MODBUS REGISTER FOR IOMB-02
Coils (0x) Function Range
0x0001 Digital output #1 Off or On
0x0002 Digital output #2 Off or On
Disc rete inputs (1x) Function Range
1x0003 Digital input #1 Off or On
1x0004 Digital input #2 Off or On
1x0005 Digital input #3 Off or On
1x0006 Digital input #4 Off or On
Input reg. (3x) Function Range
3x0009 Analog input #1 x100 (Volt) 0 to 1000
3x0010 Analog input #2 x100 (Volt) 0 to 1000
3x0 011 Analog input #3 x100 (Volt) 0 to 1000
3x0012 Analog input #4 x100 (Volt) 0 to 1000
3x0013 Analog input #1 (Ohms) 0 to 1300
3x0014 Analog input #2 (Ohms) 0 to 1300
3x0015 Analog input #3 (Ohms) 0 to 1300
3x0016 Analog input #4 (Ohms) 0 to 1300
3x0017 Analog input #1 x10 (°C) -500 to
+500
3x0018 Analog input #2 x10 (°C) -500 to
+500
3x0019 Analog input #3 x10 (°C) -500 to
+500
3x0020 Analog input #4 x10 (°C) -500 to
+500
Holding reg. (4x) Function
4x0001 Digital output #1 Range
4x0002 Digital output #2 0 or 1
4x0003 Digital input #1 0 or 1
4x0004 Digital input #2 0 or 1
4x0005 Digital input #3 0 or 1
4x0006 Digital input #4 0 or 1
4x0007 Analog output #1 x100 (Volt) /
PWM x10 (%)
0 or 1000
4x0008 Analog output #2 x100 (Volt) /
PWM x10 (%)
0 to 1000
4x0009 Analog input #1 x100 (Volt) 0 to 1000
4x0010 Analog input #2 x100 (Volt) 0 to 1000
4x0011 Analog input #3 x100 (Volt) 0 to 1000
4x0012 Analog input #4 x100 (Volt) 0 to 1000
4x0013 Analog input #1 (Ohms) 0 to 1000
4x0014 Analog input #2 (Ohms) 0 to 1300
4x0015 Analog input #3 (Ohms) 0 to 1300
4x0016 Analog input #4 (Ohms) 0 to 1300
4x0017 Analog input #1 x10 (°C) -500 to 500
4x0018 Analog input #2 x10 (°C) -500 to 500
4x0019 Analog input #3 x10 (°C) -500 to 500
4x0020 Analog input #4 x10 (°C) -500 to 500
4x0021 Digital output #1 default value *1 0 or 1
4x0022 Digital output #2 default value *1 0 or 1
4x0023 Analog output #1 default value
x100 (Volt) / PWM x10 (%)
*1 0 to 1000
4x0024 Analog output #2 default value
x100 (Volt) / PWM x10 (%)
*1 0 to 1000
4x0025 Timeout for activating default
values (4x0019-4x0024)
*2 0-600 sec
4x0026 Setting of temperature sen-
sor type, analog input 1:
0=Pt1000, 1=Ni1000LG
0 or 1
4x0027 Setting of temperature
sensor type, analog input 2:
0=Pt1000, 1=Ni1000LG
0 or 1
4x0028 Setting of temperature
sensor type, analog input 3:
0=Pt1000, 1=Ni1000LG
0 or 1
4x0029 Setting of temperature
sensor type, analog input 4:
0=Pt1000, 1=Ni1000LG
0 or 1
4x0030 Analog output type, analog
output 1: 0 = 0-10V, 1=PWM
0 or 1
4x0031 Analog output type, analog
output 2: 0 = 0-10V, 1=PWM
0 or 1
4x0032 AC power supply detected
0=DC, 1=AC
0 or 1
*1 Selectable default value that can be activated in the event of communica-
tion failure on the Modbus loop.
*2 For communication failures (Modbus) that have lasted longer than the
number of set seconds (1-600 sec), the adjustable default values for
registers 4x0019 to 4x0024 are activated. To turn off the function, select
0 seconds (factory setting).
MODBUS-COMMUNICATION
Reference Description
0x Read/Write Discrete Outputs or Coils
1x Read Discrete Inputs
3x Read Input Registers
4x Read/Write Output or Holding registers