7
Condensate Drain Pipe Sizes
Refer to table 12 for the required sizes.
Table 12 – Drain Pipe Sizes
UNIT SIZE OUTSIDE DIAMETER
18K---54K 1(25.4)
Refrigerant Charge
The outdoor units can be matched with multiple indoor units, and
thus a different amount of charge might be required when matched
with the 40MKCB**F or 40MKQB**F units. Charge to
Sub--cooling Delta from Rating Plate Value as stated below.
Table 13 – Charge Requirements
SYSTEM
TYPE
NOMINAL
CAPACITY
kBTU/Hr
OUTDOOR UNIT INDOOR UNIT
CHARGE TO
SUB-- COOLING
DELTA FROM
RATING PLATE
VALUE
Cooling
Only
18 24AHA418A003 124ANS018000 40MKCB18F--- ---3 12
24 24AHA424A003 124ANS024000 40MKCB34F--- ---3 12
30 24AHA430A003 124ANS030000 40MKCB34F--- ---3 12
34 24AHA436A003/5/6 124ANS036000 40MKCB34F--- ---3 8
48 24AHA448A003/5/6 124ANS048000 40MKCB54F--- ---3 12
54 24AHA460A003/5/6 124ANS060000 40MKCB54F--- ---3 10
Heat
Pump
30 25HHA430A003 224ANS030000 40MKQB36C--- --- 3 11
36 25HHA436A003/5/6 224ANS036000 40MKQB36C--- ---3 14
48 25HHA448A003/5/6 224ANS048000 40MKQB48C--- ---3 11
NOTE:The above additional charge is required amount for
line lengths up to 25 ft. (7.6 m). For line lengths exceeding 25 ft.
(7.6 m), an additional charge is required. Refer to the
Residential Long Line Guide.
Metering Device
The 40MKC(Q)*F unit uses a TXV. The outdoor unit uses a type
B accurator. The cooling metering device is installed with the
indoor unit, while the heating metering device is installed with the
outdoor unit. One metering device is required for the cooling only
system and two are required for the heat pump systems. Refer to
Table 14 for a breakdown of each unit’s metering devices.
Table 14 – Metering Devices
SYSTEM SIZE
kBTU/hr COOLING ONLY HEAT PUMPS
40MKCB**C 40MKQB**C 25HHA4/224ANS
18 TXV - -
24 TXV - -
30 TXV TXV 0.055"
34 TXV - -
48 TXV
54 TXV - -
36 -TXV 0.063"
48 TXV TXV 0.073"
POWER AND CONNECTING CABLES --
FIELD SUPPLIED
Recommended Connection Method for Power and
Communication Wiring (To minimize
communication wiring interference)
Power Wiring:
The main power is supplied to both the indoor and the outdoor units.
The field supplied connecting cable consists of three (3) wires. Two
wires are high voltage AC power and one is a ground wire. Consult
your local building codes and the NEC (National Electrical Code) or
CEC (Canadian Electrical Code) for special requirements. All wires
must be sized per NEC or CEC and local codes. Use Electrical Data
table MCA (minimum circuit amps) and MOCP (maximum over
current protection) to correctly size the wires and the disconnect fuse
or breakers respectively. Per caution note, only copper conductors with
a minimum 300 volt rating and 2/64--inch thick insulation must be
used.
Communication Wiring:
A separate shielded Stranded copper conductor only, with a 600
volt rating and double insulated copper wire, must be used as the
communication wire from the outdoor unit to the indoor unit.
To minimize voltage drop of the communication wire, use the wire
size and maximum lengths shown in Table 15.
Table 15 – Maximum Wire Lengths
WIRE SIZE LENGTH ft. (m)
18AWG 50 ft. (15 m)
16AWG 50 ft. (15 m) to 100 ft. (30 m)
13AWG 100 ft. (30 m) to 200 ft. (60 m)
EQUIPMENT DAMAGE HAZARD
Failure to follow the following caution may result in
equipment damage or improper operation.
Wires should be sized based on NEC and local codes.
Use copper conductors only with a 600 volt rating and double
insulated copper wire.
CAUTION
!
USER INTERFACE
The indoor unit is supplied with a wireless remote control to
operate the unit (an Owner’s Manual is supplied with the unit). The
following accessories are available.
SWall mounted control
OPERATING RANGE
Ensure that the system operates within the application guidelines
shown in the following tables.
Table 16 – Cooling Operating Range
Outdoor
Unit
MAXIMUM MINIMUM
DB °F (°C) WB °F (°C) DB °F (°C) WB °F (°C)
125 (51.7) -55 (12.8) -
Indoor Unit 90 (32) -64 (18) -
Table 17 – Heating Operating Range
Outdoor
Unit
MAXIMUM MINIMUM
DB °F (°C) WB °F (°C) DB °F (°C) WB °F (°C)
75 (23.9) 67 (19.4) 17 (-8.3) -
Indoor Unit 80 (27) 32 (0) -
ACCESSORIES
An extensive list of field installed accessories is available for both
indoor and outdoor units. Identify what accessories, if any, are
required for the application at hand and consult the separate
installation instructions for the accessories. Some of the
accessories, especially on the indoor units, can be installed much
easier if planned ahead.