
CambridgeAirSolutions 10/31/2022
BACnetControllerEVAPTechnicalManual Version4.0.2.0002
ANALOG VALUE OBJECTS
Object Description Writable Units Range Default
AV:29501 Device Address True NA 4 - 127 4
AV:29502 Device Object ID True NA 0 - 4194302 NA
AV:29510 DAT Sensor Offset True °F -10 – 10 0°F
AV:29512 Deadband True °F 0 – 20 0°F
AV:29513 High Drain Threshold True μS/cm 0-10,000 X
AV:29514 Drain Delay Time True Minutes 0 - 120 X min
AV:29515 Drying Time True Minutes 0 - 120 X min
AV:29516 Valve Delay True Minutes 0 - 120 X min
AV:29517 Fan Fault Delay True seconds 0 - 300 60 sec
AV:29518 Water Flush System True μS/cm 0-10,000 X
AV:29519 OAT Sensor Offset True °F -10 – 10 0°F
AV:29520 Low OA Lockout Setpoint True °F 40 – 160 40°F
AV:29521 Pump Down Time True Minutes 0 - 120 X min
AV:29522 Fan Start Delay True Minutes 0 - 120 X min
AV:29524 ZNT Sensor Offset True °F -10 – 10 0°F
AV:29534 Supply Fan Cycle Count False Counts NA NA
AV:29535 Supply Fan Runtime False hours NA NA
AV:29536 Supply Fan Speed (optional) True % 0 - 100 100%
AV:29537 Effective Cooling Setpoint False °F NA NA
AV:29538 OA Econ Lockout Setpoint True °F 40 – 160 65°F
AV:29539 Unoccupied Discharge Air Flow Setpoint True °F 40 – 160 65°F
AV:29540 Occupied Discharge Air Flow Setpoint True °F 40 – 160 65°F
AV:29541 Occupied Zone Cooling Set Point True °F 40 – 160 75°F
AV:29542 Unoccupied Zone Cooling Set Point True °F 40 – 160 85°F
AV:29543 Freeze Stat Setpoint True °F 40 – 160 65°F
AV:29544 Netsensor Temp False °F 32 – 104 NA
AV:29545 Netsensor Humidity False % 0 – 100 NA
AV:29546 RH Setpoint True % 0-100 60%
AV:29547 Inlet Air Cooler True NA 1-2
AV:29548 Number of Pumps True NA 1-2
AV:29549 Stage Up Delay True Minutes 0 - 30 X min
AV:29552 OA Heating Lockout Setpoint True °F 0 – 130 65°F
AV:29553 Discharge Air High Set Point True °F 40 – 160 160°F
AV:29554 Discharge Air Low Set Point True °F 40 – 160 70°F
AV:29555 Occupied Zone Heating Set Point True °F 60 – 90 60°F
AV:29556 Unoccupied Zone Heating Set Point True °F 40 - 80 55°F
AV:29557 Burner Modulation Set Point False % NA NA
AV:29560 Burner Fault Delay True seconds 0 - 300 60 sec
AV:29561 Low Temperature Cutout Setpoint True °F 45 - 55 45°F
AV:29562 Low Temperature Cutout Delay True seconds 0 - 300 60 sec
AV:29563 Effective Heating Set Point False °F NA NA
AV:29564 Effective Discharge Air Set Point False °F NA NA
AV:29565 Burner Runtime False hours NA NA
AV:29566 Burner Cycle Count False Counts NA NA