CABAC HNS220TD User manual

ADVANCED WALL TIMER SWITCH MANUAL
A: Distribution Pl, Seven Hills NSW 2147
Customer Care New Zealand P: 0800 966 969 F: 0088 6969 E: sales@cabac.co.nz W: cabac.co.nz
1
CP13944 Rev 1, 19 MARCH, 2014
1. FEATURES
• Push button timer with ON/OFF and ON/RESTART operations.
− Quick tap turns power ON/ OFF, or
− Sustained 2 seconds press restart the timer.
• Adjustable Timer Range from 10 seconds to 15 hours.
• Configurable blue LED indicator.
− Indicator ON or OFF when power ON, or
− Indicator ON or OFF when power OFF.
• Configurable Switch Mode.
− Power ON during timing (NO - Normally Open), or
− Power OFF during timing (NC - Normally Closed).
• Suitable for a wide range of load types, including motor loads up to 8A.
• Compatible with HPM and Clipsal style wall plates with push buttons provided for a perfect fit.
• Very low 80mW standby power.
• Remote switch compatible.
• Timer set to 30 minutes out of box.
2. OPERATING CONDITIONS
• Operating Voltage: 230 – 240V a.c. 50Hz
• Operating Temperature: 0 to +50 °C
• Compliance Standard: CISPR15, AS/NZS 3100
• Maximum Load: 10AX
• Timer Range: 10 seconds to 15 hours
• Timer Accuracy: ±0.5%
3. LOAD COMPATIBILITY
Incandescent ü
240V Halogen ü
Fluorescent Tube with electronic ballast ü
Fluorescent Tube with iron core ballast ü
Compact Fluorescent ü
Electronic Transformer ü
LED ü
Wirewound Transformer ü
Fan Motors ü
Heating Elements ü
Note: Operation at temperature, voltage or load outside of the above specifications may cause permanent
damage to the unit.
Note: This manual was correct at the time of manufacture. For the latest version of the manual and any technical or
safety updates refer to the website:- cabac.com.au, cabac.co.nz or scan the QR code with a mobile phone.
HNS220TD
OWNER’S MANUAL
Scan our QR code
with your phone to go
directly to our website
for technical information
3-WIRE
SUITABLE FOR FANS,
MOTORS OR IRON
CORE BALLASTS

ADVANCED WALL TIMER SWITCH MANUAL
A: Distribution Pl, Seven Hills NSW 2147
Customer Care New Zealand P: 0800 966 969 F: 0088 6969 E: sales@cabac.co.nz W: cabac.co.nz
2
CP13944 Rev 1, 19 MARCH, 2014
4. WIRING INSTRUCTIONS
Neutral
Load
Active
Rem
Neutral
Active
HNS220TD
Load
Remote
Switch(es)
4.1 REMOTE SWITCH (REM)
• The remote switch must be a normally open 240V momentary switch. Eg. HPM EM870K or CLIPSAL 681M20P.
• Remote wiring should not exceed 50m.
• Holding the remote switch for over 2 seconds will cause the HNS220TD to restart the timer.
5. OPERATING INSTRUCTIONS
ELECTRICAL SAFETY WARNING: Isolate the HNS220TD from the mains power supply before
setting the timer.
The HNS220TD is an Advanced Wall Timer which allows flexible configurable operation. The LED can be
configurable to be either ON or OFF during timer operation. The power to the load can be either ON or OFF
during timer operation.
With a Quick Tap of the button the LED will change indication, depending on LED switch setting and the power
to the load will either switch ON or OFF.
When the timer is in operation, the LED will blink every 5 seconds. During the last 10 seconds of operation the
LED will flash indicating imminent time out.
If there is a sustained 2 seconds press of the button the timer will restart. At any time when the timer is running
a Quick Tap will turn the timer OFF.
The HNS220TD is configured by adjusting the 8 DIP switches inside the unit to the settings required.
LOAD
OUTPUT
IND
LED
TIMER
RANGE
TIMER
SETTINGS
NO ON R1 R2 8 4 2 1
NC OFF OFF OFF OFF OFF OFF OFF
5.1 LOAD OUTPUT (POWER ON/ POWER OFF) SWITCH
The HNS220TD can be set so that the power is ON (Normally Open - NO) when the timer is running or set to
OFF (Normally Closed -NC) when the timer is running by setting the Load Output switch.
Load Output Switch Operating Mode
Normally Open (NO) Power ON during timer operation (Relay contact closed)
Normally Closed (NC) Power OFF during timer operation (Relay contact open)
5.2 LED INDICATOR SWITCH
The sense of the HNS220TD LED Indicator can be set to ON or OFF in timer mode based on the table below.
LED Indicator Switch LED Indicator Mode
ON Indicator ON when power ON. Indicator OFF when power OFF
OFF Indicator OFF when power ON. Indicator ON when power OFF

ADVANCED WALL TIMER SWITCH MANUAL
A: Distribution Pl, Seven Hills NSW 2147
Customer Care New Zealand P: 0800 966 969 F: 0088 6969 E: sales@cabac.co.nz W: cabac.co.nz
3
CP13944 Rev 1, 19 MARCH, 2014
5.3 SETTING THE TIMER
The Timer duration is set by configuring the Timer Range and Timer Settings switches.
• The Timer Range is determined by the positions of the Timer Range switches R1 and R2.
• The Timer Settings is determined by the sum of the values for each of the Timer Settings switches that are set
to ON (any combination of 8, 4, 2 and 1)
TIMER RANGE TIMER SETTINGS (8, 4, 2 and 1)
R1 R2 MULTIPLIER MIN TIME SETTING MAX TIME SETTING
OFF OFF 10 seconds 10 seconds 2.5 minutes
ON OFF 1 minute 1 minute 15 minutes
OFF ON 10 minutes 10 minutes 2.5 hours
ON ON 1 hour 1 hour 15 hour
The Timer duration is then calculated by the Timer Settings multiplied by the Timer Range.
For example, if 8,2 and 1 are ON, and the range R1 is OFF and R2 is ON, the timer duration will be
(8 + 2 + 1) x 10 minutes = 110 minutes ( 1 hour and 50 minutes )
5.4 APPLICATION EXAMPLE 1
10 minute timer, Power ON when timer is running, Indicator ON while power ON
• Set all switches to the OFF position
• Set the Load Output switch to the NO position to select the power ON during timer mode.
• Set the LED Indicator switch to the ON position to select the indicator on while power ON mode.
• Set the Timer Range to 1 minute ( 1 minute to 15 minutes possible duration ) switch R1 = ON, switch R2 = OFF
• Set the Timer Settings switches to add up to 10 ( 8 + 2 = 10 ), 10 x 1 minute = 10 minutes
LOAD
OUTPUT
IND
LED
TIMER
RANGE
TIMER
SETTINGS
NO ON R1 R2 8 4 2 1
NC OFF OFF OFF OFF OFF OFF OFF
5.5 APPLICATION EXAMPLE 2
7 hour timer, Power OFF when timer is running, Indicator ON while power OFF
• Set all switches to the OFF position
• Set the Load Output switch to the NC position to select the power OFF during timer mode.
• Set the LED Indicator switch to the OFF position to select the indicator OFF while power ON mode.
• Set the Timer Range to 1 hour with switch R1 = ON, switch R2 = ON
• Set the Timer Settings switches to add up to 7 ( 4 + 2 +1 = 7 ), 7 x 1 hour = 7 hours.
LOAD
OUTPUT
IND
LED
TIMER
RANGE
TIMER
SETTINGS
NO ON R1 R2 8 4 2 1
NC OFF OFF OFF OFF OFF OFF OFF

ADVANCED WALL TIMER SWITCH MANUAL
A: Distribution Pl, Seven Hills NSW 2147
Customer Care New Zealand P: 0800 966 969 F: 0088 6969 E: sales@cabac.co.nz W: cabac.co.nz
4
CP13944 Rev 1, 19 MARCH, 2014
5.6 ON/ RESTART OPERATION
When the Timer is running, holding the front push button of the HNS220TD for 2 seconds (LED will go off )
or remote switch for 2 seconds will restart the timer.
5.7 ON/ OFF OPERATION
The HNS220TD can be used as a simple ON/ OFF switch when all the Timer Settings switches are set to the
OFF position.
6. IMPORTANT SAFETY WARNINGS
6.1 LOAD REPLACEMENT
• It should be assumed that even when OFF, mains voltage will still be present at the load fitting. Mains
power must be disconnected at the circuit breaker before replacing faulty loads.
6.2 INSTALLATION
• The HNS220TD is to be installed as part of a fixed wire electrical installation. By law, such installations must
be made by an electrical contractor or similary qualified person. Mains power must be disconnected at
circuit breaker before installation of the wall timer. Avoid excessive force during installation.
• The recommended stripped wire length for wires used in the installation of the HNS220TD is 10mm.
6.3 CLEANING
• Clean only with damp cloth. Do not use abrasives or chemicals.
7. TROUBLESHOOTING
7.1 POWER TO LOAD FAILS TO TURN ON
• Ensure that the HNS220TD has power by checking the circuit breaker.
• Ensure the load is not damaged or broken.
• Check the front button or remote push buttton is not stuck ON.
• Check the Timer Range and Timer Settings switches to ensure correct timer duration is set.
7.2 POWER TO LOAD FAILS TO TURN OFF
• Check the power at the circuit breaker.
• Check the front button or remote push button is not stuck on.
• Check the correct Load Output Switch mode is selected.
• Check the Timer Range and Timer Settings switches to ensure correct timer duration is set.
7.3 POWER TO LOAD FAILS TO TIME OUT
• Check the HNS220TD is not set to ON/ OFF mode.
• Check the remote push button is not stuck on.
• Check the Timer Range and Timer Settings switches to ensure correct timer duration is set.
8. WARRANTY AND DISCLAIMER
CABAC warrant the product against manufacturing and material defect from the date of invoice to the
initial purchaser for a period of 12 months. During the warranty period CABAC will replace products that
proved to be defective where the product has been correctly installed and maintained and operated within
the specifications defined in the product data sheet and where the product is not subjected to mechanical
damage or chemical attack. The warranty is also conditional that the unit being installed by a licensed
electrical contractor. No other warranty is expressed or implied.
CABAC shall not be liable for any direct, indirect, incidental or consequential damages.
Note: This manual was correct at the time of manufacture. For the latest version of the manual and any technical or
safety updates refer to the website:- cabac.com.au, cabac.co.nz or scan the QR code with a mobile phone.