Calix ODC-120 User manual

Calix ODC-120 Installation Guide
June 2005
#220-00050, Rev. 12

Copyright 2005, Emerson Network Power, Energy Systems, North America, Inc. All rights reserved.
Any unauthorized reproduction or transmission without the prior consent of Emerson Network Power,
Energy Systems, North America, Inc. is prohibited.
This document is the property of Emerson Network Power, Energy Systems, North America, Inc. and
contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use or disclosure of it without the written permission of
Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

Calix ODC-120 Installation Guide
Proprietary Information: Not for use or disclosure except by written agreement with Calix.
© 2005 Calix. All Rights Reserved.
i
TABLE OF CONTENTS
1. ABOUT THIS DOCUMENT 1
2. CABINET DESCRIPTION 1
2.1 Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2.2 Physical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.3 Standards Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.4 Cabinet dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.5 Cabinet Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3. OPENING AND CLOSING THE CABINET DOORS 5
3.1 Resetting The MESA®Intrusion Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
4. INSTALLATION CONSIDERATIONS 7
4.1 Site Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4.2 Concrete Foundation Pad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4.3 Form Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.4 Unpacking the Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4.5 Preparing the Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
4.6 Lifting the Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4.7 Placing the Cabinet on Foundation Pad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
4.8 Leveling the Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
5. CABLE INSTALLATION 22
6. AC POWER 24
6.1 Installing AC Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
6.2 Grounding Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
6.3 Turning Up AC Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
7. DC POWER 28
7.1 Installing Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
8. COPPER AND BROADBAND PROTECTION 31
9. SPLICE COMPARTMENTS 32
10. MAINTENANCE AND REPLACEMENT PARTS 33
10.1 Battery Chamber Cover, Filter Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
10.2 Heat Exchanger Fan Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
10.3 Accessories and Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37


Calix ODC-120 Installation Guide
Proprietary Information: Not for use or disclosure except by written agreement with Calix.
© 2004 Calix. All Rights Reserved.
ii
LIST OF FIGURES
Fig. 1 MESA®6 NxT / Calix ODC-120 Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Fig. 2 Cabinet Diagram with Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Fig. 3 Computer Shelf (shown open and closed) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Fig. 4 T-Handle Door Lock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Fig. 5 Wind Latch Secured . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Fig. 6 Disable Intrusion Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Fig. 7 Concrete Pad Layout Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Fig. 8 Power Transfer Pedestal Mounting Templates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Fig. 9 Cabinet Mounting Template with Power Transfer Switch Template . . . . . . . . . . . . . . . . . . . 10
Fig. 10 Foundation Pad Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Fig. 11 Position of Conduit in Template . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Fig. 12 Rubber Gasket Sections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Fig. 13 End Chamber Base Access Cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Fig. 14 Remove Splice Chamber Base Plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Fig. 15 Splice Chamber (Lower View) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Fig. 16 Slings Inserted in Eye Bolts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Fig. 17 Front Access Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Fig. 18 Pallet Mounting Bracket . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Fig. 19 Lowering Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Fig. 20 Anchor Bolt . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Fig. 21 Attaching the Alignment Bracket . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Fig. 22 Inserting the Cinch Bolt . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Fig. 23 Raising the Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Fig. 24 Inserting Shims . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Fig. 25 Attaching External Ground to Ground Bar in Splice Chamber . . . . . . . . . . . . . . . . . . . . . . . 23
Fig. 26 AC Load Center. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Fig. 27 AC Distribution Center . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Fig. 28 Grounding Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Fig. 29 Battery Module Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Fig. 30 Typical Battery String and Interconnecting Cable Placement . . . . . . . . . . . . . . . . . . . . . . . . 30
Fig. 31 Protection Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Fig. 32 Splice Compartment Pegboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Fig. 33 Filter Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Fig. 34 Removing Top Fan Cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Fig. 35 Removing Screws from Fan Mounting Plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Fig. 36 Disconnecting Fan Power Plug . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Fig. 37 Removing Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Fig. 38 Removing Internal Fan Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
Fig. 39 Removing Internal Fan Access Cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Fig. 40 Removing Internal Fan From Mounting Plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36


MESA®6 NXT / CALIX ODC-120
OUTDOOR CABINET
DESCRIPTION AND INSTALLATION
1
1. ABOUT THIS DOCUMENT
1.1 Purpose - This practice provides a description of Emerson Network Power’s MESA®(Modular
Electronic Seated Architecture) 6 NxT Outdoor Enclosure as well as installation instructions.
Note: Optional Battery Heater Pad kit must be ordered separately from the cabinet.
1.2 Reason for Reissue - Whenever this practice is reissued, the reason for reissue will be stated in
this paragraph.
1.3 Information Not Provided in this Practice - Refer to other local practices or building codes as
applicable for the correct methods, tools and materials to beused inperforming procedures not
specifically described in this document.
Note: The information contained in this practice is subject to change without notice and
may not be suitable for all applications.
2. CABINET DESCRIPTION
2.1 Application
2.1.1 The MESA®6 NxT / Calix ODC-120 is part of the MESA®line of Modular Electronic Sealed
Architecture cabinets. The MESA®NxT provides a flexible, economical housing within the
network infrastructure. The MESA®6 NxT / Calix ODC-120 cabinet is deployed in limited
size and remote outside plant applications. The cabinet offers a compact solution for housing
electronics, protection, distribution, and battery backup.
2.1.2 The MESA®6 NxT / Calix ODC-120 cabinet provides a thermally managed internal
environment where outside cooling air and batteries are totally isolated from the electronic
equipment.

2
Calix ODC-120 Installation Guide
Proprietary Information: Not for use or disclosure except by written agreement with Calix.
© 2005 Calix. All Rights Reserved.
2.2 Physical Specifications
2.2.1 The MESA®6 NxT / Calix ODC-120is a welded 1/8-in. thick aluminum structure protected with
a two tone multistage dry powder polyester paint finish for maximum durability and
performance.
2.2.2 The cabinet consists of an equipment chamber that houses the electronics, an AC power
chamber, a splice chamber, and a vented compartment containing six battery modules.
2.2.3 The cabinet has four lifting eyes at the top that allow the enclosure to be lifted into mounting
position using lifting equipment.
2.3 Standards Compliance
2.3.1 The MESA®6 NxT / Calix ODC-120 is designed to meet the following standards:
• Bellcore, GR-63-CORE, Network Equipment - Building System (NEBS) Requirements:
Physical Protection, Issue 1, October 1995.
• Bellcore, GR-487-CORE, Generic Requirements for Electronic Equipment Cabinets,
Issue 1, June 1996.
System meets Seismic, Zone 4 requirements.
• Bellcore, GR-1089-CORE, EMC and Electrical Safety Generic Criteria for Network
Communications Equipment, Issue 1 November 1997.
• Underwriters Laboratory, UL 50, and UL 1950
• Underwriters Laboratory, UL 67.
Fig. 1 : MESA®6 NxT / Calix ODC-120 Cabinet

3
Calix ODC-120 Installation Guide
Proprietary Information: Not for use or disclosure except by written agreement with Calix.
© 2005 Calix. All Rights Reserved.
2.4 Cabinet dimensions
•Height: 74.50" (189.38 cm) overthe highest part of the solar shield in the front of the unit.
The height with lifting eyes in place is an additional 2 inches.
•Depth: 46.498" (118.10 cm).
•Width: 116.846" (296.79 cm) over the heat exchanger vent.
•Weight: Approximately 4,300 lb. (1,950.45 kg) pounds, unconfigured.
2.5 Cabinet Features
2.5.1 Cabinet Access - The MESA®6 NxT / Calix ODC-120 has double front and rear
environmentally sealed doors to access the main chamber, and two environmentally sealed
doors on the end chambers.
All doors are equipped with a locking mechanism requiring a cylinder lock (customer
provided), and a security bolt.
A T-Handle tamper-proof wrench,5/16-inch hex/pin tool opens the Equipment, Power, and
Splice chamber security latches.
The doorshave intrusion alarm switches,and have self-locking wind latches to secure the door
open during installation or maintenance.
The equipment chamber doors have a pull-down computer shelf and document holder (Fig. 3)
and a Calix proprietary coffee cup holder.
116.846"
(296.79 cm) 46.498"
(118.10 cm)
50.866"
(129.20 cm)
74.56"
(189.38 cm)
Fig. 2 : Cabinet Diagram with Dimensions

4
Calix ODC-120 Installation Guide
Proprietary Information: Not for use or disclosure except by written agreement with Calix.
© 2005 Calix. All Rights Reserved.
2.5.2 Mounting options - The cabinet is designed to be pad mounted. A universal pad-mounting
template is offered as an option. Rubber pads will be provided to isolate the cabinet from the
concrete pad. The cabinet willbe lifted into place on the pad using the lifting eyes provided on
the top of the cabinet.
ALERT
Batteries are to be installed only after cabinet placement.
2.5.3 Equipment Rails - The equipment chamber is equipped with painted conductive steel rails that
can accommodate 19-in. (48.26 cm) rack-mount equipment. The equipment mounting rails
have tapped EIA spaced holes.
The rails are designed to accept standard 12-in. (30.48 cm) deep with 5-in. (12.7 cm) front
offset mounted equipment.
Each rail is bonded by contact through the cabinet chassis to the Master Ground Bar (MGB).
2.5.4 EnvironmentalControl - The cabinet is equipped with a heat exchanger climate control system.
The cabinet contains two heat exchangers, each capable of removing up to 2,700 Watts of heat
at 19oC.
• The heat exchanger fans are field replaceable.
2.5.5 Cable Entry - Cable entry is through four 4-in. (10.16 cm) inside diameter split-sleeve cable
cones, one 1/2-in. (1.27 cm) grommeted opening for grounding, one 1 1/2-in. (3.81 cm) AC
conduitknockout located in the protection chamber, and one 10-position ground bar located in
the end chamber.
2.5.6 Battery Reserve - The MESA®6 NxT / Calix ODC-120 has battery modules designed to accept
up to (6) strings of front post batteries.
2.5.7 Battery Compartment - The MESA®6 NxT / Calix ODC-120 cabinet has a ventilated battery
compartment equipped with six battery modules, to accommodate (6) stings of 100 Amp hour
Northstar batteries.
An optional fused thermostatically controlled battery heater pad kit can be factory installed to
protect batteries in colder environments.
Fig. 3 : Computer Shelf (shown open and closed)

5
Calix ODC-120 Installation Guide
Proprietary Information: Not for use or disclosure except by written agreement with Calix.
© 2005 Calix. All Rights Reserved.
2.5.8 Battery Disconnect Panel and Breakers - The cabinet is equipped with six 40 Amp DC
alarmed circuit breakers (one per string) within the battery compartment.
2.5.9 AC Load Center - The MESA®6 NxT / Calix ODC-120 cabinet is wired for 60Amp 120/240
Volt single phase 50/60 Hz systems. A Nationally Recognized Test Laboratory (NRTL)
certified 10-position power distribution panel contains:
• one 60A/240Vac main circuit breaker,
• one 60A/240Vac generator circuit breaker,
• one 30A/240Vac circuit breaker for the rectifier A,
• one 30A/240Vac circuit breaker for the rectifier B,
• one 15A/120Vac circuit breaker for the convenience outlet, and
• one 15A/120Vac circuit breaker provided for the battery heater pad.
3. OPENING AND CLOSING THE CABINET DOORS
3.0.1 Purpose - This section describes the locking mechanisms on the doors of the cabinet and
explains how to open and close the doors. Refer to this section whenever instructed to open or
close cabinet doors.
3.0.2 Lock Type - The MESA®cabinet door latches are equipped with a pad lockable tamper resistant
lock (shown in Fig. 4).
3.0.3 Opening a Door - Perform the following steps to open a door:
Step 1: If required, use a key to unlock the door according to local practices.
Step 1: Insert the tamper-resistant wrench into the cup sems hex bolt.
Step 2: Turn the bolt a few degrees counter clockwise to release the latch.
Step 3: Lift the latch to open the door. See Fig. 4.
PUSH DOWN
TO CLOSE
PADLOCKABLE
HASP 5/16" T-HANDLE
TYPE LATCH
EQUIPMENT CHAMBER DOOR LATCH
P96330_C
Fig. 4 : T-Handle Door Lock

6
Calix ODC-120 Installation Guide
Proprietary Information: Not for use or disclosure except by written agreement with Calix.
© 2005 Calix. All Rights Reserved.
Step 4: Pull the door open wide enough to secure the wind latch at the bottom or top of the
door. The wind latch is secured when the shoulder engages the hole and slot at the
end of the bar. (See Fig. 5.).
3.0.4 To close a door - Perform the following steps to close a door:
Step 1: Lift the slotted bar on the wind latch to release the shoulder from the hole and slot.
(See Fig. 4.).
Step 2: Close the door.
Step 3: While holding thedoor closed, lower the door latch into the lock bed.Lock the door.
(See Fig. 4.)
3.1 Resetting The MESA®Intrusion Alarm
3.1.1 Purpose - This section describes the intrusion alarm function of the MESA®cabinets and
explains how to reset (disable) the alarm while performing routine maintenance.
3.1.2 The MESA®cabinet is equipped with an intrusion
alarm in the equipment, power, and splice
chambers.
3.1.3 When a cabinet door is opened, the intrusion switch
will report an alarm.
3.1.4 Resetthealarmbypullingtheswitchplungeroutward
as shown in Fig. 6. When pulled, the switch
disables the alarm until such time as the switch is
reset manually or by closing the cabinet door.
Fig. 5 : Wind Latch Secured
Cabinet Door
Equipment
Chamber
Wind Latch
Fig. 6 : Disable Intrusion Alarm
Pull out
switch

7
Calix ODC-120 Installation Guide
Proprietary Information: Not for use or disclosure except by written agreement with Calix.
© 2005 Calix. All Rights Reserved.
4. INSTALLATION CONSIDERATIONS
4.1 Site Selection
4.1.1 Consider the following when deciding on the location for the MESA®6 NxT / Calix ODC-120
cabinet:
• Before construction begins, obtain the rights-of-way from landowners, and other permits
or approvals from public authorities. Place MESA®6 NxT / Calix ODC-120 cabinets in
servitudes, on dedicated (recorded) easements, or on property owned by the company.
Avoid any unrecorded easements. If the cabinet is used in a rooftop application, additional
permits may apply.
• Use public safety road and street rights-of-way only when there is enough space to place
the closure and provide safe working conditions. The cabinet should be easily accessible
with adequate parking to ensure safety for people and vehicles. Place the cabinet where it
will not create a visual or physical obstruction to either vehicles or pedestrians.
• Select locations that will minimize accidental or intentional vandalism. Consider the use
of protective posts when the cabinet is located near parking areas where vehicles could
back into the cabinet.
• Accessibility: Place the cabinet at least 42 inches (106.68 cm) away from any obstruction,
fence, hedge, etc.
• If an area is subject to frost, choose a site free of heaving.
• Do not place the cabinet in ditches or areas subject flooding. Always locate the MESA®
cabinet on a site above the 100-year flood plain and not subject to water runoff or flash
flooding during heavy rains.
4.2 Concrete Foundation Pad
4.2.1 The MESA®6 NxT / Calix ODC-120 cabinet is installed on a concrete foundation pad, which is
either cast-in-place or precast. A power transfer pedestal may also be installed on the pad or
mounted on a pole near the cabinet. Fig. 7 shows the generalposition of the cabinet and power
transfer pedestal on the concrete pad. Use concrete only for the foundation pad. Do not use
substitute materials, such as reinforced plastics, since they lack the rigidity required for cabinet
placement.
• Use a MESA®6 NxT / Calix ODC-120 mounting template, part no. F1004239 (Fig. 9), to
orient the mounting bolts and access conduits in the pad. The template consists of
galvanized metal mounting plate with anchor bolts and support rails. A rubber gasket is
installed in two sections between the pad and the cabinet to prevent corrosion. If installing
a JuiceBox™ or other power transfer pedestal from Emerson Network Power on the pad,
use a separate template (Fig. 8).
• Order the power transfer template separately at the same time the engineering work order
is issued. The template(s) are ordered from Emerson Network Power Customer Service at
(630) 579-5000.

8
Calix ODC-120 Installation Guide
Proprietary Information: Not for use or disclosure except by written agreement with Calix.
© 2005 Calix. All Rights Reserved.
• For excavated pad applications, excavate a hole for the pad and cable conduits in
accordance with the engineering work prints, generally to a depth of 30 inches (76.2 cm)
for standard applications and 60 inches (152.4 cm) for areas where there is heavy frost.
• Use a minimum of six inches (15.24 cm) of sand or gravel as a base for thefoundation pad.
This will level the location to accept the pad.
• Use a high-early strength concrete mix so the cabinet may be placed three days following
concrete pouring. Coarse aggregate used in the concrete shall be graded from 3/4-inch (1.9
cm) to No. 4 only.
• Fig. 10 shows the arrangement of the reinforcing mesh and the template in the form prior
to pouring concrete (without a power transfer pedestal).
• Power transfer pedestals may be mounted to the same pad as the MESA®6 NxT / Calix
ODC-120 cabinet, mounted to a separate pad, or mounted to a pole. Install the power
transfer pedestals according to the recommendations provided by the manufacturer. If
using a power transfer pedestal mounted to the pad, before pouringthe concrete, install the
template for the power pedestal into the main MESA®pad, located as shown in Fig. 7 &
Fig. 8.
• When using a pole-mounted power transfer switch, route the
1 3/4inch (4.45 cm) electrical conduit from the AC end chamber to a point beyond the pad
near the pole location.
MESA 6 NxT
/ Calix ODC-120
40"
(101.6 cm) 42.5"
(107.95 cm)
40"
(101.6 cm)
42.5"
(107.95 cm)
POWER CHAMBER
SPLICE CHAMBER
POWER
PEDESTAL
12"
(30.48 cm)
SEE
NOTE
46.498"
(118.10 cm)
131"
(332.74 cm)
39.5"
(100.33 cm)
116.846"
(296.79 cm)
194.4"
(493.78 cm)
39.5"
(100.33 cm)
Fig. 7 : Concrete Pad Layout Diagram
NOTE: 22" (55.88 cm) for Emerson Network Power Transfer pedestal.
Recommended circumference of pad is 6" (15.24 cm) beyond cabinet with doors open.

9
Calix ODC-120 Installation Guide
Proprietary Information: Not for use or disclosure except by written agreement with Calix.
© 2005 Calix. All Rights Reserved.
4.3 Form Preparation
4.3.1 If the soil is not firm, compact it. For excavated pad applications, clear an area for the pad and
cable conduits in accordance with the engineering work prints. For a typical installation,
excavate the foundation hole to a depth of 12 to 16 inches (30.48 to 40.64 cm).
4.3.2 Construct a level base for the pad, using a minimum of six inches (15.2 cm) of sand or gravel.
The pad should be level to within 1/4-inch (6 mm) over the entire length and width.
4.3.3 Dig a trench to the area where the cable and electrical conduit will rise into the MESA®6 NxT
/ Calix ODC-120 cabinet (Fig. 10). Excavate the trenches to a depth of 30 inches (76.2 cm) for
a standard installation, and 60 inches (152.4 cm) for areas where there is heavy frost.
— If using a separate power transfer pedestal, dig a trench for the electrical conduit
going from the cabinet to the power transfer pedestal.
— If using a pole-mounted AC source, dig a trench for the electrical conduit from the
cabinet to the pole.
FRONTSIDE
OFCABINET
5.00"
(12.7 cm)
19.63" REF
(49.66 cm)
18.00" REF
(45.72 cm)
5.88"
(14.94 cm)
21.50" REF
(54.61 cm)
24.76" REF
(62.89 cm)
1.00" REF
(2.54 cm)
6.63" REF
(26.52 cm)
9.89" REF
(25.12 cm)
FRONTSIDE
OFCABINET
6.25"
15.88 cm)
19.87" REF
(50.47 cm)
18.00" REF
(45.72 cm)
7.10"
(18.03 cm)
21.50" REF
(54.61 cm)
10.44" REF
(26.51 cm)
13.70" REF
(34.79 cm)
1.00" REF
(2.54 cm)
24.76" REF
(62.89 cm)
Fig. 8 : Power Transfer Pedestal Mounting Templates
JuiceBox

10
Calix ODC-120 Installation Guide
Proprietary Information: Not for use or disclosure except by written agreement with Calix.
© 2005 Calix. All Rights Reserved.
Fig. 9 : Cabinet Mounting Template with Power Transfer Switch Template

11
Calix ODC-120 Installation Guide
Proprietary Information: Not for use or disclosure except by written agreement with Calix.
© 2005 Calix. All Rights Reserved.
4.3.4 Place the conduits, cables, ground rod(s), and ground wire(s) as indicated on the engineering
work prints.
Note: At the splice chamber end, place the conduits to hold the four 4-inch (10.2 cm)
conduits in a 2-by-2 pattern. If required, at the power chamber end, place two
4-inch (10.2 cm) conduits side by side.
4.3.5 Install a ring groundsystemaround theproposed foundation pad according to local practices and
building safety codes.
4.3.6 Lay the MESA®6 NxT / Calix ODC-120 template (Fig. 10) on the ground, placing it over the
conduits. Slip the conduits into the template holes to position them. Back fill and tamp the
trench to hold the conduit firmly in place.
Note: Be sure the conduit ends extending through the template are aligned vertically
(perpendicular to the template surface).
Note: The pad top surface should be approximately six inches (15.2 cm) above the
gravel base, and two inches (5.08 cm) above the final grade.
4.3.7 If a power transfer template will be mounted to the pad, place the power transfer template in one
corner of the pad. Route the 1 3/4-inch (4.45 cm) conduit from the AC end chamber side of the
cabinet template to the power transfer pedestal template. Remove the template. Backfill and
tamp the trench to hold the conduits in position.

12
Calix ODC-120 Installation Guide
Proprietary Information: Not for use or disclosure except by written agreement with Calix.
© 2005 Calix. All Rights Reserved.
Fig. 10 : Foundation Pad Design
INSTALLATION NOTES:
• Square and level the template on the stakes so the top of the mounting plates are flush (-0 +1/4inch).
• Check the template to be sure both diagonal measurements between the anchor bolts are equal (nominal 97 7/32" or (246.94 cm).
• Be sure the 1/2-13 anchor bolts are fully threaded into anchor nuts before pouring concrete.
GENERAL NOTES:
• Center template in concrete form.
• Bending or twisting template can result in door misalignment.
• Concrete surface shall be level and flat, not beveled.

13
Calix ODC-120 Installation Guide
Proprietary Information: Not for use or disclosure except by written agreement with Calix.
© 2005 Calix. All Rights Reserved.
4.3.8 Remove the template(s). Add the wooden stakes and level them.
4.3.9 Place the wire mesh (6 x 6, 4 gauge). Be sure the wire mesh is centered vertically.
Note: No. 3 (3/8-inch or 9 mm) or larger reinforcing rod, placed on 15-inch (38.1 cm)
centers, may be used in place of wire mesh.
4.3.10 Place the MESA®6 NxT / Calix ODC-120 template in the form and over the conduits. If used,
place the JuiceBox template into the form and over the 1 3/4-inch conduit.
4.3.11 Fasten the template(s) to wooden stakes as shown in Fig. 10.
CAUTION
Make certain the MESA®6 NxT / Calix ODC-120 cabinet template is flat and levelto prevent
misalignment of cabinet doors.
4.3.12 Square and level the template(s) on the stakes so the tops of the mounting plates are flush with,
or no more than 1/4-in. (6 mm) above, the top of the pad (Fig. 11). Square the template(s) so
the diagonal measurement between the anchor bolts is equal.
Note: The cabinet must clear the finished concrete surface so that the base panel below
the cabinet end chamber can be removed.
4.3.13 The conduit should extend approximately two inches (5.08 cm) above the template (Fig. 11).
Cover the conduits at the top to keep concrete from entering them during the pour.
Note: Make sure the conduit ends extend vertically through the template (perpendicular
to the template surface).
4.3.14 Before pouring concrete, be sure that all eight 1/2" x 13 anchor bolts in the MESA®template
are threaded all the way down in the anchor nuts.
ELECTRICAL CONDUIT
EXTENDING 2" (50.8 mm) ABOVE
CONCRETE PAD
CABLE CONDUITS
2" (5.08 cm) ABOVE
CONCRETE PAD CABINET TEMPLATE
FLUSH WITH, TO 1/4" (6.4 mm)
ABOVE TOP OF CONCRETE
2" (5.08 cm)
2" (5.08 cm)
2
" (5.08 cm)
WOODEN FORM
(2 x 6) TYPICAL 6" (15.24 cm)
CONCRETE PAD
NOTE: If pole-mounted power transfer switch is used, delete power
pedestal opening and conduit, and extend AC power conduit
12" (30.5 cm) beyond concrete pad in direction shown on
engineering drawings.
WELDED MESH
6 X 6 X 4/4 (4 GAUGE WIRE
)
GROUND WIRE TO
GROUNDING SYSTEM
COMPACTED
SOIL
SAND
OR GRAVEL
16" STAKES
Fig. 11 : Position of Conduit in Template

14
Calix ODC-120 Installation Guide
Proprietary Information: Not for use or disclosure except by written agreement with Calix.
© 2005 Calix. All Rights Reserved.
4.3.15 Be sure that all the wire mesh or reinforcing bars are set approximately two inches (5.08 cm)
off the bottom of the form.
4.3.16 If required, use local practices to treat the area below the pad and for two feet (61 cm) around
the perimeter against insect infestation.
4.3.17 Use a high-early strength concrete mix so the cabinet may be placed three days following
concrete pouring. Coarse aggregate used in the concrete shall be graded from 3/4-in. (1.8 cm)
to No. 4 only. The compression strength of the concrete must be a minimum of 4000 psi as
determined by ASTM C39 test of compression strength of concrete cylinders.
4.3.18 Pour the concrete. Finish the concrete so that the entire surface is flush with or 1/4inch (6 mm)
below the top of the template mounting plates.
4.3.19 Cure the pad for a minimum of three days before cabinet installation, or according to the type
of concrete used and/or local practices.
4.4 Unpacking the Cabinet
4.4.1 MESA®6 NxT / Calix ODC-120 cabinets are shipped on wooden pallets with plastic covering
and corrugated cardboard to protect the cabinet during shipment.
DANGER
A CABINET NOT SECURED TO A PALLET OR PAD IS UNSTABLE AND COULD
TIP OVER CAUSING SERIOUS INJURY OR DAMAGE TO EQUIPMENT.
Do not install any equipment until the cabinet is secured to its concrete foundation pad.
CAUTION
TO AVOID EQUIPMENT DAMAGE:
DO NOT REMOVE The pallet, corrugated cardboard and plastic covering from the cabinet
until the cabinet is transported to the installation site.
Always ship and store the MESA®6 NxT / Calix ODC-120 cabinets on the pallet in an upright
position to avoid possible damage to the internal equipment.
Until the cabinet is turned up for service, the desiccant shipped with the cabinet must remain
in the cabinet to retard moisture condensation.
4.4.2 If the external packaging appears excessively damaged, do not accept the unit from the shipper
as interior damage may not be apparent.
4.4.3 CAREFULLY remove all packaging material from around the cabinet and pallet. Dispose of the
packaging according to local practices. DO NOT REMOVE THE CABINET FROM IT'S
PALLET AT THIS TIME.
Table of contents
Other Calix Enclosure manuals
Popular Enclosure manuals by other brands

Ventev
Ventev Hazardous Installation & operating manual

PCB Piezotronics
PCB Piezotronics IMI SENSORS 691A50/08 Installation and operating manual

Johnson Controls
Johnson Controls S300 Series Hardware installation manual

Peavey
Peavey DS DS-1803 Specifications

Eden
Eden D Series Operation manual

Rosewill
Rosewill Himars Quick user guide

Wet Sounds
Wet Sounds Stealth AS Series Installation & owner's manual

MTX
MTX THUNDER FORM F250X00BK20A-TN owner's manual

Altelix
Altelix NX161206-DIN installation guide

Sennheiser
Sennheiser EZL 1030-20 L Instructions for use

Positron
Positron BRX-VDSL2-2 quick start guide

Tempest
Tempest Thunder 6600 user manual