not change for
3 minutes, the second stage of heating will be activated.
This only applies for a two stage machine.
There will be 5 minutes delay on a break after the unit
cycles off on temperature, a power interruption or
because of a fault condition.
at any point in time the control will ignore a low pressure
switch condition for 120 seconds before turning off the
compressor.
Cooling Mode
When the unit is operated in the cooling mode and the
leaving water temperature is above temperature set
point plus the differential setting, terminals Y1 will close
(first stage compressor of a two stage unit) and the unit
will operate in the cooling mode. When the set point is
satisfied the compressor is turned off. The reversing
valve is always activated when the unit is in the cooling
mode.
On two stage units, after first stage activation if water
temperature increases two degrees above the set point,
the second stage (terminal Y2) will be activated (if
control is configured for both compressors). Both stages
will remain on until the set point is satisfied.
when the unit runs after power is applied or the mode is
changed from heating to cooling, if fluid temperature is
above cooling point and does not change for 3 minutes,
the second stage of cooling will be activated. this only
applies for a two stage machine.
There will be 5 minute delay on break after the unit
cycles off on temperature, a power interruption or
because of a fault condition.
Auto Changeover Mode
The controller’s auto change over mode control feature
will switch from the heating mode to cooling mode and
vice versa based on the setting of the change over
sensor. There will be a dead-band where the control will
not call for either heat or cool. The dead -band setting is
adjustable in the configuration mode. When the auto
changeover mode is selected the changeover set point
will be displayed for 5 seconds, however this point is
only adjustable when the controller is in the
configuration mode. Once the controller has switched to
either heating or cooling mode, pressing the up or down
buttons will display the set point for that particular
mode.
When the reading from the changeover sensor is above
the change over set point plus the dead-band setting,
the unit will operate in the cooling mode and will
maintain the cooling set point temperature. While in the
cooling mode the user can adjust the cooling set point.
Likewise when the change over sensor is below the
changeover set point minus the dead-band setting, the
unit will switch to the heating mode and will maintain
the heating set point temperature. While in the heating
mode the user can adjust the heating set point.
Once the reading from the sensor enters the
dead-band zone it will terminate the call for cooling or
heating even if the set points are not satisfied.
Mode switching will be HEAT – COOL – OFF in a closed
loop. If the changeover sensor is shorted when the
control is in Auto changeover mode then the control will
switch to the OFF mode. If no sensor is connected the
controller will indicate a sensor error code.
Unit Protection
The unit controller will protect the unit against a
high or low pressure condition and brownout. To
avoid nuisance lockouts an intelligent reset
function is built into the controller to allow the unit
to restart one time in the event of a fault condition.
If a fault condition is initiated on any circuit the
corresponding compressor will be turned off and
the 5 minute delay on break time period timer is
initiated. After the delay expires the unit will attempt to
restart. If the fault condition still exists or reoccurs
within the next 60 minutes, the unit will go into a hard
lockout and requires a manual lockout reset. During this
period the fault LED will indicate the cause of the fault.
A 120 second time delay is built into the low pressure
switch to avoid nuisance trips with low fluid
temperatures.
While in a soft lockout condition the display will
show the specific fault (for example LP1) and the
“service” LED will turn on according to the malfunction
mode. If the setting for malfunction
mode is “steady,” the service LED will turn and
remain on. If the setting is “pulse,” the service LED
will blink according to the blink code as follows: