CALECTRO IOMB-TCP/IP User manual

Calectro AB Phone: +46 31-69 53 00 info@calectro.com www.calectro.com
IOMB-TCP/IP INSTALLATION INSTRUCTION
ENGLISH
GATEWAY FOR I/O-MODULES. Fits IOMB-
02, IOMB-03 and IOMB-04.
TECHNICAL DATA
Supply voltage: From the I/O-
modules IOMB-02
IOMB-03/IOMB-04
Communication: TCP/IP
Connection: RJ45
Indications LED on PCB
- Yellow, ash: TCP/IP
communication
- Yellow, double ash: DHCP energising
via push button
- Green, xed: Operation
- Green, blink: Internal Modbus
communication
Ambient temperature: -20 till +50°C
Dimensions (WxHxD): 75x39x33 mm
USE
IOMB-TCP/IP is a gateway for IOMB-02, IOMB-
03 and IOMB-04 that permits communication
with the I/O modules via TCP/IP.
FUNCTION
The TCP/IP gateway communicates inter-
nally with the I/O module via modbus RTU and
externally via TCP/IP. In order for the factory-
set Modbus communication to work, all DIP
switches On the I/O module must be set to
OFF. You can change the Modbus communica-
tion settings in the web interface for the TCP/
IP gateway, in which case you must also adjust
the DIP switch settings in the I/O module.
The TCP/IP gateway has the capacity to com-
municate with one external device (e.g. OPC
server) at a time.
MOUNTING
The IOMB-TCP/IP is mounted using the 4 screws
and washers provided, onto the I/O modules IOMB-
02, IOMB-03 or IOMB-04.
By replacing the rubber gasket in the M20 screw in
the I / O module with the supplied multi-hole gasket,
a pre-contacted Cat5 / 6 can be used. See Figure 1.
Remove the termination jumper located on the I / O
module. Please note that the 10-pin strip fits correct-
ly during the assembling. See Figure 2.
INSTALLATION
The DIP switches (1–10) in the I/O module must be
in their OFF positions to enable internal communica-
tion between the I/O module and the TCP/IP gateway.
Instruction, connection to network:
1. Connect the TCP/IP module to the designated
location on IOMB-02, IOMB-03 or IOMB-04.
2. Fit the 4 accompanying washers and screws.
3. Energise the I/O module. The green and yellow
LEDs on the TCP/IP module light up.
4. Press the button to the right of the yellow LED and
hold it down until the yellow LED flashes twice.
The TCP/IP gateway is now set to receive an IP
address via DHCP.
5. Plug in the network cable.
6. To access the network settings, open a web
browser and search for host name: ”http://calec-
trobrige”. If you experience problems locating the
TCP/IP gateway, download and install the pro-
gram: “Microchip TCPIP Discoverer” available-
from Calectro’s website: http://www.calectro.se/
products/#!/programvaror/. This program looks
for all connected gateways that have a TCP/IP
circuit from Microchip and displays their assigned
IP addresses.
7. Log in to network settings with the user name:
“admin” and password: “admin”.
8. Click NETWORK SETTINGS to access the net-
work settings.
9. Under MODBUS SETTINGS you can manage
internal communication between the I/O module
and the TCP/IP gateway. You do not usually need
to adjust this. The default settings in MODBUS
SETTINGS correspond to the I/O module’s DIP
switch in the OFF position.
MAINTENANCE
IOMB-TCP/IP is maintenance-free.
© 2020.07.07 R1.0 Calectro AB HFE6046
EN
MODBUS-SETTINGS FOR I/O-MODUL
(DIP-SWITCH: 0 = OFF / 1 = ON)
Modbus ID DIP-switch
1,2,3,4,5 and 6
1000000
2100000
3010000
4110000
5001000
6101000
7011000
81110 00
9000100
10 100100
11 010100
12 110100
13 001100
14 101100
15 011100
16 11110 0
17 000010
18 100010
... ...
64 111111
Modbus Parity DIP- switch 7 and 8
None (2 stop bits) 00
None (1 stop bit) 11
Even (1 stop bit) 10
Odd (1 stop bit) 01
Modbus Baud rate DIP- switch 9 and 10
9600 00
19200 10
38400 01
57600 11
Reservation for changes and printing errors.
2
MODBUS REGISTER FOR IOMB-02
Coils (0x) Function Range
0x0001 Digital output #1 Off or On
0x0002 Digital output #2 Off or On
Disc rete inputs (1x) Function Range
1x0003 Digital input #1 Off or On
1x0004 Digital input #2 Off or On
1x0005 Digital input #3 Off or On
1x0006 Digital input #4 Off or On
Input reg. (3x) Function Range
3x0009 Analog input #1 x100 (Volt) 0 to 1000
3x0010 Analog input #2 x100 (Volt) 0 to 1000
3x0 011 Analog input #3 x100 (Volt) 0 to 1000
3x0012 Analog input #4 x100 (Volt) 0 to 1000
3x0013 Analog input #1 (Ohms) 0 to 1300
3x0014 Analog input #2 (Ohms) 0 to 1300
3x0015 Analog input #3 (Ohms) 0 to 1300
3x0016 Analog input #4 (Ohms) 0 to 1300
3x0017 Analog input #1 x10 (°C) -500 to
+500
3x0018 Analog input #2 x10 (°C) -500 to
+500
3x0019 Analog input #3 x10 (°C) -500 to
+500
3x0020 Analog input #4 x10 (°C) -500 to
+500
Holding reg. (4x) Function
4x0001 Digital output #1 Range
4x0002 Digital output #2 0 or 1
4x0003 Digital input #1 0 or 1
4x0004 Digital input #2 0 or 1
4x0005 Digital input #3 0 or 1
4x0006 Digital input #4 0 or 1
4x0007 Analog output #1 x100 (Volt) /
PWM x10 (%)
0 or 1000
4x0008 Analog output #2 x100 (Volt) /
PWM x10 (%)
0 to 1000
4x0009 Analog input #1 x100 (Volt) 0 to 1000
4x0010 Analog input #2 x100 (Volt) 0 to 1000
4x0011 Analog input #3 x100 (Volt) 0 to 1000
4x0012 Analog input #4 x100 (Volt) 0 to 1000
4x0013 Analog input #1 (Ohms) 0 to 1000
4x0014 Analog input #2 (Ohms) 0 to 1300
4x0015 Analog input #3 (Ohms) 0 to 1300
4x0016 Analog input #4 (Ohms) 0 to 1300
4x0017 Analog input #1 x10 (°C) -500 to 500
4x0018 Analog input #2 x10 (°C) -500 to 500
4x0019 Analog input #3 x10 (°C) -500 to 500
4x0020 Analog input #4 x10 (°C) -500 to 500
4x0021 Digital output #1 default value *1 0 or 1
4x0022 Digital output #2 default value *1 0 or 1
4x0023 Analog output #1 default value
x100 (Volt) / PWM x10 (%)
*1 0 to 1000
4x0024 Analog output #2 default value
x100 (Volt) / PWM x10 (%)
*1 0 to 1000
4x0025 Timeout for activating default
values (4x0019-4x0024)
*2 0-600 sec
4x0026 Setting of temperature sen-
sor type, analog input 1:
0=Pt1000, 1=Ni1000LG
0 or 1
4x0027 Setting of temperature
sensor type, analog input 2:
0=Pt1000, 1=Ni1000LG
0 or 1
4x0028 Setting of temperature
sensor type, analog input 3:
0=Pt1000, 1=Ni1000LG
0 or 1
4x0029 Setting of temperature
sensor type, analog input 4:
0=Pt1000, 1=Ni1000LG
0 or 1
4x0030 Analog output type, analog
output 1: 0 = 0-10V, 1=PWM
0 or 1
4x0031 Analog output type, analog
output 2: 0 = 0-10V, 1=PWM
0 or 1
4x0032 AC power supply detected
0=DC, 1=AC
0 or 1
*1 Selectable default value that can be activated in the event of communica-
tion failure on the Modbus loop.
*2 For communication failures (Modbus) that have lasted longer than the
number of set seconds (1-600 sec), the adjustable default values for
registers 4x0019 to 4x0024 are activated. To turn off the function, select
0 seconds (factory setting).
MODBUS-COMMUNICATION
Reference Description
0x Read/Write Discrete Outputs or Coils
1x Read Discrete Inputs
3x Read Input Registers
4x Read/Write Output or Holding registers
3
MODBUS REGISTER FOR IOMB-03
Coils (0x) Function Range
0x0001 Digital output #1 Off or On
0x0002 Digital output #2 Off or On
0x0003 Digital output #3 Off or On
Disc rete inputs (1x) Function Range
1x0004 Digital input #1 Off or On
1x0005 Digital input #2 Off or On
1x0006 Digital input #3 Off or On
Input reg. (3x) Function Range
3x0010 Analog input #1 x100 (Volt) 0 to 1000
3x0 011 Analog input #2 x100 (Volt) 0 to 1000
3x0012 Analog input #3 x100 (Volt) 0 to 1000
3x0013 Analog input #1 (Ohms) 0 to 1300
3x0014 Analog input #2 (Ohms) 0 to 1300
3x0015 Analog input #3 (Ohms) 0 to 1300
3x0016 Analog input #1 x10 (°C) -50 to +50
3x0017 Analog input #2 x10 (°C) -50 to +50
3x0018 Analog input #3 x10 (°C) -50 to +50
Holding reg. (4x) Function Range
4x0001 Digital output #1 0 or 1
4x0002 Digital output #2 0 or 1
4x0003 Digital output #3 0 or 1
4x0004 Digital input #1 0 or 1
4x0005 Digital input #2 0 or 1
4x0006 Digital input #3 0 or 1
4x0007 Analog output #1 x100 (Volt) 0 to 1000
4x0008 Analog output #2 x100 (Volt) 0 to 1000
4x0009 Analog output #3 x100 (Volt) 0 to 1000
4x0010 Analog input #1 x100 (Volt) 0 to 1000
4x0011 Analog input #2 x100 (Volt) 0 to 1000
4x0012 Analog input #3 x100 (Volt) 0 to 1000
4x0013 Analog input #1 (Ohms) 0 to 1300
4x0014 Analog input #2 (Ohms) 0 to 1300
4x0015 Analog input #3 (Ohms) 0 to 1300
4x0016 Analog input #1 x10 (°C) -500 to +500
4x0017 Analog input #2 x10 (°C) -500 to +500
4x0018 Analog input #3 x10 (°C) -500 to +500
4x0019 Digital output #1 default
value
*10 or 1
4x0020 Digital output #2 default
value
*10 or 1
4x0021 Digital output #3 default
value
*10 or 1
4x0022 Analog output #1 default
value x100 (Volt)
*10 to 1000
4x0023 Analog output #2 default
value x100 (Volt)
*10 to 1000
4x0024 Analog output #3 default
value X100 (Volt)
*10 to 1000
4x0025 Timeout for activating default
values (4x0019-4x0024)
*20-600 sec
4x0026 Setting of temperature
sensor type, analog input 1:
0=Pt1000, 1=Ni1000LG
0 or 1
4x0027 Setting of temperature
sensor type, analog input 2:
0=Pt1000, 1=Ni1000LG
0 or 1
4x0028 Setting of temperature
sensor type, analog input 3:
0=Pt1000, 1=Ni1000LG
0 or 1
*1 Selectable default value that can be activated in the event of communica-
tion failure on the Modbus loop.
*2 For communication failures (Modbus) that have lasted longer than the
number of set seconds (1-600 sec), the adjustable default values for
registers 4x0019 to 4x0024 are activated. To turn off the function, select
0 seconds (factory setting).
MODBUS-COMMUNICATION
Reference Description
0x Read/Write Discrete Outputs or Coils
1x Read Discrete Inputs
3x Read Input Registers
4x Read/Write Output or Holding registers
Calectro AB Phone: +46 31-69 53 00 info@calectro.com www.calectro.com
FIGURES
FIG. 1
FIG. 2
FIG. 3
FIG. 4
FIG. 5
FIG. 6
Termination-jumper
10-pin strip

This manual suits for next models

3

Popular Control Unit manuals by other brands

NARVI IR-IC1 Installation and operating instructions

NARVI

NARVI IR-IC1 Installation and operating instructions

WIDE Automation WALR 24-2A operating instructions

WIDE Automation

WIDE Automation WALR 24-2A operating instructions

Harman AMX HPX-AV102A-DP-R quick start guide

Harman

Harman AMX HPX-AV102A-DP-R quick start guide

Pepperl+Fuchs VU120 Brief instructions

Pepperl+Fuchs

Pepperl+Fuchs VU120 Brief instructions

Bose Sub1 manual

Bose

Bose Sub1 manual

GSS PADT 6400 Assembly instructions

GSS

GSS PADT 6400 Assembly instructions

Renishaw MCR20 User instruction

Renishaw

Renishaw MCR20 User instruction

National Instruments NI FlexRIO PXIe-7971R Getting started guide

National Instruments

National Instruments NI FlexRIO PXIe-7971R Getting started guide

Guinaz G3270 installation guide

Guinaz

Guinaz G3270 installation guide

Huawei UPS5000-E Series user manual

Huawei

Huawei UPS5000-E Series user manual

RCNTEC RPCM Series Quick install guide

RCNTEC

RCNTEC RPCM Series Quick install guide

BFT Sirio TN1 Installation and user manual

BFT

BFT Sirio TN1 Installation and user manual

V2 Easy3 manual

V2

V2 Easy3 manual

Thermo Technologies USDT2004 Installation and user guide

Thermo Technologies

Thermo Technologies USDT2004 Installation and user guide

Texas Instruments TPS65253 user guide

Texas Instruments

Texas Instruments TPS65253 user guide

GEM 613 Installation, operating and maintenance instructions

GEM

GEM 613 Installation, operating and maintenance instructions

Senect AQUACULTURE Series manual

Senect

Senect AQUACULTURE Series manual

Elektrogas VML Series Technical manual

Elektrogas

Elektrogas VML Series Technical manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.