CAC / BDP RG57F3(B) User manual

Service Manual
RG57F3(B)/BGEFU1
Wireless Remote Controller
TABLE OF CONTENTS PAGE
INTRODUCTION 1...................................
HANDLING THE REMOTE CONTROLLER 2.............
STANDARD FUNCTION BUTTONS 3...................
ACCESSING THE SERVICE FUNCTIONS 4...............
REMOTE CONTROLLER SERVICE FUNCTIONS 4........
Auto−Start Function (F1) 4.............................
Heating Temperature Compensation (F2) 4................
Anti−Cold Air Function (F3) 5..........................
Indoor Fan Motor Speed Control after Set Temperature is
Reached (F4) 5......................................
Louver Angle Memory Function (F5). 6...................
Heating Only or Cooling and Heating Setting (F6). 6.........
Cooling Temperature Compensation (F7). 6................
Refrigerant Leakage Detection (F8). 6....................
Cleaning Filter Reminder (F9). 6........................
Filter Replacement Reminder (E1). 7.....................
Lowest Temperature Setting (E2). 7......................
Highest Temperature Setting (E3). 7......................
Special Anti−Cold Air Function Setting (E4). 7.............
Priority Setting of Heating or Cooling (only on Multi−Zone
Systems) (E5). 7.....................................
Network Address Setting (E6). 7........................
Capacity Code Selection (E7). 7.........................
Twins Setting (E8). 7.................................
Static Pressure Setting (E9). 7...........................
DEFAULT VALUES OF INDOOR UNITS 8................
POINT CHECK FUNCTION 9...........................
INTRODUCTION
This service manual provides the necessary information to use the
service functions on the RG57 wireless remote controller. Use the
Table of Contents to locate a desired topic.
Fig. 1 – Remote Controller

2
HANDLING THE REMOTE
CONTROLLER
Remote Controller Location
Keep the remote controller within a distance where its signals can
reach the indoor unit’s receiver (not to exceed a distance of 26 ft.
(8m)).
8m
ON/OFF
TEMP
FP
TIMER
ON
TIMER
OFF
MODE
FAN/SLC
SLEEPSWING
DIRECT
TURBOCLEANLED
FOLLOW
Fig. 2 – Remote Controller Location
SThe air conditioner will not operate if curtains, doors or
other materials block the signals from the remote controller
to the indoor unit.
SPrevent any liquid from falling on or into the remote
controller. Do not expose the remote controller to direct
sunlight or heat.
SIf the infrared signal receiver on the indoor unit is exposed
to direct sunlight, the air conditioner may not function as
designed. Use curtains to prevent sunlight from shining
directlyon the air conditioner.
SIf other electrical appliances respond to the remote
controller, either move the appliances or consult your local
dealer.
!CAUTION
Replacing Batteries
The remote controller uses two alkaline dry batteries (AAA).
1. Slide the battery compartment cover off, according to the
arrow direction, then replace the old batteries with new
batteries.
2. Insert the new batteries. Ensure the batteries are installed
correctly, based on their (+) and (−) polarities.
3. Slide the battery compartment cover back into position.
NOTE:
SDo not mix old and new batteries or batteries of different
types.
SDo not leave the batteries in the remote controller if the
remote is not going to be used for 2 or 3 months.
SDispose old batteries in the appropriate recycle bins.
Fig. 3 – Replacing batteries
Remote Controller Specification
Table 1—Remote Controller Specification
Model RG57F3(B)/BGFEU1
Rated Voltage 3.0V (Dry batteries AAA)
Signal Receiving Range 26 ft. (8m)
Environment 23_F (-5_C) ~ 140_F (60_C)

3
STANDARD FUNCTION BUTTONS
Before you use your new system, familiarize yourself with the remote controller. The following is a brief introduction of the remote controller.
FP
Activate/Disable freeze
protection function
ON/OFF
Turns the unit on or off
MODE
Scrolls through operation
modes as follows:
AUT O
COOL
DR Y
HEA T
FAN
FAN/SLC
Selects fan speeds in the
following order:
AUT O LOW
MED
HIGH
SLEEP
Saves energy during
Hold down this button for
2 seconds to activate the
Silence function.
sleeping hours
TURBO
Enables unit to reach
preset temperature in
shortest possible time
TEMP
Increases temperature in
O
1 F (1
°C)
increments
Max. temperature is
O
86 F
TEMP
Decreases temperature in
O
1F(1
°C) increments
Min. temperature is
O
62 F
TIMER ON
Sets timer to turn unit on
TIMER OFF
Sets timer to turn unit off
SWING/DIRECT
Starts and stops up-down
airflow louver movement
LED
Turns indoor unit s LED display on and off.
,
FOLLOW ME
Temperature sensing
and room temperature
display button
SELF CLEAN
Starts and stops
self clean feature
ON/OFF
TEMP
FP
TIMER
ON
TIMER
OFF
MODE
FAN/SLC
SLEEP
TURBO
SWING
DIRECT
CLEAN LED
FOLLOW
If you are sensitive to light when you go to
sleep, you can press the LED button to turn
off the LED display on the indoor unit. Press
the button again to turn it back on
NOTE: Press and hold
and buttons
together for 3 seconds to
alternate the temperature
display between the
OO
C & F scale
Fig. 4 – Remote Controller

4
ACCESSING THE SERVICE
FUNCTIONS
In order to access the service functions, after installing the batteries,
during the first 30 seconds, press and hold MODE, FAN, and
TIME ON together for 5 seconds. The remote controller resets
and the LCD window displays “F1”. Use the service functions
(F1) menu to configure the remote controller’s functions to
personalizethe unit’s use.
ON/OFF
TEMP
FP
TIMER
ON
TIMER
OFF
MODE
FAN/SLC
SLEEP SWI NG
DIRECT
TURBO CLEAN LED
FOLLOW
Fig. 5 – Remote Controller
IMPORTANT: The remote controller is enabled within 10
minutes after the indoor unit is powered on, and the indoor
unit must be turned off.
ON/OFF
POWER OFF: Press to turn off the unit
Fig. 6 – Power Off
MODE
MODE: Use to modify the selected function.
Press MODE to enter the parameter setting
interface, and the selected parameter indicator
will flash. Use TEMP ▲ and ▼to modify the
parameter or select another parameter in
conjunction with FAN and TIMER OFF.
Fig. 7 – Mode
TEMP
TEMP ▲ and ▼: Use to select fuctions or
adjust parameters. On the parameter
unadjustable interface, press ▲ and ▼to
select the specified function in a range of
F1~F9 and E1~E9. Next, press MODE to
enter the parameter modifying interface and
the relevant parameter flashes. Press
▲ and ▼to adjust the parameter.
Fig. 8 – Temp
TIMER ON
TIMER ON: Press to confirm the setting parameter
and transmit the signal to the unit.
Fig. 9 – Timer ON
TIMER OFF
FAN & TIMER: On the parameter setting
interface, press FAN and TIMER OFF to
select the parameter to modify.
FAN
Fig. 10 – Fan and Timer
LOCK: Press and hold SLEEP and DIRECT for
2 seconds, all the indoor unit’s current settings
are locked in and the remote controller will not
accept any operation other than the LOCK
operation.
SLEEP
DIRECT
Fig. 11 – Lock
REMOTE CONTROLLER SERVICE
FUNCTIONS
NOTE: The indoor unit beeps for 2 seconds indicating the
function has been successfully set.
Auto−Start Function (F1)
In case of a sudden power failure, the module memorizes the
setting conditions before the power failure. The unit resumes the
previous operation setting automatically after 3 minutes when the
power returns. In order to enable/disable this function:
1. Press ▲ and ▼to select “F1”.
Fig. 12 – Select F1
2. Press MODE. Next, press ▲ and ▼to select “ON” or
“OFF”.
MODE
Fig. 13 – Select On or Off
3. Press TIMER ON and the Auto−start function setting is
complete.
TIMER ON
Fig. 14 – TIMER ON
Heating Temperature Compensation (F2)
Defines the adjustment for the thermal stratification in the room
and how the indoor unit is sensing the space. To adjust the
temperaturecompensation, in Celsius only:
NOTE: The temperature compensation in Celsius regardless of the
units used.
1. Press ▲ and ▼ to select “F2”.
Fig. 15 – Select F2
2. Press MODE. Next, press ▲ and ▼to select the parameter
(range: −6_C ~ 6_C).
MODE
-
---
--
.... ....
....
....
Fig. 16 – Select the parameter
3. Press TIMER ON to confirm.
TIMER ON
Fig. 17 – Timer On
NOTE: The recommended setting is 0_C. The adjustment should
not be more than 2_C.

5
Anti−Cold Air Function (F3)
A) Intelligent Anti−Cold Air Function
NOTE: The intelligent anti−cold air parameter changes with the
room temperature. Once the room temperature rises, the anti−cold
air temperature rises as well, which is designed to provide the user
with increased comfort. After the room temperature decreases, the
anti−cold temperature decreases as well, which is designed to
improve fan speed and result in a faster heating operation.
NOTE: No setting adjustment recommended.
1. Press ▲ and ▼to select “F3”.
Fig. 18 – Select F3
2. Press MODE. Press FAN to select the parameter. Next,
press ▲ and ▼to select 1.
Flashing
MODE
FAN/ SL C
Fig. 19 – Select 1
3. Press TIMER OFF to adjust the parameter. The parameter
continues to flash. Next, press ▲ and ▼to adjust the
parameter (range: 63_F (17_C) ~ 70_F(21_C)).
Flashing
TIMER OFF
Fig. 20 – TIMER OFF
4. Press TIMER ON to confirm.
TIMER ON
Fig. 21 – TIMER ON
B) General Anti−Cold Air Function Setting (Cold Blow
Prevention Function)
The general anti−cold air parameter is set regardless of the room
temperature.
NOTE: No setting adjustment recommended.
1. Press ▲ and ▼ to select “F3”.
Fig. 22 – Select F3
2. Press MODE. Press FAN to select the parameter. Next,
press ▲ and ▼to select “2”.
Flashing
MODE
FAN/SLC
Fig. 23 – Select 2
3. Press TIMER OFF to adjust the parameter, which
continues to flash. Next, press ▲ and ▼to adjust the
parameter (range: 46_F(8_C) ~ 82_F(28_C)).
Flashing
TIMER OFF
Fig. 24 – Adjust the parameter
4. Press TIMER ON to confirm.
TIMER ON
Fig. 25 – TIMER ON
Indoor Fan Motor Speed Control after Set
Temperature is Reached (F4)
1. Press ▲ and ▼to select “F4”.
Fig. 26 – Select F4
2. Press MODE. Next, press ▲ and ▼to select “1”, “2”,
“3”, or “4”.
MODE
Indicates fan motor stopping
Indicates unit operating at lowest fan speed
Indicates unit operating at setting fan speed
Indicates terminal function
Fig. 27 – Select a number
3. Press TIMER ON to confirm.
TIMER ON
Fig. 28 – TIMER ON

6
Louver Angle Memory Function (F5)
1. Press ▲ and ▼to select “F5”.
Fig. 29 – Select F5
2. Press MODE. Next, press ▲ and ▼to select “1”, “2”, or
“3”.
MODE
Indicates memory function cancellation
Indicates the louver angle memory function is enabled
either by turning off or a power failure
Indicates the louver angle memory function is enabled
by turning off and disabled due to a power failure
Fig. 30 – Select a number
3. Press TIMER ON to confirm.
TIMER ON
Fig. 31 – TIMER ON
Heating Only or Cooling and Heating Setting (F6)
1. Press ▲ and ▼ to select “F6”.
Fig. 32 – Select F6
2. Press MODE. Next, press ▲ and ▼ to select “HH” or
“CH” (HH: Heating only − CH: Cooling and Heating).
MODE
Fig. 33 – Select HH or CH
3. Press TIMER ON to confirm.
TIMER ON
Fig. 34 – TIMER ON
Cooling Temperature Compensation (F7)
Defines the adjustment for the thermal stratification in the room
and how the indoor unit is sensing the space. To adjust the
temperaturecompensation, in Celsius only:
NOTE: Temperature compensation in Celsius regardless of the
units used.
1. Press ▲ and ▼to select “F7”.
Fig. 35 – Select F7
2. Press MODE. Next, press ▲ and ▼ to select the
parameter (range: −2_C ~ +2_C).
3. Press TIMER ON to confirm.
TIMER ON
Fig. 36 – TIMER ON
Refrigerant Leakage Detection (F8)
1. Press ▲ and ▼to select “F8”.
Fig. 37 – Select F8
2. Press MODE. Next, press ▲ and ▼ to select “ON” or
“OFF”.
3. Press TIMER ON to confirm.
TIMER ON
Fig. 38 – TIMER ON
Cleaning Filter Reminder (F9)
1. Press ▲ and ▼ to select “F9”.
Fig. 39 – Select F9
2. Press MODE. Next, press ▲ and ▼to select “ON” or
“OFF”.
3. Press TIMER ON to confirm.
TIMER ON
Fig. 40 – TIMER ON

7
Filter Replacement Reminder (E1)
1. Press ▲ and ▼to select “E1”.
Fig. 41 – Select E1
2. Press MODE. Next, press ▲ and ▼to select “ON” or
“OFF”.
3. Press TIMER ON to confirm.
TIMER ON
Fig. 42 – TIMER ON
Lowest Temperature Setting (E2)
1. Press ▲ and ▼to select “E2”.
Fig. 43 – Select E2
2. Press MODE. Next, press ▲ and ▼ to set the temperature
(range: 63_F(17_C) to 75_F(24_C)).
3. Press TIMER ON to confirm.
TIMER ON
Fig. 44 – TIMER ON
Highest Temperature Setting (E3)
1. Press ▲ and ▼ to select “E3”.
Fig. 45 – Select F3
2. Press MODE. Next, press ▲ and ▼ to set the temperature
(range: 77_F(25_C) to 86_F(30_C)).
3. Press TIMER ON to confirm.
TIMER ON
Fig. 46 – TIMER ON
Special Function Setting (E4)
Not available, used on future applications.
Priority Setting of Heating or Cooling (only on
Multi−Zone Systems (E5))
1. Press ▲ and ▼ to select “E5”.
:Heatingmodefirs
t
:coolingmodefirst
Fig. 47 – Select E5
2. Press MODE. Next, press ▲ and ▼to select “H” or “C”.
3. Press TIMER ON to confirm.
TIMER ON
Fig. 48 – TIMER ON
Network Address Setting (E6)
Not available, used on future applications.
Capacity Code Selection (E7)
Not available, used on future applications.
Twins Setting (E8)
Not available, used on future applications.
Static Pressure Setting (E9)
Available only on 40MBDQ Ducted Units.
1. Press ▲ and ▼ to select “E9”.
Fig. 49 – Select E9
2. Press MODE. Next, press ▲ and ▼to select the values
between 0 and 4.
3. Press TIMER ON to confirm.
TIMER ON
Fig. 50 – TIMER ON
NOTE: Depending on the model, some of the remote controller’s
functions may not function.

8
DEFAULT VALUES OF INDOOR UNITS
Table 2—Default Values of Indoor Units
Description Remote
Code High Wall Cassette Ducted Floor
Console
Auto-Start Function F1 ON ON ON ON
Heating Temperature Compensation F2 2C 6C 6C 0C
Anti-Cold Air Function F3 NORMAL NORMAL NORMAL NORMAL
Indoor Fan Motor Speed Control after Set Temperature is Reached F4 LOWEST SPEED SET SPEED SET SPEED SET SPEED
Louver Angle Memory Function F5 ON N/A N/A N/A
Heating Only or Cooling and Heating Setting F6 CH CH CH CH
Cooling Temperature Compensation F7 -2C -2C -2C -2C
Refrigerant Leakage Detection F8 ON ON ON ON
Cleaning Filter Reminder F9 OFF OFF OFF OFF
Filter Replacement Reminder E1 OFF OFF OFF OFF
Lowest Temperature Setting E2 17C 17C 17C 17C
Highest Temperature Setting E3 30C 30C 30C 30C
Special Anti-Cold Air Function Setting E4 N/A N/A N/A N/A
Priority Setting of Heating or Cooling (Multi-Zone Systems only) E5 H H H H
Network Address Setting E6 N/A N/A N/A N/A
Capacity Code Selection E7 N/A N/A N/A N/A
Twins Setting E8 N/A N/A N/A N/A
Static Pressure Setting E9 N/A N/A 0 N/A

9
POINT CHECK FUNCTION
Press LED on the remote controller three times and then press SWING three times within 10 seconds, the buzzer rings for 2 seconds and the
air conditioner enters the information enquiry status.
Next, press LED to search the information. Press SWING to search the remaining information. When the air conditioner enters the enquiry
information status, it displays the code name in 2 seconds (see Table 3).
Table 3—Point Check Function
Enquiry Information Displaying Code Meaning
T1 T1 T1 temp.
T2 T2 T2 temp.
T3 T3 T3 temp.
T4 T4 T4 temp.
T2B Tb T2B temp.
TP TP TP temp.
TH TH TH temp.
Targeted Frequency FT Targeted Frequency
Actual Frequency Fr Actual Frequency
Indoor fan speed IF Indoor fan speed
Outdoor fan speed OF Outdoor fan speed
EXV opening angle LA EXV opening angle
Compressor continuous running time CT Compressor continuous running time
Causes of compressor stop ST Causes of compressor stop
Reserve A0
Reserve A1
Reserve b0
Reserve b1
Reserve b2
Reserve b3
Reserve b4
Reserve b5
Reserve b6
Reserve dL
Reserve Ac
Reserve Uo
Reserve Td

10
When the air conditioner enters the enquiry information status, it displays the code value in the next 25 seconds after the display name appears
(see Table 4).
Table 4—Code Value
Enquiry Information Display Value Meaning Remark
T1,T2,T3, T4,T2B,TP, TH,
Targeted Frequency, Actual
Frequency
-1F,-1E, -1d,-1c, -1b,-1A -25,-24,-23,-22,-21,-20 1. The displaying temperature is
the actual value.
2. The temperature is Celsius no
matter what kind of remote
controller is used.
3. T1,T2,T3,T4,T2B display range:
77_F(-25_C)~ 158_F (70_C),
TP display range: -20~ 130.
4. Frequency display range:
0~159HZ.
5. If the actual value exceeds the
range, it displays the maximum
value or minimum value.
-19-99 -19-99
A0,A1...A9 100,101......109
b0,b1...b9 110,111....119
c0,c1....c9 120,121....129
d0,d1...d9 130,131....139
E0,E1...E9 140,141....149
F0,F1...F9 150,151....159
Indoor fan speed/Outdoor fan
speed
0 OFF
1,2,3,4 Low speed, Medium speed,
High speed, Turbo For some big capacity motors
14-FF
Actual fan speed = Display value
turns to decimal value and then
multiply by 10. The unit is RPM.
For some small capacity motors,
display value is from 14-FF
(hexadecimal), the corresponding
fan speed range is from
200-2550RPM.
EXV opening angle 0-FF
Actual EXV opening value =
Display value turns to decimal
value and then multiply by 2.
Compressor continuous running
time 0-FF 0-255 minutes
If the actual value exceeds the
range, it displays the maximum
value or minimum value.
Compressor stop causes 0-99 For a detailed meaning, please
consult with an engineer Decimal display
Reserve 0-FF
Reserve 0-FF
Reserve 0-FF
Reserve 0-FF
Reserve 0-FF
Reserve 0-FF
Reserve 0-FF
Reserve 0-FF
Reserve 0-FF
Reserve 0-FF
Reserve 0-FF
Reserve 0-FF
Reserve 0-FF