Martem TELEM-AGC-L User manual

Street lighting controller TELEM-AGC-L
User Manual
Martem AS
2018

Contents
1. INTRODUCTION................................................................................................................................. 3
2. FEATURES ......................................................................................................................................... 3
3. TECHNICAL DATA............................................................................................................................. 4
4. TERMINAL CONNECTORS ............................................................................................................... 7
5. COMMUNICATION CABLES ............................................................................................................. 8
6. FIRMWARE UPDATE......................................................................................................................... 9
7. DIP SWITCHES................................................................................................................................. 10
8. INDICATION LED-S.......................................................................................................................... 10
9. CONFIGURATION TOOL................................................................................................................. 10
10. ORDER CODE ................................................................................................................................ 11
11. OPEN-SOURCE SOFTWARE INFORMATION ............................................................................. 11

AS Martem Street Lighting Controller TELEM-AGC-L User Manual Rev. 1 / 2018
AS MARTEM Tel: +372 639 7979 [email protected] www.martem.eu
- 3-
1. Introduction
TELEM-AGC-L is used as LCBC (Light Control Box Controller) in smart street
lighting solutions. The system is visualized by central map based user interface
software. TELEM-AGC-L is a good choice for solutions where older and newer
individually controlled LED luminaries are in same control network
2. Features
Autonomous control without need of permanent connection to control center
based on internal astronomical clock and sensors
GPRS communication via secure VPN channels
Integrated radio and gateway functionality for individually controlled luminaires
solution
Interfaces for energy meters and transducers
> 10 sec. operation after power outage for sending last signals
Astronomical clock
NTP time synchronization

AS Martem Street Lighting Controller TELEM-AGC-L User Manual Rev. 1 / 2018
AS MARTEM Tel: +372 639 7979 [email protected] www.martem.eu
- 4-
Logical operations between digital and analog signals
Alarms via SMS and e-mail
Web browser interface for control and maintenance
OpenVPN, IPsec, L2TP and SSH secure connections
Historical data recording
SNMP for monitoring
Various data exchange protocols via Ethernet and serial ports
An user friendly free configuration tool
Configurable remotely over communication line
Configuration export/import to/from CSV format files
Charger for external backup battery
3. Technical Data
Data communication protocols
To upper level systems:
IEC 60870-5-104
IEC 60870-5-101
Modbus-TCP (on development)
To lower level devices:
IEC 61850
IEC 60870-5-101 unbalanced
IEC 60870-5-103
IEC 60870-5-104
Modbus-RTU
Modbus-TCP
IEC 62056-21 (IEC 1107)
SPA-Bus
Communication ports can be freely configured for upper or lower level
communication.

AS Martem Street Lighting Controller TELEM-AGC-L User Manual Rev. 1 / 2018
AS MARTEM Tel: +372 639 7979 [email protected] www.martem.eu
- 5-
Interfaces on base board
Communication ports
GPRS modem
Optional radio network interface
Ethernet RJ45 connector, 1,5 kV isolation
2 x RS-232 with RJ9-4P4C connector, galvanically isolated, 15 kV
surge protection
RS-485, galvanically isolated, 15 kV surge protection
1-wire for environmental sensors
Photo and temperature resistor inputs
USB console port for maintenance
IO connectors
8 optically isolated digital inputs (wet contacts with internal supply)
4 relay outputs (max 0,5 A 250 VAC; 0,25 A 220 VDC)
Expansion modules
Module A
8 optically isolated digital inputs (wet contacts with internal supply)
4 relay outputs (max 0,5 A 250 VAC; 0,25 A 220 VDC)
Module B
8 optically isolated digital inputs (wet contacts with internal supply)
3 relay outputs (max 0,5 A 250 VAC; 0,25 A 220 VDC)
DALI master interface
Module F
16 optically isolated digital inputs (wet contacts with internal supply)
8 relay outputs (max 0,5 A 250 VAC; 0,25 A 220 VDC)
Module G
16 optically isolated digital inputs (wet contacts with internal supply)
7 relay outputs (max 0,5 A 250 VAC; 0,25 A 220 VDC)
DALI master interface

AS Martem Street Lighting Controller TELEM-AGC-L User Manual Rev. 1 / 2018
AS MARTEM Tel: +372 639 7979 [email protected] www.martem.eu
- 6-
Serial data communication parameters
1 start bit
Odd, even or no parity
Communication rates from 300 to 115200 bit/sec
Electrical characteristics of isolated input
Withstand to static discharge IEC 61000-4-2
Withstand to bursts, surges IEC 61000-4-4, 61000-4-5
Power frequency magnetic field IEC 61000-4-8
Voltage dips, variations IEC 61000-4-11
Mechanical parameters
Degree of protection IP 31
Dimensions (W x H x D) 65x155x190 mm
(with protruding parts)
Ambient temperature in operation –40°C…+70°C
Weight 900 g
Mounting DIN rail
Relative humidity 95% non-condensing
Radio frequency compatibility
RF emission IEC 55022 Class A
Immunity to RF fields IEC 61000-4-3, 61000-4-6
Power supply
Supply voltage range 230V AC
Power consumption < 7W

AS Martem Street Lighting Controller TELEM-AGC-L User Manual Rev. 1 / 2018
AS MARTEM Tel: +372 639 7979 [email protected] www.martem.eu
- 7-
4. Terminal Connectors
RJ9-4P4C
C2 RS232
– RS485
+ RS485
C3 GND C3 R485
1
C
2
C
3
C
4
C
RJ45
COMMON
DI 1
DI 2
DI 3
DI 4
Reset
Default Setup
C1&C2 GND 4
Tx 3
Rx 2
C1&C2 GND 1
C1&C2 GND 4
Tx 3
Rx 2
C1&C2 GND 1
Console
Modem
Run
Alert
Telem-AGC-L
MAIN BOARD, FRONT PANEL
DOWNSIDE
1-WIRESENSORSSIM 1
Radio
Modem
Antenna
GPRS
Antenna
13
C
14
C
15
C
16
C
COMMON
DI 13
DI 14
DI 15
DI 16
DO 6
DO 7
DO 8
9
C
10
C
11
C
12
C
DI 9
DI 10
DI 11
DI 12
DALI
or DO5
A
nc
B
21
C
22
C
23
C
24
C
COMMON
DI 21
DI 22
DI 23
DI 24
DO 9
DO 10
DO 11
DO 12
17
C
18
C
19
C
20
C
DI 17
DI 18
DI 19
DI 20
OPTIONAL INTERFACES
See order codes
UPSIDE
SD
C1 RS232
ETH 0
RJ9-4P4C
RJ9-4P4CRJ9-4P4C
DIGITAL INPUTS 8...5
DO 4 DO 3 DO 2
RELAY OUTPUTS 4...1
POWER
230VAC BATTERY
or OUTP.
12V 0,4A
- +
DI8 DI7 DI 6 DI 5
C 8 C 7 C 6 C 5
L N PE DO 1
or IFR

AS Martem Street Lighting Controller TELEM-AGC-L User Manual Rev. 1 / 2018
AS MARTEM Tel: +372 639 7979 [email protected] www.martem.eu
- 8-
5. Communication cables

AS Martem Street Lighting Controller TELEM-AGC-L User Manual Rev. 1 / 2018
AS MARTEM Tel: +372 639 7979 [email protected] www.martem.eu
- 9-
6. Firmware update
NB! Before updating to new firmware read the setup from your device, and
make a backup.
Run GWS.exe and set up SSH connection with the device
Press the Upd▼button next to R W C
buttons
If you have compressed .7z firmware update
file (provided by Martem AS) choose Update
From File
If you do not have .7z firmware update file choose Check martem.ee to
refresh exsisting firmware versions list for this AGC-L device
Press Update to feature and choose needed firmware version. Download is
starting...
After firmware is downloaded Confirm window appears. Press Yes button, the
update process starts
Wait until the device resumes to its normal operation state (RUN LED will start
slow blinking again)
Firmware update is complete.
Checking results of the firmware update operation:
Press Rbutton to read back the device setup data
Check the Version from GWS Status tab

AS Martem Street Lighting Controller TELEM-AGC-L User Manual Rev. 1 / 2018
AS MARTEM Tel: +372 639 7979 [email protected] www.martem.eu
- 10 -
7. DIP switches
Reset: Switch RESET to ON state and then back to OFF state for Reset operation
Dft. Set: To apply default setup:
1. Switch DFT. SET to ON state
*Alert indication LED starts blinking within 5 seconds
*Alert indication LED will blink for 2 seconds
2. Switch DFT. SET back to OFF state when the alert indication LED is
blinking to apply default setup
*If DFT. SET is switched back to OFF state when the alert indication LED is not
blinking, default setup will NOT be applied
8. Indication LED-s
MODEM –green LED –indicates the 4G, 3G, 2G modem network connection
RUN –green LED –blinking green indicates that the program is running
ALERT –red LED –failure
Green LED-s for serial communication ports for RX, TX indication.
9. Configuration tool
The Telem-AGC device is configured with Telem-GWS software.
The configuration process is described in Telem-GWS software manual.

AS Martem Street Lighting Controller TELEM-AGC-L User Manual Rev. 1 / 2018
AS MARTEM Tel: +372 639 7979 [email protected] www.martem.eu
- 11 -
10. Order code
AGC-LX-XX-X Power A –230 V AC
Extra communication R –Radio; N –No
GPRS modem 3 –3G; 4 –4G; N –No
Expansion module A –8 DI, 4 DO;
B –8 DI, 3 DO, DALI;
F –16 DI, 8 DO;
G –16 DI, 7 DO, DALI;
N –No
11. Open-source software information
This device produced by Martem Ltd. includes open-source components. The
most up to date info of exact software used by Martem’s build system and licensing
info of used software can be found from https://phobos.martem.ee/shr/br-sources/
Table of contents
Popular Controllers manuals by other brands

MicroImage Video Systems
MicroImage Video Systems MIR540 Operation manual

Metal-Fach
Metal-Fach ecoMAX 860P User's manual and installation

WEST
WEST 8800 operating manual

Contemporary Research
Contemporary Research ICW-STA product manual

Valcom
Valcom V-1092 user guide

Burkert
Burkert 2051 operating instructions