Cairox 010 LCD 2T User manual

010 LCD 2T
010 LCD 4T
WALL LCD
MB 010 2T
MB 010 4T
MB 010 E
IOM_005_00
IOM_011_00
EN
Installation manual

2

3
The pictograms in the next chapter provide the necessary
information for correct, safe use of the appliance in a rapid,
unmistakable way.
Symbols
U
User
Refers to pages containing instructions or information for
the user.
I
Installer
Refers to pages containing instructions or information for
the installer.
S
Service
Refers to pages containing instructions or information for
the CUSTOMER TECHNICAL ASSISTANCE SERVICE
installer.
Editorial pictograms
Safety pictograms
Warning
The operation described may cause physical harm if not
carried out in accordance with safety regulations.
Dangerous electrical current
Make personnel aware that the operation described may
lead to electrical shocks if not carried out in accordance
with safety regulations.
High temperature danger
Of safety regulations, the risk of burns caused by contact
with components with high temperatures.
Prohibition
Refers to prohibited actions.
EN

4
1.1 General warnings
- This instruction is an integral part of the booklet of
the appliance on which the kit is installed. Please consult
thisbookletforgeneralwarningsandfundamentalsafety
rules.
- This manual is designed only for the qualified
and authorised installation technician, who must be
sufficiently trained and in possession of all psycho-
physical requirements as per the law.
- All operations must be carried out with care and
according to best practices, and in compliance with
workplace safety regulations.
- After unpacking, check that the contents are intact
and that all parts are included. If not, contact the agent
who sold the appliance to you.
- It is forbidden to modify the safety or adjustment
deviceswithoutauthorisationfromandindicationsofthe
manufacturer.
- It is forbidden to dispose of, or leave in the reach of
children, the packaging materials which could become
a source of danger.
- Repairs or maintenance must be performed by the
Technical Assistance Service or by qualified personnel
in accordance with this manual. Do not modify or tamper
with the appliance as this could create dangerous
situations and the manufacturer will not be liable for any
damage caused.
GENERAL

5
3.2
3.1
A
D
E
C
H
I
L
B
G
M
Assembly
010 LCD 2T - MB 010 2T - 010 LCD 4T - MB 010 4T
Assembly, set-up and connection of on-board control panels
010 LCD 2T, MB 010 2T, 010 LCD 4T, MB 010 4T
The controllers have two independent clean contacts
for controlling a refrigerator unit, a boiler and a presence
input. The 2 tube versions have a 230V output to power
the summer and winter solenoid valve whereas the 4-tube
versions have two independent 230V outputs for controlling
a summer solenoid valve and a winter valve.
The 10 kΩ water temperature probe positioned in the
compartment on the battery regulations the minimum level
when heating (30°C) and the maximum level when cooling
(20°C).
The board also has a function when there is no water
probe, in such cases the fan stop thresholds are ignored.
Slide the control panel into its housing in the upper part
of the device and fix it with the two fixing screws (ref. A).
To install the connection box:
- open the box (ref. B);
- lock the lower tooth into its hole (ref. C) on the side of
the device;
- hook the upper part of the box to the side (ref. D);
- fix it with the two fixing screws (ref. E);
- connect the grounding cable to the fan coil body (ref. M)
using the fixing screws (the minimum force that must be
applied for tightening screws must be around 2N);
- connect the fast connector of the MOTOR to the other
on the board (ref. I) *;
- on the two GRID block terminals (ref. L) there is a bridge
that allows SLI and RSI versions to work without a
microswitch.
- For other versions, remove the bridge and connect the
twoterminalsoriginatingonthegrillsafetymicroswitch*;
- connect the water probe to the H2 connector on the
device.
Thewatertemperatureprobecontrolsthetemperature
insidethebatteriesand determineswhenthefanstarts
according to pre-set parameters (minimum operation
in winder and maximum in summer).** Check that
they are correctly inserted into the compartment on
the battery.
- Connect the electrics, tidy cables and fix them with
the three clevises supplied (ref. G);
- close the box with the 4 screws (ref. H);
- refit the vanity plate on the side of the unit;
- tighten the upper screws on the control panel;
- place the screw head covers in their housing on the
control panel;
* For versions with hydraulic connections on the right,
refer to the relevant paragraph
** The regulation also works without a water probe
connected
EN

6
A
C
B
N
EV1
N
EV2
BA
ON
D
C
H4 H2 AIR
COMM
ASCII
RTU
MOTOR
LN
GRIDGRIDCP
CHILLER BOILER
LED
5.2
5.3
There are two dip switches on the controller circuit board
for configuring unit operation as per requirements.
- The night-time heating operation logic is modified by
using dip switch C:
- in the ON position, the fan is always off, and heats the
room using radiation and natural convection, as with
traditional radiators; in the off position it operates as
a normal fan.
- By positioning dip switch B to ON, when cooling, the
fan operates at the minimum speed even after having
reached the set point, to allow for more uniform
operation of the temperature probe and to avoid
layering in the air. With the cursor in the OFF position,
the functions are cycled (4 minutes ON, 10 minutes
OFF).
On closing the contact connected to the CP input (ref. A)
the panel is placed in stand-by mode.
If the contact is open the unit is active, if the contact
is closed it is deactivated when a key is pressed the
symbol flashes.
The input cannot be connected in parallel to that of other
electronic boards (use separate contacts).
Set-up of auxiliary dip-switch functions B and C
CP presence contact input connection (only for 010 LCD 2T and 010 LCD 4T models)

7
B
C
D
A
A
C
B
AUTO
C
5.4
5.5
- To position the temperature probe (ref. A):
- pass the probe through the hole on the shoulder (ref. B)
- insert the probe into the lower hole (ref. C)
- fix the probe on the relevant hook (ref. D)
By regulating these settings, the system can select either
heatingorcoolingautomatically,excludingnormalmanual
selection. This setting is particularly suitable for 4-tube
versions.This regulation system can only be activated by a
qualified and authorised installer.To activate this function,
press the summer/winter key (ref. A) for 10 seconds until
both the cooling (ref. C) and heating (ref. B) symbols come
on together. To return to the cooling only or heating only
setting, press and hold the summer/winter key (ref. A) for
10 seconds until the cooling (ref. C) and heating (ref. B)
symbols switch off. Press the key again to select winter
mode. Check the heating symbol is working (ref. B) (on
when set point is higher than ambient temperature, both
are off when the set point is lower. Press the summer/
winter key once to select summer mode. Check the
cooling symbol is working (ref. B) (on when set point is
lower than ambient temperature, both are off when the set
point is higher). This selection is saved even if the power
is turned off.
Air temperature probe assembly (only for models 010 LCD 2T, 010 LCD 4T)
Cooling/Heating automatic settings (only for 4-tube units)
EN

8
5.6
010 LCD 2T, 010 LCD 4T
010 LCD 2T and 010 LCD 4T connections
H2* water temperature probe 10kΩ
H4* cold water temperature probe 10kΩ (only for
010 LCD 4T)
AIR air temperature probe 10kΩ
M1 DC inverter fan motor
S1 grill safety micro-switch
Y1 water solenoid valve (230V/ 50Hz 1A output
voltage)
Y2
cold water solenoid (010 LCD 4T only) or mobile
flap connection (010 LCD 2T only).
230V/ 50Hz 1A output voltage.
L-N
230V/50Hz electrical power supply
BO boiler consent output (free contact max 1A)
CH chiller consent output (free contact max 1A)
CP presence input sensor (if closed, the fan coil unit
is placed in standby).
HRS RS water probe (2kΩ) (010 LCD 2T only)
RS RS version cabling (010 LCD 2T only)
*If after switching the power on the board
detects the H2 probe, start-up occurs in normal
conditionswiththeminimumwatertemperature
when heating (30°C) and maximum when
cooling (20°C).
The board also has a function when there is no
probe, in such cases the fan stop minimum and
maximum thresholds are ignored.

9
H4
5.7
8mm0.2-1.5mm2
MB 010 2T, MB 010 4T
A
MB 010 2T and MB 010 4T connections
-AB+ serial connection for wall-mounted remote
control WALL LCD (respect AB polarity)
H2** hot water temperature probe 10kΩ
H4** cold water temperature probe 10kΩ (648 only)
M1 DC inverter fan motor
S1 grill safety micro-switch
Y1 hot water solenoid valve (230V/ 50Hz 1A output
voltage)
Y2
cold water solenoid valve (MB 010 4T) or mobile
flap (MB 010 2T).
(230V/ 50Hz 1A output voltage)
L-N
230V/50Hz electrical power supply
BO boiler consent output (free contact max 1A)
CH chiller consent output (free contact max 1A)
CP not used in this version
HRS RS water probe (2kΩ) (MB 010 2T only)
AIR Air probe optional (*)
RS RS version cabling (MB 010 2T only)
*Alternatively, connect the wall-mounted
controller WALL LCD to the air probe
** If after switching the power on the board
detects the H2 probe, start-up occurs in normal
conditionswiththeminimumwatertemperature
when heating (30°C) and maximum when
cooling (20°C).
The board also has a function when there is no
probe, in such cases the fan stop minimum and
maximum thresholds are ignored.
Rigid or flexible wires with a 0.2 to 1.5 mm² cross-section
(0.75 mm² if two wires are connected to the same
terminal block) can be inserted in the 4 spring-loaded
terminal blocks (ref. A) for connection of the wall-mounted
controller WALL LCD. If the wires have wire end ferrules
with a plastic collar, the maximum cross-section is 0.75
mm².
Strip 8 mm of the wire, then if the wire is rigid, you can
insert it easily whereas, if it is flexible, it is advisable to use
long nose pliers.
Push the wire completely in and check that it is anchored
by pulling it gently.
To disconnect the cables, press the
corresponding white indent (ref. A) with a
screwdriver and remove the conductor.
EN

10
6.1
B
A
A
The wall-mounted remote control WALL LCD is an
electronic thermostat (fitted with an optional temperature
probe which can be remotely installed in one of the fan
coils connected to it) with the possibility to control one
or more units (up to max. 30) fitted with an electronic
controller for remote control MB 010 2T or MB 010 4T.
- Install the wall-mounted remote control WALL LCD
away from doors and/or windows and from heat
sources (radiators, fan coils, hobs, direct sunlight), on
internal walls and around 1.5m from the floor.
The wall-mounted remote control is inside the pre-
assembled package, therefore prior to affixing to the wall,
the two parts should be separated by unhooking the two
protruding teeth on the rear (A).
Use the base of the controller (ref. B in diagram) to trace
the fixing points on to the wall (use two opposing holes).
Then proceed with the following operations:
- drill holes in the wall;
- pass the cables through the window on the base;
- fix the base of the controller to the wall using suitable
screws and wall plugs;
- make the electrical connections then close the
controller taking care not to crush the conducting
wires.
WALL LCD
Wall-mounted remote control panel assembly WALL LCD

11
8mm0.2-1.5mm2
6.2
C
A
Rigid or flexible wires with a 0.2 to 1.5 mm² cross-section
can be inserted in the spring-loaded terminal blocks for
the serial connection. If the wires have wire end ferrules
with a plastic collar, the maximum cross-section reduced
to 0.75 mm².
For correct and safe connection, carry out the following
operations:
- Strip back the wires by 8mm as shown below;
- if the cable is rigid the end of the wire can be inserted
easily, whereas with flexible cable it may be easier to
use a long pointed pair of pliers to insert correctly.
- Push the wire completely in and check that it is
anchored by pulling it gently.
- To disconnect the cables, press the corresponding
white indent (ref. C) with a screwdriver and remove
the conductor.
Spring-loaded terminal connections -AB+ and CP
6.3 CP occupancy contact input connection
On closing the contact connected to the CP input (ref.
A) the panels are placed into stand-by. If the contact is
open the units are active, if the contact is closed they are
deactivated when a key is pressed the symbol flashes.
- The input cannot be connected in parallel to that
of other electronic boards (use separate contacts).
EN

12
6.4
Connect the RS485 line of the wall-mounted remote control
to one or more (up ot a maximum of 30) devices fitted with
electronics for remote control MB 010 2T or MB 010 4T
using a suitable two-core cable for serial connections RS485
keeping the power supply cables separate.
- Chase out the wall in order to minimise the length of
the leads;
- complete the line with the supplied 120 Ω heating
element;
- do not make "star" connections;
- The RS485 cable connection is polarised, respect the
"A" and "B" indications on every periphery connected
(for connecting, it is preferable to use a shielded two-
core cable with a minimum thickness of 0.35 mm2);
- connect the + and - power terminals on the wall
mounted terminal block, 5V DC, to one of the boards
MB 010 2T or MB 010 4T, respecting polarity.
WALL LCD Connections


14
A
HI
D
E
C
G
B
F
L
7.1
7.2
7.3
When fitted on board the machine it allows for managing the
motor,with modulated speed; motorregulation canbemade
using an analogue 0-10V DC input with 25 kΩ impedance.
For board MB 010 E control outputs these impedance values
must be considered, especially when controlling more than
one unit in parallel.
It has a 230 V output to pilot the solenoid valve.
Slide the blanking panel into its housing in the upper part of
the device and fix it with the two fixing screws (ref. A).
To install the connection box:
- open the box (ref. B);
- lock the lower tooth into its hole (ref. C) on the side of
the device;
- hook the upper part of the box to the side (ref. D);
- fix it with the two fixing screws (ref. E);
- connect the grounding cable to the unit structure using
the fixing screws (the minimum force that must be
applied for tightening screws must be around 2N);
- on the two GRID block terminals (ref. I) there is a bridge
that allows SLI and RSI versions to work without a
microswitch.
- For other versions, remove the bridge and connect the
twoterminalsoriginatingonthegrillsafetymicroswitch;*
- connect the fast connector of the MOTOR to the other
on the board (ref. H);
- Connect the electrics, tidy cables and fix them with
the three clevises supplied
(ref. F)
;
- close the box with the 4 screws
(ref. G)
;
- refit the vanity plate on the side of the unit;
- tighten the upper screws on the blanking panel;
- place the screw head covers in their housing on the
blanking panel;
* For versions with hydraulic connections on the right,
refer to the relevant paragraph
MB 010 E
Assembly and fitting of fan control for remote control MB 010 E.
Assembly
LED signals
The LED (ref. L) is off is the input signal is less than 0.9V.
It turns on with values greater than 1V and indicates normal
operation.
• Flashesfrequentlyif the grillemicroswitch S1is activated
due to the filter cleaning operation
• 2 flashes + pause due to a motor alarm (e.g. blockage
caused by foreign objects, faulty rotation sensor).

15
Y2
OFF
0
10 V
INPUT
(V DC)
M1
110
Y1
1,1
MAX rpm
ON
0,9
MIN rpm
CARATTERISTICA DELLE USCITE /
OUTPUT FEATURE
7.4
7.5
make the electrical connections to a thermostat fit for use
according to the diagram
The 10V input, if the S1 input which the grill safety micro
switch is connected to is closed, activates solenoid valve Y1
and regulations fan revolutions.
The speed "ramp" provides for linear regulation from the
minimum value (400 rpm) to the maximum value (1,400 rpm)
for voltage values ≥ 1.1V÷10 V DC.
The motor is off when values are lower than 1V DC.
The Y1 solenoid valve is activated for power values > 1V
DC and switches off then the power drops below 0.9V
DC.
Connection diagram MB 010 E with 0-10V DC thermostats / signals
MB 010 E connections with 0-10V thermostats
L-N Electrical power supply 230V-50 Hz
10V Appliance piloting input 0÷10 V
Y1 water solenoid valve (230V/ 50Hz 1A output
voltage)
Y2 output for mobile suction panel servo (power
output 230 V/ 50Hz 1A)
RS RS version cabling
HRS water probe for RS 2 kΩ
M1
DC inverter fan motor
S1 safety micro-switch for grill
Input impedance 25 kΩ /
Input impedance 25 kΩ /
EN

IOM_011_00
This manual suits for next models
4
Table of contents
Popular Thermostat manuals by other brands

Vimar
Vimar SMART CLIMA 30440-02970 Series manual

Vaughn
Vaughn ETC101 installation manual

Sygonix
Sygonix Touch 2 operating instructions

Bticino
Bticino Smarther X8000W quick start guide

Honeywell
Honeywell Magic Stat MS3000 installation manual

ThermoTex
ThermoTex CoziStat Installation instructions & operating manual