Brower MC Series User manual

INSTRUCTIONS
AND REPAIR PARTS LIST
WARRANTY INFORMATION
MC - MH - MJ - MK
SERIES AUTOMATIC
WATERERS
We know that you will be pleased with your decision to purchase a Brower waterer. Please take time to familiarize yourself with this
manual. Included are tips that will make use of your waterer more trouble free and more economical. Red and white Brower waterers
were marketed under the Marlor label for 25 years. Marlor waterers carried a light green and white color scheme. Brower parts will ser-
vice most Marlor waterers. This instruction manual covers the following model numbers: MC32E, MC32N, MK32HE, MK32HN, MJ31HE,
MJ31HN, MC32HE, MC32HN, MH30E, MH30N.
EQUIPMENT FOR POULTRY • LIVESTOCK • PETS
P.O. BOX 2000, HOUGHTON, IOWA 52631, USA
TELEPHONE 319-469-4141 • FAX 319-469-4402
E-mail: sales@hawkeyesteel.com web: www.browerequip.com
COPYRIGHT © 2023
ALL RIGHTS RESERVED
ISBWATERER
Rev. 1.7
PRINTED IN U.S.A.
MK
MC
MH
18”
13 1/4” 23 3/4”
24”
21” 31”
MJ
8 1/2”
23 3/4”
13 1/4”
18”
13 1/4” 15 1/2”
READ ALL DIRECTIONS CAREFULLY BEFORE BEGINNING INSTALLATION
WARNING
1. INSTALLATION MUST BE MADE AND MAINTAINED IN STRICT ACCORDANCE WITH
NATIONAL/LOCAL PLUMBING AND NATIONAL/LOCAL ELECTRICAL CODES (CSA
IN CANADA). INSTALLATION MUST BE MADE BY A QUALIFIED ELECTRICIAN. THE
APPLICABLE PROVISIONS OF THE ABOVE MENTIONED CODES TAKE PRECEDENT.
IMPROPER ELECTRICAL INSTALLATION AND MAINTENANCE MAY RESULT IN SERIOUS
INJURY OR DEATH FOR PERSONNEL OR LIVESTOCK.
2. EACH ELECTRICAL UNIT MUST BE WIRED THROUGH A FUSED SWITCH BOX AND FUSED
ACCORDING TO AMPS REQUIRED FOR EACH SPECIFIED ELECTRICAL UNIT. SEE
EXHIBIT A. CANADIAN ELECTRICAL CODE--PART 1 REQUIRES LIVESTOCK WATERERS
INSTALLED IN FEEDLOTS IN OPEN FEEDING AREAS TO BE GROUNDED BY A SEPARATE
STRANDED COPPER GROUNDING CONDUCTOR OF AT LEAST NO. 6 AWG TERMINATING
AT A POINT WHERE THE BRANCH CIRCUIT RECEIVES ITS SUPPLY.
3. THIS UNIT MUST BE GROUNDED TO A COPPER GROUND ROD 5/8" (1.6CM) DIAMETER
BURIED AT LEAST 8 FEET (2.5 METERS) IN UNDISTURBED SOIL. SEE EXHIBIT A.
4. DO NOT USE SUPPLEMENTAL HEAT SUCH AS A SPACE HEATER.
!
!

The following is intended to be used as a general
guide for wiring electrically heated waterers.
Paragraph 5, 6, and 7 are taken from ASAE
Engineering Practice: ASAE EP 342.3. Safety for
Electrically Heated Livestock Waterers, October
2015. Installation can only be completed by a
qualified electrician.
5. Electrical Service
5.1 Service conductors should conform to the
following:
5.1.1 Conductors shall have sufficient ampacity for
the load to be served.
5.1.2 Overhead conductors shall have mechanical
strength for the distance spanned. The
conductors shall not be smaller than NO. 8
American wire gage, AWG, copper.
5.1.3 Buried connectors shall be of type USE
(or UF when protected as a feeder or
EXHIBIT B
Waterer supplied by
building service equipment
EXHIBIT C
Waterer supplied by its own service equipment
I
I
)
I
-
Waterer disconnecting
means with over current
protection.
Cable or
Conduit
Building
service
equipment
To
Grounding
Electrode
Grounded
Conductor
Equipotential Plane
Equipotential Plane
with Voltage Ramp.
6" Tile Southern States
12" Tile Northern States
Extend at least 3 ft. or
below frost line.
Pressure Water Supply
with Shut Off Valve.
NOTE: Check local codes.
Some jurisdictions require 2
grounds & rods.
branch circuit) and shall be buried at least 610mm (24 in.) below the ground surface (or according to state/load codes). Wet
rated conductors in non-metallic conduit are also recommended for providing service.
5.2 Waterer installed near or in a building may be served by a dedicated 15A GFI from the service equipment of the building.
6. Supply Circuits
6.1 Waterers installed within or near a building and shall be served by a dedicated 15A GFI from the service equipment of the
building and shall be connected as in Exhibit B.
6.1.1 The equipment grounding conductor shall originate at the service equipment of the building.
6.1.2 The equipment grounding conductor shall be connected to the equipment grounding terminal of the waterer and bonded to
any intermediate enclosure or device that requires grounding. The equipment grounding conductor shall be isolated from
the grounded (neutral) conductor at every point beyond service equipment.
6.2 An individual waterer installed in a lot and served by separate service equipment shall be connected as in Exhibit C.
6.2.1 Overhead conductors shall be firmly attached to support points and conform to 5.1.1 and 5.1.2. Buried conductors shall
conform to 5.1.3.
6.2.2 The incoming grounded conductor shall be bonded to the service equipment enclosure and to a grounding electrode
conductor at the grounding bar in the service equipment. The grounding electrode conductor shall extend to a grounding
electrode (a ground rod or other effective electrode).
6.2.3 An equipment grounding conductor shall originate at the service equipment and shall be installed with the circuit conductors
to the waterer.
6.2.4 The equipment grounding conductor shall be installed as described in 6.1.2.
7. Multiple Installations
7.1 When more than one waterer is to be served from a central service, the service equipment should be located near the load
center.
7.2 Each waterer shall be connected as specified in 6.2.
NOTE: THE USE OF THE RISER PIPE AS A GROUNDING MEANS IS NOT RECOMMENDED
There shall be only one ground fault interrupter in the electrical delivery to the waterer.
4" - 6" Gravel Fill
EXHIBIT A
NOTE:
External disconnect
with property rated
overcurrent protection
device (OCPD)
2

LOCATION: Locate waterer in a place sheltered from the prevailing winds for reduced energy consumption.
Install the waterer 25 feet or more from self-feeders or bunk feeders to reduce the amount of feed and salt that is
dropped into the waterer.
WATER SUPPLY LINE: Horizontal underground waterline should be sized to account for any pressure drop relat-
ing to distance. The vertical supply pipe should be rigid plastic, copper or galvanized. We suggest you use a 1/2”
(1.27 cm) pipe for hog waterers and a ¾” (1.91 cm) for cattle waterers. Water lines over 50 feet (15.3 m) should
be one inch (2.54 cm), or larger. Use of undersized feeder pipe causes excessive pressure drop and loss of re-
covery capacity of waterer. Models are equipped with the following for supply connection: MH- ½ inch (1.27 cm),
MC, MJ, and MK – ¼ inch (.635 cm)
A shutoff valve should be provided under the waterer to shut off water when servicing. Flush supply pipe thor-
oughly before connecting to fountain. Water supply with foreign material such as sand, rust, etc. may require a
filter to keep valve working properly.
The full length of the vertical supply pipe must be centered in a 6-inch (15.3 cm) (or larger if the waterer will ac-
commodate it) riser tile or PVC casing. Extend the tile from a point 1 inch (2.54 cm) above the top of your platform
to a point below the frost line. DO NOT place insulation or other materials in the tile. This will stop the air flow and
cause water line to freeze up. Consider using an insulated foam sleeve on the vertical supply line (not included).
MOUNTING PAD: Waterer must be mounted on a concrete pad. The pad should be sloped about one-quarter
inch per foot away from the waterer. We recommend a minimum thickness of four inches (10.2 cm). The size of
the pad is left to the user’s discretion but we suggest you pour a pad large enough for livestock to stand on while
drinking. This is about 8’ square (.75 square meter) for MC, MJ, and MK models and 16’ square (1.5 square me-
ters) for model MH. An additional 4” to 6” pedestal (on top of the pad) extending 10 to12 inches from the waterer
on all four sides will provide protection from livestock backing up to or rubbing against the waterer. It will also
protect it from manure and manure handling equipment. A rough broom finish to the concrete surface provides a
better footing for livestock.
BE SURE TO PLACE A COPPER GROUND ROD TO USE IN GROUNDING THE WATERER AS SHOWN IN EXHIBIT
A. THE WATERER MUST BE GROUNDED AT LEAST 8 FEET (2.4 meters) INTO THE GROUND.
INSTALLATION
1
2
3
3
SETTING THE WATERER: Once the concrete is firm, mark the concrete for bolts by referring to Exhibits B, C, and
D. Space the bolts so you can easily line up the inlet pipe connection in the waterer. It is advisable to make a tem-
plate of the base of the waterer to check holes before the concrete is set. Alternatively, you may wish to mark the
concrete after it has set and drill holes to hold the anchor bolts. Install four 3/8” (.95 cm) x 5” (12.7 cm) bolts (not
included) in the concrete. When the concrete is dry, we recommend that you caulk (all weather sealant) the area
of waterer base contact. This will prevent air from leaking under the waterer and decreasing energy efficiency.
Also a sheet of aluminum foil placed over the concrete pad inside the waterer will reduce heat loss. Also a sheet
of aluminum foil or an aluminum faced foam board (not included) placed over the concrete pad inside the waterer
will reduce heat loss.
4

BASE DIMENSIONS
4
EXHIBIT B EXHIBIT C
EXHIBIT D
CONNECTION TO WATER SUPPLY LINE: See Exhibit E. On models MC, MJ, and MK, the valve in your waterer is
connected to part number MC180 - 1/2 x 1/4 reducing elbow. The elbow is connected to either a 1/2” x 7” galva-
nized nipple (MC) or a 1/2” x 12” galvanized nipple (MJ and MK). The valve, the elbow and the nipple are as-
sembled in the waterer. Part number MC183 flex hose assembly is in the valve hardware bag. It is 6 inches long.
Connect the female end of the flex hose assembly to the galvanized nipple in the waterer and then to your water
supply on the other end (and / or preferably the shutoff valve (not included) you installed to the top of your water
supply). The flex hose is included to prevent frost heave problems. Make sure pipe or flex hose do not touch an
outside surface of the waterer or the heater. On model MH, the valve is connected to part number OP2 3/4” x 1/2”
reducing elbow. The elbow is connected to a 1/2” x 17” galvanized nipple. Connect your water supply (or shutoff
valve) with a flexible hose (not included). Use Teflon tape or a Teflon sealant on all connections.
OUR VALVE IS MOLDED WITH ABS RESIN. FOR THREAD SEALING, USE ONLY STANDARD TEFLON
TAPE OR PLASTIC COMPATIBLE TEFLON SEALANT. DO NOT USE PIPE THREAD SEALANT (COMMONLY
CALLED “PIPE DOPE”) OR SEALANT FORMULATED WITH PTFE.
5
MJ MC/MK
MH

VALVE ADJUSTMENT: Water flow is controlled to a degree by the size of the valve orifice (Ref No 5). More water
flows with the VP26 1/4” orifice than with VP24 1/8” orifice. The two orifices are interchangeable without changing
the valves. If you have low or gravity flow pressure, you might be able to use a VP26 orifice in a VP226 valve to get
higher water flow. If your valve will not shut off completely, check your water pressure. The valve works best on wa-
ter pressure up to about 60 psi. Higher pressures may require the installation of a pressure regulator.
If the float bounces, valve chatters or there is a pounding noise in the water line when the water turns on or off, it
can be due to an excessive amount of air in the water line. The best course probably is to consult an experienced
plumber as there can be several options to correct this.
If there are issues with valves, they tend to be related to high water pressure as discussed above. The origin of high
water pressure issues tend to be rural or urban water systems. If your water source is your own well, low pressure is
more likely to be an issue. Low water pressure from wells can have many sources including: low water yields from
the well, size of the well casing, adequacy and working condition of the pump, pressure settings if available, size
of distribution pipes among others. Consult a well driller or knowledgeable plumber. Higher pressures may require
the installation of a pressure regulator. ALSO NOTE: If you purchased Models MC,MJ or MK, you are receiving our
VP226 valve, which comes with VP24 orifice. VP24 orifice has an 1/8 inch opening. See Exhibit F. Also included
with VP226 valve, is a small poly pack containing a VP25 orifice. If water drip is a problem and you believe you have
done everything correctly- installation, controlled water pressure, etc, try VP25 orifice. It has a 3/32 inch opening. It
flows about .5 to 1.5 gallons per minute.
7
6INSTALL FLOAT: SEE EXHIBITS F AND G. Screw either VA225P 1 1/8” arm
(MC, MJ, MK) or WC726P 3 5/8” arm (Ref No 10) into the boss on OP321
Float (Ref no 11). The hole on the float is not threaded. Make sure the arm
is threaded in as straight as possible. Note that the float goes in the waterer
in the vertical position. The arm can be tightened using VP115 (ref No 9)
adjust screw (wing nut or thumb screw). You can alter the water level in the
trough by changing the float position. Loosen the adjust screw and try vari-
ous float positions until the desired level is attained. Tighten adjust screw
securely. Place the valve cover, drain and refill the trough several times to
ensure that the float arm operates freely. If the float tilts to one side or the
other, loosen the assembly nut (Ref No 8) and turn the valve body slightly.
If you still think there is interference, you may need to trim some insulation
underneath of the cover. If you have high water pressure, it may be that the
float will not always stay in the same position where you would like to have
it. A star washer (not included) placed between the VP29 valve arm and the
float arm will help secure the float at the desired height.
MC180 ELBOW
ASSEMBLED TO
VALVE IS ALREADY
ATTACH MC183 FLEX
HOSE ASSEMBLY TO
LOWER END OF
GALVANIZED NIPPLE
AND THEN TO YOUR
SHUTOFF VALVE AND/OR
WATER SUPPLY
Exhibit E
5
HEATER: Model 77 heater is installed on our MC, MJ, MK, and MH waterers. Model 77 is a 500 watt heater that plugs
into a 120 volt outlet. It draws a maximum of 4 amps. The heater features a control knob which allows a range of 15
watts (at the lowest setting) to a maximum of 500 watts. You will probably never need to turn the knob more than
about half way. The electrical supply line needs to be installed by a qualified electrician in accordance with all electri-
cal codes. See the WARNING on page 1 and Exhibit A on page 2. When heat is not needed, we recommend that you
unplug the heater. The heater is not thermostatically controlled. The heater is not immersible.
Model 77 Utility Heater is warrantied for 18 months. Please return your warranty card. The serial number for your model
77 heater is found on the label which is around the control knob. Look for it just below the knob.
If a new unit fails to operate after installation of the unit has been installed and working and then begins to freeze, check
the following:
Make sure the heater is getting 120 volts of electricity. Low voltage will reduce the heat put out. If no electricity is pres-
ent, turn off the main fuse box for the unit. Check all wire connections to sure they are correct and tight. Check all fuses.
Then, turn on the electricity.
Make sure the water trough is clear of mud and silt. Mud can insulate and not allow the water to heat.
If you are sure that adequate electricity is being delivered to the unit and there is still no heat, most likely the heater
needs to be replaced.
8

6
EXHIBIT F- FOR MC, MJ, MK EXHIBIT G- FOR MH
PO BOX 2000 •HOUGHTON, IOWA 52631 • USA
PHONE: 319-469-4141 FAX: 319-469-4402
READ ALL DIRECTIONS CAREFULLY BEFORE BEGINNING INSTALLATION
INSTRUCTIONS
AND REPAIR PARTS LIST
MODEL NUMBERS
The MODEL NUMBERS are: VP221, VP223, VP224, VP226, VP227, VP2-1/8RP, VP2-1/4RP
WHEN ORDERING PARTS
(1) Show MODEL NUMBER and NAME: Example - VP221 Float Valve, 1/4” Orifice
(2) Show PART NUMBER and FULL DESCRIPTION of part: Example - VP21 Valve Body, Poly
HOW TO ORDER PARTS
Repair parts may be ordered from your dealer.
COPYRIGHT © 2017
ALL RIGHTS RESERVED
ISHVP2
REV. 3.0
PRINTED IN U.S.A.
VP2
Valve Series
VP2 PARTS LIST
Ref
No
Item
Number Description VP226VP221 VP2-1/8RP*VP2-1/4RP*
1 VP29 Valve Arm, Poly • • • •
2 VP21 Valve Body, Poly • • •
3 VM106 Lock Pin, Poly • • •
4 VP28 Plunger, Poly/Rubber • • •
•
5 VP24 1/8” Diameter Orifice, Poly ••
5 VP26 1/4” Diameter Orifice, Poly ••
6 VP112 5/8” O-Ring x .103, Rubber • • • •
7VP117 3/4” NPT Base, Brass •
7 VP118 1/2” NPT Base, Brass
8 VP15 Assembly Nut, Poly •
9 VP115 Adjust Screw, Poly
10 VA225P 1 1/8" Float Arm, Poly •
•
C
M
Y
CM
MY
CY
CMY
K
VP2.pdf 1 11/29/2016 4:21:43 PM
10 WC726P 3 5/8" Float Arm, Poly
11 OP321 Float Poly 3 1/2" x 4 1/2" x 3" ••
•
•
••
•
Adjust screw, Float Arms, Float (none are included as part of the valve)
*You can purchase individual parts or you can purtchase the 2 repair kits which include
Ref. nos. 1 through 6. These kits do not include the brass base or the assembly nut.
Valve for
MC, MJ, MK
Valve for
MH Repair Repair
9
10
8
7
6
5
4
2
3
1
11
VP226 VALVE
VA225P FLOAT ARM
OP321 FLOAT
8
7
1
2
4
6
5
3
10 9
11
VP221 VALVE
WC726P FLOAT ARM
OP321 FLOAT
To maintain float height under high water pressure,
consider adding a star washer (not included) between
the valve arm and the float arm.

7
Table 1
VP2 VALVE FLOW RATES
Gallons Per Minute
PSI
VP226
VP24 - 1/8” (.125) Orifice
VP221
VP26 - 1/4” (.25) Orifice
25 1.1 4.2
40 1.3 7.5
60 1.6 9.2
80 1.9 9.7
ELECTRIC HEATING UNIT OPERATION
Model 77 heater carries an 18 month non prorated warranty. Heaters will be repaired or replaced
at no charge during the warranty period provided they have been registered by sending the card
which accompanies each waterer to the manufacturer. If you like, call our sales and service desk
at 800-553-1791 to discuss your situation. We may ask you to either return a defective heater or to
field destroy it. Alternatively, return the heater in question with an explanatory note. If the heater is
returned and shows signs of abuse, it will be repaired or replaced at the customer’s expense. The
manufacturer reserves the right to either repair a unit or replace it with a new unit. When the warranty
period has expired or if a unit is returned that has not been registered for warranty, it will be repaired
or replaced and the customer charged accordingly.
All other parts (including valve, float and valve parts) of our heated waterers are also covered by an
18 month warranty from the date of purchase for defects due to materials and workmanship. Return
any components to: 609 Main Street, P.O. Box 2000, Houghton, Iowa 52631. USA.
WARRANTY
ELECTRICALLY HEATED WATERERS AND ENERGY USE
Our waterers are insulated with polyurethane foam with an R value of 7.14 per inch. Our foam
contains no formaldehyde and is not attractive as a food source to vermin. Here is a check list of
items to consider in the management of your waterer with regard to energy use
1. Inspect condition of wiring and insulation before each heating season.
2. Check waterers daily for cleanliness and proper operation of the water valve and heater.
3. In warm seasons, make sure excess condenstion is not forming inside the lower cabinet of the
waterer which can contribute to the deterioration of insulation and the heater.
4. Counter the effects of cold winter winds with a wind barrier which will reduce energy
consumption.
5. Repair leaking valves to eliminate wasting water which has already been pumped and heated.
6. Caulk or close up openings in the waterer cabinet especially around the foundation.
7. Make sure the electric service wires are of the proper size.
8. Make sure waterers are properly grounded to prevent leakage (as well as to ensure safety).
OPTIMAL WATER TEMPERATURE: Studies have shown that there is little, if any, variation in daily
water intake, feed intake, daily gain or feed efficiency with different water temperatures. Heating
the water above say 40 degrees F in the winter will increase costs but there is no evidence to sug-
gest improved animal performance. Animal water consumption is more dictated by ambient air
temperature than by the temperature of the drinking water.
Flow rates at discharge can vary depending on the diameter of the supply line, the distance water travels to the waterer,
variability in water pressure, the buildup of deposits inside the water supply line among other factors.

8
MC MJ MK MH
Trough Assembly MC168-1
(1 Stud for
Heater)
MA168-0
(No Stud)
MC168-0
(No Stud)
MH302SS
(No Stud)
Top Angle Assembly 1/4-20 x 3/4 MC170 MC170
Truss Screw Tough Corner OF196 OF196 OF196 MH30SS
Cover Drain Fitting, Rubber MC163 MC163 MC163 MF164
Plug F/ Trough, Rubber A203R A203R A203R OM5R
Valve Cover Assembly MC166 MA165 MC166 MH315
5/16 Hex Nut Brass
(to retain valve cover)
OF146 OF146 OF146 OF146
Access Door Assembly MC175 MJ313 MK311 WE539
Hardware for Door:
1/4” Turn Stud, SS OF196 OP77 OP77
1/4” Clip on Receptacle OP78 OP78
Stud Retainer OP79 OP79 WE343
LATCH ARM
Heater: 77 77 77 77
(Takes 2)
Heater Bracket
(Attaches Heater to Trough)
M77MB
Heater Standoff
(Attaches Heater to Cabinet)
None MK315 MH316 MH316
Washer for Valve MF197 MF197 MF197 OF627
Inlet Pipe Assembly
(Elbow & Pipe Nipple)
MC174 MK317 MK317 MF186
Flex Hose Assembly MC183 MC183 MC183 None
Hinge Rod MC162
1/8” x 3/4” Cotter Pin OF78
Mud Grate MC158
Trough Lid MC167
Trough Lid Hinge MC159
REPAIR PARTS
Valve and float part numbers are shown on page 6. Following are other parts available. There may
be some other parts available, such as cabinet panels, which are not listed. Ask our sales desk
about these.
This manual suits for next models
13
Table of contents