Brigantia 57-DVRS50 Owner's manual

200-0057
April 2013
57-DVRS50
Gas Fired Vented Room
Heater (Direct Vent)
USERS’ INSTALLATION
OPERATION and
MAINTENANCE MANUAL
7116 Beatty Dr
Mission, BC V2V 6B4
Canada
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future reference.
Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other
appliance.
WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.
Do not touch any electrical switch; do not use
any phone in your building.
Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
If you cannot reach your gas supplier, call the fire
department.
Installation and service must be performed by a
qualified installer, service agency or the gas
supplier.
This appliance may be installed in an aftermarket
permanently located, manufactured home (USA
only) or mobile home, where not prohibited by
local codes.
This appliance is only for use with the type
of gas indicated on the rating plate. This
appliance is not convertible for use with other
gases, unless a certified kit is used.
*Conversion kit required for Propane use
WARNING: If the information in this manual is
not followed exactly, a fire or explosion may
result causing property damage, personal
injury or loss of life.
Tested and
listed by
LABTEST Certification Inc
Richmond, British Columbia
ANSI Z21.88-2009/CSA 2.33-2009
SERIAL NUMBERS 510000 AND HIGHER

57-DVRS50 2
5.08: Modifications to NFPA-54, Chapter 10
(2) Revise 10.8.3 by adding the following additional requirements:
(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part
for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is
less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following
requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled
equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-
up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe
that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, build-
ing or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to
secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon
monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a
period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery
operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provi-
sions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of
eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or
equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, "GAS VENT DIRECTLY BELOW. KEEP
CLEAR OF ALL OBSTRUCTIONS".
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the instal-
lation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions
of 248 CMR 5.08(2)(a)1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as
adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling,
building or structure used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Prod-
uct Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the
equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a
Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies
"special venting systems", the following requirements shall be satisfied by the manufacturer:
1. The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and
2. The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list
and detailed installation instructions.
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting in-
structions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at
the completion of the installation.
STATE OF MASSACHUSETTS REQUIREMENTS
For the State of Massachusetts, installation and repair must be done by a plumber or gasfitter li-
censed in the Commonwealth of Massachusetts.
For the State of Massachusetts, flexible connectors shall not exceed 36 inches in length.
The State of Massachusetts requires the installation of a carbon monoxide alarm in accordance
with NFPA 720 and a CO alarm with battery back up in the same room where the gas appliance is
installed.
For the State of Massachusetts the appliances individual shut –off must be a t-handle type valve.

INTRODUCTION
Congratulations on choosing a Brigantia!
The 57-DVRS50 is one of the most advanced Direct Vent Gas Fireplace heaters available
today. It is solidly designed using the latest technology and manufactured to the highest quality.
It is our aim to provide you with an appliance for many trouble-free years of reliable service.
Some of the many features of your 57-DVRS50 are:
Heater Classification The 57-DVRS50 is classified as a heating appliance.
Therefore, it uses Direct Vent safety technology and it is
suitable for continuously operated zone heating.
High Efficiency The 57-DVRS50 has one of the highest efficiencies of any
Direct Vent gas fireplace, which means that it is less
expensive to operate.
Adjustable Flame The flame aesthetics and heat output can be adjusted to suit
the owner’s liking and heating needs.
Solid Construction The 57-DVRS50 is mainly constructed of 16 and 18 gauge
galvanized and aluminized coated steel for long life and
durability.
Optional Accessories Check with your Authorized Brigantia Dealer for optional
accessories to suit your home’s décor and your tastes.
Electronic Control System The 57-DVRS50 uses a gas control valve that is operated by
a Multifunction Remote Control. It can be used as either an
Intermittent Pilot or Standing Pilot system.
Fireplace Model Number 57-DVRS50
Fireplace Serial Number
Date of Installation
Type of Gas Used by the Fireplace
Dealer’s Name

TABLE OF CONTENTS
Caution and Safety Instructions 4
Appliance Certification, Installation Codes and Specifications 5
Rating Plate 6
Appliance Dimensions 7
Framing Dimensions and Clearance to Combustibles 8-9
Installation Instructions 10-12
Venting Instructions 13-18
Gas Connections 18
Panel & Baffle installation 19
Burner media, Door Surround Installation 20-21
Checking Inlet & Outlet pressures 22
Final Installation Check and Initial Operation 23
Lighting Instructions on Rating Plate 24
First Fire and Lighting Instructions (CAUTION) 25
Remote Control Setup and Operation 26-32
Conversion Kit Instructions 33-35
Maintenance and Cleaning the Appliance 36
Servicing Under Warranty 37
Wiring Schematics 38
Parts List 39
Frequently Asked Questions 40
Notes 41
Warranty 42
Warranty Registration Card 43

57-DVRS50 5
Due to high temperatures, the appliance should be located out of traffic and away from furniture
and draperies.
Children and adults should be alerted to the hazards of high surface temperature and stay
away to avoid burns or clothing ignition.
Young children should be carefully supervised when they are in the same room as the
appliance. Toddlers, young children and others may be susceptible to accidental contact
burns. A physical barrier is recommended if there are at risk individuals in the house. To
restrict access to a fireplace or stove, install an adjustable safety gate to keep toddlers, young
children and other at risk individuals out of the room and away from hot surfaces.
Clothing or other flammable material should not be placed on or near the appliance.
Do not operate with cracked or broken glass. Be careful not to strike or slam the glass.
Any safety screen or guard removed for servicing an appliance must be replaced prior to
operating.
Installation and Repair should be done by a qualified service person. The appliance should be
inspected before use and at least annually by a professional service person. More frequent
cleaning may be required due to excessive lint from carpeting, bedding materials, etc. It is
imperative that the control compartments, burners and circulating air passageways of the
appliance are kept clean.
Do not use this appliance if any part has been under water. Immediately call a qualified service
technician to inspect the appliance and to replace any part of the control system and any gas
control which has been under water.
CAUTION & SAFETY
FOR YOUR SAFETY - Do not install or operate your Brigantia 57-DVRS50 without reading and
understanding this manual. Any installation or operational deviation from this instruction manual
voids the Brigantia Industries Warranty and may prove hazardous.
This appliance must be installed by a qualified gas installer and the installation must conform to
the installation codes.
Provide adequate clearance around air openings.
Never obstruct front openings.
Provide adequate clearances for proper operation and servicing of the appliance.
This appliance must be properly connected to an approved venting system and must not be
connected to a chimney flue serving a separate solid fuel burning appliance.
Must provide adequate clearance around the intake and exhaust openings
This appliance is equipped with a three pin plug for your protection against shock hazard and
should be plugged directly into a properly grounded three prong receptacle. Do not cut or
remove the grounding plug from this plug.
Caution: Label all wires prior to disconnection when servicing controls. Wiring errors can cause
improper and dangerous operation.

57-DVRS50 6
This appliance was listed by LABTEST Certification Inc to the following USA and Canadian gas
appliance standards.
- ANSI Z21.88-2009/CSA 2.33-2009 Vented Gas Fireplace Heaters
-CSA P.4.1-09 testing method for measuring annual fireplace efficiency.
The listing label is attached to the appliance on the bottom right side of the appliance.
A copy is shown on page
Please contact Archgard Industries Ltd., if you have any questions regarding the certification of
this appliance.
APPLIANCE CERTIFICATION
INSTALLATION CODES
This appliance must be installed by a qualified gas appliance installer. The installation must
conform with the local codes or, in the absence of local codes, with the current National Fuel
Gas Code ANSI Z223.1/ NFPA 54 in the US, or Installation Code CAN/CGA-B149.1 in Canada.
Electrical connections and grounding must conform with local code, or current National
Electrical code ANSI/NFPA No. 70-1987 in the US, and in Canada the current Canadian
Electrical Code CSA C22.1.
A manufactured home (USA only) or mobile home OEM installation must conform with the
Manufactured Home Construction and Safety Standard, Title 24CFR, Part 3280, or, when such
a standard is not applicable, the Standard for manufactured Home Installations, ANSI/NCSBCS
A225.1 or Standard for Gas Equipped Recreational vehicles and Mobile Housing, CSA Z240.4
We recommend that our gas hearth products be installed and serviced by professionals
who are certified in the U.S. by the National Fireplace Institute®(NFI) as NFI Gas
Specialists.
SPECIFICATIONS
HIGH ALTITUDE INSTALLATION
When installing this appliance beyond 2000 ft. (610 M) above sea level, the appliance must be
properly de-rated and installed according to local codes, in the absence of local codes, with the
current National Fuel Gas Code, ANSI Z223.1/ NFPA 54, in the US or Installation Code, CAN/
CGA-B149, in Canada.
Natural Gas LPG
Maximum input rating / Entrée assignee
Minimum input rating / Entrée assignee
50,000 BTU/hr (14.7kW)
21,000 BTU/hr (6.1 kW)
50,000 BTU/hr (14.7kW)
19,000 BTU/hr (5.6kW)
Maximum manifold pressure / Pression d’admission
Minimum manifold pressure / Pression d’admission
3.5” W.C. (0.9 kPa)
1.7” W.C. (0.4 kPa)
10” W.C. (2.5 kPa)
6” W.C. (1.5 kPa)
Orifice size - Center / Dimension de l’orifice
Orifice size - Sides / Dimension de l’orifice
#35 DMS (2.77mm) x 1
#48 DMS (1.93mm) x 2
#53 DMS (1.63mm) x 1
#58 DMS (1.09mm) x 2
Minimum supply pressure for purpose of input adjustment /
Pression minimale d’alimentation pour le but d’adjustement
de contribution
4.5.0” W.C. (1.24kPa)
11.0” W.C. (2.8 kPa)
Control Valve / La soupape controle SIT Proflame 885 SIT Proflame 885
Altitude / Elevation 0 - 2000ft (0 - 610m) 0 - 2000ft (0 - 610m)
Electrical Rating / Tension electrique 120 VAC, 60 Hz, 1.4A 120 VAC, 60 Hz, 1.4A
Primary Air opening 1/16” (3mm) OPEN 1/4” (12mm) OPEN

57-DVRS50 7
RATING PLATE
NG / NATURAL
LP / PROPANE
This appliance must be installed in accordance with local
codes, if any; if none, follow the National Fuel Gas Code,
ANSI Z223.1/NFPA 54, or Natural Gas and Propane
Installation Codes, CSA B149,1. Electrical connections and
grounding must be in accordance with local codes, if any; if
none, follow the current CAN/CSA C22.1 in Canada and
ANSI/NFPA 70 in the US. This appliance is certified for
installation in a bedroom or a bed sitting room. This
appliance is only for use with the gas indicated on the rating
plate and may be installed in an aftermarket, permanently
located, manufactured (mobile) home where not prohibited
by local codes. See owner’s manual for details. This
appliance is not convertible with other gases, unless a
certified kit is used.
Il faut que cet appareil soit installé selon les codes locaux, s’il y en a;
sinon, suivre le CAN/CGA-B149 actuel au Canada et ANSI Z223.1 aux
É.-U. Il faut que le raccordement électrique et la mise à la masse soient
en conformité avec les codes locaux, s’il y en a; sinon, suivre le CAN/
CSA C22.1 actuel au Canada et ANSI/NFPA 70 aux É.-U. Cet appareil
est certifié pour l’installation dans une chambre à coucher ou une pièce
qui sert de chambre.
LISTED VENTED GAS FIREPLACE HEATER. RADIATEUR VENTILE, CIRCULATEUR DU TYPE
VENTILATEUR. Tested to / Testée selon les normes :
ANSI Z21.88-2009 / CSA 2.33-2009
VENTED GAS FIREPLACE HEATER-NOT FOR USE WITH SOLID FUEL. This vented gas fireplace
heater is not for use with air filters. Certified for use in both CANADA and USA. / Certifié pour
utilisation dans le Canada et les ÉTATS-UNIS
DO NOT REMOVE THIS LABEL
NE PAS ENLEVER CETTE ÉTIQUETTE
# de série
Serial # LC
Made in Canada by / Fabrique
au Canada par:
Archgard Industries Ltd.
NG LPG
Input rating (min/max)/ Entrée assignée 21,000- 50,000 BTU/hr
(6.1 - 14.7 kW)
19,000 - 50,000 BTU/hr
(5.6 - 14.7kW)
Manifold pressure ( min - max)/ Pression d’ad-
mission 1.7”W.C.(.4 kPa) - 3.5”. W.C. (0.9 kPa) 6”W.C.(1.5kPa) - 10” W.C. (2.5
kPa)
Orifice size-Center/ Dimension de l’orifice
Orifice size-Sides/ Dimension de l’orifice
#35 DMS (2.77 mm dia.) x 1
#48 DMS (1.93 mm dia.) x 2
#53 DMS (1.63 mm dia.) x 1
#58 DMS (1.09 mm dia.) x 2
Minimum supply pressure (for the purpose of input
adjustment) / Pression minimale d’alimentation
pour le but d’adustment de contribution
4.5 in. W.C. (1.24 kPa) 11.0 in. W.C. (2.8 kPa)
Control valve / La soupape contrôle: SIT Proflame 885 SIT Proflame 885
Altitude / Elevation 0 - 2000 ft (0 - 610 m) 0 - 2000 ft (0 - 610 m)
Electrical rating / Tension électrique 120 VAC, 60 Hz, 1.4 A 120 VAC, 0.6A
Keep burner and control compartment clean.
See Instructions accompanying the heater.
Maintenir propres le brûleur et le compartiment
de commande. Voir les instructions relatives à
l’installation et au fonctionnement qui accom-
pagnent le radiateur.
Optional LP fuel conversion kit : 57-CKLP
Minimum Clearances to Combustibles / Distances:
Minimales entre l’appareil et les combustibles:
Ceiling / Plafond: 24” (609 mm) Measured from top of host shell
Floor / Plancher: 10” (152 mm) Measured from bottom of host shell
Adjacent Side Wall/Paroi latéraleadjacent: 18” (457 mm)
8” Deep Mantle : 12” (304 mm) Measured from top of host shell
Adjacent sides and rear: 0” from stand-offs.
See Owner’s Manual for additional clearances
MODEL / MODÈLE: 57-DVRS50
303-6057 APRIL

57-DVRS50 8
APPLIANCE DIMENSIONS
Surround Removed
Surround Attached

57-DVRS50 9
Framing Dimensions
The following section describes the requirements for framing for the model 57-DVRS50.
Note: Framing should be constructed as required by local building codes
2 x 6 Framing, opening in framing should be minimum of 66.50”W x 42.00”H.
Figure 1
Figure 2

57-DVRS50 10
Figure 3
Figure 4
12” (304)mm
16” (403)mm
20” (504)mm
Measured from top
of host shell.
Corner Install View
Mantle Clearances
Inches MM
Top - to standoffs 0” 0
Sides-to standoffs 0” 0
Adjacent Side Wall 18” 454
Room Floor* (From
bottom of host shell)
5” 101
Vent - Top 2” 50
Vent - side/bottom 1” 25
Front 48” 1210
Room Ceiling (From
top of host shell)
24” 907
Minimum measurements below are from the edge
of door (unless otherwise noted).
Clearance to Combustibles
* Clearance to combustible floor must maintain
clearances from the top surface of carpet, flooring,
etc.

57-DVRS50 11
Installation Instructions
Figure 5
999-DV-8HTCL
Stand-off
The 999-DV-HTCLT termination
allows the horizontal run to a
maximum of 32”.
Use when connecting to a flexible
vent system
Maximum 6” Horizontal run
when using the basic
999-DV-HTCL Termination.
Used only when there is a
direct connection to the unit

57-DVRS50 12
Installation Instructions
Frame opening and cut out hole for the termination and thimble
as shown in fig. #6
Figure 6
When installing on an exterior wall you must install the exterior wall insula-
tion board (#57-IB).
Place insulation board with the foil facing into the room.
Install the wall thimble (as shown below) and seal it and the edges of the
insulation board with a good quality silicone sealant to prevent cold drafts.
(exterior wall only)
Figure 7
Se
Nailing Flanges
Install the nailing flanges provided, by screwing them to the side of the outer shell using the appropriate holes for the facing
material. Place the fireplace into the framed opening and secure the nailing flanges to the wall.
Figure 8 Figure 9

57-DVRS50 13
Installation Instructions Cont.
Caulk the outside portion of the vent collar to the fire-
stop to prevent cold drafts.
Next install the outer portion of the wall thimble and the
termination.
Installed fireplace with stand-offs
Figure 11
Figure 12
Figure 10
N O T E
For installations straight off the back of the 57-DVRS50
the Archgard 999-DV-8HTCL termination is required.
The maximum horizontal run straight out the back is
6.00”(no rise).
For horizontal venting of up to 32” use the 999-DV-
8HTCLT.
When using the “TALL” termination a 1”/ft rise is
recommended

57-DVRS50 14
Installation Instructions Cont.
VENTING
Clearance to combustibles
The following clearances must be maintained around the vent pipe:
Vertical runs: 1”
Horizontal runs: 2” on top, 1” sides and bottom
IMPORTANT: This appliance venting system is a sealed system (DV), which means that all combustion
air is supplied from outdoors and the combustion products are exhausted to the outdoors.
Note: Only venting systems listed in this manual may be used with the model 57-DVRS50
Planning your vent installation
This type of direct vent system may terminate in one of two ways: vertical termination using a vent cap, or
horizontally using a wall termination. There are limitations to the vertical and/or horizontal lengths (see
page 18 for venting chart).
When calculating the length of the vent pipe from the outlet of the appliance to termination, allowing for
ceiling thickness, the vertical rise in the attic or second story and sufficient vertical height above the roof.
Fire stops are required at each floor level the vent passes through.
The following vent systems are certified for use with the model 57-DVRS50
If for any reason the vent pipe is disconnected it must be correctly resealed
Fig 14-A
Manufacturer Vertical Termination Adapter
Archgard 999-DV-8HTCL (Direct connect to unit)
999-DV-8HTCLT ( Flex connect to unit) N/A
Dura Vent ??? - Co-Axial Cap (requires adapter)
??? - Co-Axial High Wind (requires adapter) 58DVA-MG
ICC/Excel ?? - Co-Axial (requires adapter)
???- Co-Axial (requires adapter)
Ameri-vent DVC - Co-Axial Cap (requires adapter)
Selkirk Direct Temp DV Venting 5DT-AA Series
2-ply Aluminum 5” x 8” 2-ply Listed Aluminum Flexible pipe
A T T E N T I O N
NO OTHER VENTING SYSTEM OR COMPONENTS MAY BE USED. Follow manufacturer instructions
for installation of termination.
The listed chimney vent systems use a twist lock connection. Assemble the vent system using the de-
sired combination of sections and elbows for your installation. Make sure you fully insert and twist the
mating sections all the way to make a solid connection.
Install as per manufactures instructions

57-DVRS50 15
Installation Instructions Cont.
The position of the horizontal vent termination
must be positioned in such a way as to meet all
local building codes.
Cut and frame the exterior wall to accept the
Wall Thimble. Install the Wall Thimble shield
using wood screws. If the wall being penetrated
is constructed of non-combustible material con-
crete or block wall a 8” hole sufficient for the
vent pipe is acceptable.
Venting terminals must not be recessed
into wall or siding
When the termination is to be attached to vinyl siding apply a bead of non-
hardening mastic around the outside edge to form a seal between the
standoff and the terminal. Attach the termination to the exterior wall using four wood
screws through the holes in the corners.
Complete the termination installation and apply a bead of mastic around the outer edge
of the vinyl standoff.
With the termination installed you can now connect the completed vent assembly by
sliding the unit back towards the wall and carefully inserting the pipe into the terminal.
Slide the pipe into the vent, making sure that at least 1¼” overlap between the pipe
and the termination.
N O T E
ALLOWING THE VENT PIPE TO SLOPE DOWN TOWARDS THE VENT TERMINA-
TION WILL CAUSE POOR COMBUSTION AND/OR HIGH TEMPERTURES THAT
MAY PRESENT A FIRE HAZARD.
WHEN HORIZONTAL VENTING RISE IS REQUIRED SEE VENTING CHART FOR
ACCEPTABLE VENTING CONFIGURATIONS
Fig 15-A Fig 15-B
Horizontal Wall Vent Terminations
Standard Installation:
Built in to exterior wall
999-DV-HTCL termination
Build-in to room Installation:
Requires the
999-DV-8HTCLT termination
Standard Termination Tall Termination

57-DVRS50 16
Installation Instructions Cont.
Horizontal Installation
The horizontal run must have a 1/4” rise on an exterior wall and
must meet all local and national building codes, and must not be
easily blocked or obstructed. Termination clearances are as
follows (see Figure 16):
A. Clearance above ground, verandah, porch, deck, or bal-
cony: 12” minimum (30 cm.)
B. Clearance to a window or door that may be opened: 9”
minimum (23 cm)
C. Vertical clearance to a ventilated soffit located above the
termination within a horizontal distance of 2 feet from the
centerline of the termination: 18” minimum (46 cm). Note:
Clearances are to be in accordance with local installa-
tion codes and the requirements of the gas supplier.
D. Clearance to an unventilated soffit: 18” minimum (45 cm).
Note: Clearances are to be in accordance with local
installation codes and the requirements of the gas
supplier.
E. Clearance to an outside corner: 12” (30 cm). Note: Clear-
ances are to be in accordance with local installation
codes and the requirements of the gas supplier.
F. Clearance to an inside corner: 12” (30 cm). Note: Clear-
ances are to be in accordance with local installation
codes and the requirements of the gas supplier.
G. Do not install above a meter/regulator assembly within 3
feet (90 cm) horizontally from the centerline of the meter/
regulator. Note: Clearances are to be in accordance
with local installation codes and the requirements of
the gas supplier.
H. Clearance to a service regulator vent outlet: 6’ minimum
(1.8 m)
I. Clearance to a non-mechanical air supply inlet to a building
or the combustion air inlet to any other appliance: 12” mini-
mum (30 cm)
J. Clearance to a mechanical air supply inlet: 6’ minimum (1.8
m)
K. Clearance above paved sidewalk or paved driveway lo-
cated on public property: refer to local code
L. Clearance under open verandah, porch, deck, or balcony:
12” minimum (30 cm). Note: Clearances are to be in ac-
cordance with local installation codes and the require-
ments of the gas supplier.
M. Maximum horizontal run 5’ after 2’ vertical rise. Liquid Pro-
pane gas 5’ horizontal run to 35’ vertical rise. Natural Gas
maximum 35’ horizontal run with 7’ vertical rise. Note:
Clearances are to be in accordance with local installa-
tion codes and the requirements of the gas supplier.
Figure 22 –Vent Termination Locations

57-DVRS50 17
Vertical Venting Examples
Installation Instructions Cont.
Always maintain a 1” clearance around the vent pipe (vertical) and on horizontal venting 2” clearance on the top of
the vent, when passing through ceilings, walls, roofs, enclosures, attic rafters or any combustible surfaces.
DO NOT PACK AIR SPACES WITH INSULATION.
Refer to the vent chart on page 18 for maximum allowable vertical and horizontal allowable installations.
When planning your installation, determine if ceiling joists, roof rafters or other framing will obstruct the vent system.
You may have to use 45° elbows to navigate around any obstacles. When passing through a flat ceiling, install a
Box/Wall thimble. Cut a 10” square hole and frame as shown in the diagram opposite.
Ensure all pipe sections are fully twist locked.
NOTE: ALWAYS CHECK YOUR LOCAL
CODES BEFORE INSTALLING VENTING.
CLEARANCES, ETC, MAY VARY FROM
STATE TO STATE(PROVINCE TO PROV-
INCE).
Through Roof / Floor Framing
Use a suitable round or square support
through the roof as supplied by the vent
manufacturer.
Fig 17-A
Fig 17-C
Vent Restrictors
Due to the extra flow produced by tall venting configurations the vent restrictors must be adjusted to
maintain performance. The vent restrictor is designed into the appliance firebox.
When required, adjust the restrictor inside the unit firebox. Release the screws and adjust the restrictor
position according to the venting charts.
Adjust restrictor as re-
quired using appropriate
hole position
Fig 17-B

57-DVRS50 18
Installation Instructions Cont.
Venting Chart Maximum Total Venting Length
Maximum total venting allowed is 50ft.
This would be when configured for 40ft
vertical with 10ft horizontal.
Maximum vertical vent is 40ft.
Maximum horizontal vent is 20ft.
Minimum 10ft vertical vent rise required
for maximum 20ft horizontal vent run.
See chart for allowable vent runs.
Maximum horizontal elbows
allowed - 3
Note: if more than 1 90˚ elbow is used
horizontally the maximum horizontal is
reduced by 1ft.
Example:
If to reach the desired termination at
point ‘A’ you use 2 90˚ elbows, you
would be required to reduce the maxi-
mum horizontal from16’ to 15’.
If 3 90 ˚ elbows were used to reach
point ’A’, the maximum horizontal
would be reduced from 16’ to 14’.
40
35
30
25
20
15
10
A
5
0 1 2 3 4 5 6 7 8 10 15 2011 12 13 14 16 17 18 19
Restrictor
Note: The model 57 DVRS50 is sup-
plied with an adjustable restrictor. The
restrictor is not required for most in-
stalls. However if the flame is consid-
ered too lively, the restrictor may be
installed and adjusted to provide the
required flame picture.
Example: Using rigid pipe over 40’ may
require restriction.
HORIZONTAL VENT RUN
Fig 18-A
V
E
R
T
I
C
A
L
V
E
N
T
R
U
N
6” - 32” Horizontal available
with the use of the
999-DV-8HTCLT termination.
Fig 18-B

57-DVRS50 19
Before connecting the appliance to the gas supply line, double check that the appliance you
have purchased is designed for the gas type you are using. The gas type markings are located
on the certification label and also on the appliance’s gas valve.
Adequate clearance for proper installation and checking of the gas connections must be
provided. All gas connections must be checked for gas leaks.
GAS CONNECTIONS
Have your gas supplier or a qualified gas fitter run a gas supply line into the fireplace. The line
must be properly sized and fitted according to the installation codes. Immediately upstream of the
supply connection, the fitter shall provide an accessible manual shut-off valve. When connecting
the supply line to the gas valve, the installer shall brace the gas valve to ensure that the gas valve
is not moved from its bracket. If the valve is not braced when the supply line is connected, the
valve may be moved and cause a “break” in the main burner supply line. Such damage is not
covered by the manufacturer’s warranty.
CAUTION: The appliance must be isolated from the gas supply piping system by closing its
individual manual shutoff valve during any pressure-testing of the gas supply piping system at
test pressures equal to or less than 1/2 psig (3.5 kPa). Failure to do so will damage the
appliance’s gas valve. Such damage is not covered by the manufacturer’s warranty.
Natural Gas Pressure Settings:
The inlet supply or line pressure must be a minimum of 5” W.C. (1.2 kPa) and a maximum of 14”
W.C. (3.5 kPa). The orifices are a #35 DMS (2.73 mm) drill size for the center burner and #48
DMS (1.93 mm) for the two outer burners.
ELEVATION INPUT RATING
0-2,000 ft (0-610 M) 50,000 BTU/hr (14.7 kW)
2,000 ft (610 M) and above. 50,000 BTU/hr (14.7 kW) less 4% per 1000 ft. (305 M)
Please contact your local distributor for the appropriate orifice size you require.
Propane Pressure Settings:
The inlet supply or line pressure must be a minimum of 11” W.C. (2.8 kPa) and a maximum of 14”
W.C. (3.5 kPa). The orifices are a #52 DMS (1.78 mm) drill size for the center burner and
#57 DMS (1.07mm) for the two outer burners .
ELEVATION INPUT RATING
0-2,000 ft. (0-610 M) 50,000 BTU/hr (14.7 kW)
2,000 ft. (610 M) and above. 50,000 BTU/hr (14.7 kW) less 4% per 1000 ft. (305 M)
Please contact your local distributor for the appropriate orifice size you require.
NOTE: THE INPUT RATING SHOULD ALWAYS BE CHECKED WHEN FIRST RUNNING THIS
APPLIANCE. To do this, reduce the background flow rate, time the meter, light the fireplace and
take another reading after 15 minutes of operation. Check with your gas supplier for the gas BTU
content at your elevation. Input is the rate of flow multiplied by the heating value of the gas (cubic
feet/hour x BTU per cubic feet). Adjust the manifold pressure so that the unit does not operate
above the rated input.
IMPORTANT: For high altitude installations above 2000 ft (610 meters), consult local gas distributor or the authority having juris-
diction for proper de-rating methods.

57-DVRS50 20
1. Hang the left and right side back panel onto the bracket in the
back of the firebox. Align with the far outside edge of the
bracket.
2. Hang the center back panel onto the bracket and slide the two
outside panels in until they touch the center panel.
Rear Panel Installation Instructions
Side Panel & Baffle Installation Instructions
Set the right and left side
panels by inserting the tabs
into the slot of the support
plate. Panel s should angle
into the firebox (as shown)
Set the baffle on top of the side
panel so the slot in the baffle
sets over the tab on the side
panel.
Small holes to the back
The side panels are secured
thru the side of the firebox
Table of contents
Other Brigantia Indoor Fireplace manuals
Popular Indoor Fireplace manuals by other brands

Vanguard
Vanguard VYGF33NRA OWNER'S OPERATION AND INSTALLATION MANUAL

Firesense
Firesense 60354 Use and care guide

Heat & Glo
Heat & Glo 6KX-CU installation manual

RealFlame
RealFlame IGNITE XLF50 Assembly & installation manual

Heat & Glo
Heat & Glo EXCLAIM-50 owner's manual

ModaFlame
ModaFlame Lugo GF101600 user manual

RealFlame
RealFlame IGNITE XL BOLD Installation & operating manual

foc.us
foc.us édofocus 630 dv Specific instructions

Heat & Glo
Heat & Glo Cosmo-SXT-IPI owner's manual

bemodern
bemodern BM-091 2 Series User instructions

Legend
Legend Ethos Landscape Installation and user instructions

Urbana
Urbana U50I-S installation manual