3
After installing the backplate in a suitable location, wiring connections can be made
as shown above. The following criteria apply to the installation:
• The incoming AC mains supply should be 230Vac and fused at 5amps
• Optimum cable size for installation is 1.5mm2; wiring colours should be in
accordance with the current requirements of the IEE Wiring Regulations
• Cable entry should be from the rear of the backplate
• All wiring connections should be securely made, and be firmly gripped between
the square brass washers on each terminal
Do not restore the mains supply to the system until all associated items are fully
installed.
NOTE: All electrical installation work should be carried out by a suitably qualified Electrician
or other competent person. If you are not sure how to install this thermostat consult
either with a qualified electrician, heating engineer or your boiler/heating system
supplier for advice on how to continue.
Do not remove or refit the TPST201 onto the backplate without the mains supply to
the system being isolated.
User Instructions
The TPST201 is adjusted very easily by turning the rotary dial on the front of the
thermostat to the required temperature setting. To adjust the set temperature, turn
the rotary dial to the left to decrease, or right to increase the set temperature.
The indicator on the front panel will light when the temperature is below the set
value, showing that the thermostat is calling for heat from the boiler. Once the room
reaches the set temperature, it will turn off and the TPST201 will stop calling for
heat from the boiler.
Heat cut off at high temperature
When room temperature is over limit at 36°C, all heating outputs will be turned off
regardless of the control pattern and delay timers.
Valve protection
This function can be enabled/disabled by jumper, set jumper to OFF to disable this
function or ON to enable this function.
This turns on the relay (valve) for 5 minutes in every 7 days to prevent the valve
getting stuck through not moving for a long time.