KlassKeeper –Installation, Operation, and Maintenance Manual 12
© Copyright 2013 CGC Group Inc.
Last Revised April 2020 Installation, Operation, and Maintenance Manual is Subject to Change without Notice.
Low Discharge Air Temperature
If at any point the discharge air temperature (TA) drops below 40°F, the compressors will be turned off,
the general alarm contact (K7) will be energized, a flashcode of 1 will be displayed, and the alarm output
(AN1) will produce 1 VDC.
Low Refrigerant Temperature
If at any point the refrigerant temperature (TR) drops below 35°F, the compressors will be turned off, the
general alarm contact (K7) will be energized, a flashcode of 2 will be displayed, and the alarm output (AN1)
will produce 2 VDC.
Low Water Temperature
If at any point the water temperature (TW) drops below 60°F, the compressors will be turned off, the
general alarm contact (K7) will be energized, a flashcode of 3 will be displayed, and the alarm output (AN1)
will produce 3 VDC.
High Water Temperature
If at any point the water temperature (TW) rises above 140°F, the compressors will be turned off, the
general alarm contact (K7) will be energized, a flashcode of 4 will be displayed, and the alarm output (AN1)
will produce 4 VDC.
Low Refrigerant Pressure
If the low pressure switch opens after the compressor has been running for three minutes, a low pressure
alarm will be activated, the compressor will be turned off, the general alarm contact (K7) will be energized,
a flashcode of 5 will be displayed, and the alarm output (AN1) will produce 5 VDC.
A low pressure alarm will also be activated if the low pressure switch opens without the compressor
running.
High Refrigerant Pressure
If the high pressure switch opens at any time, the compressors will be turned off, the general alarm
contact (K7) will be energized, a flashcode of 6 will be displayed, and the alarm output (AN1) will produce
6 VDC.
Heat Wheel Malfunction
During ERV operation, if the fresh air leaving temperature (FRSH-LAT) drops below 40°F, both the heat
wheel and ERV fan will be de-energized and an alarm will be activated. The general alarm contact (K7) will
be energized, a flashcode of 7 will be displayed, and the alarm output (AN1) will produce 7 VDC.
Condensate Overflow
If there is water accumulated in the drain an alarm will be activated. The general alarm contact (K7) will
be energized, a flashcode of 8 will be displayed, and the alarm output (AN1) will produce 8 VDC.
The fan should stop for 30 seconds to refill the condensate trap.
System Lockout
If there are three low pressure alarms or three high pressure alarms in a 24-hour period, the system will
go into a hard lockout.
If either the high pressure switch or the low pressure switch remains open for 10 minutes, the system will
also go into a hard lockout.