Cameron BARTON 580A User manual

BARTON®NUCLEAR MODEL 580A
DIFFERENTIAL PRESSURE
SWITCH
User Manual
Part No. 9A-C10795, Rev. 03
September 2015
Model 580A-0 Switch
with Indicator
Contents
Safety............................................................................................................ 2
Section 1—Introduction................................................................................. 3
General ......................................................................................................... 3
Wiring ........................................................................................................ 5
Differential Pressure Unit (DPU) ............................................................... 5
Specications ............................................................................................... 6
General...................................................................................................... 6
Nuclear Qualications ............................................................................... 6
Application Specications ......................................................................... 7
Storage Specications .............................................................................. 7
Section 2—Installation................................................................................... 9
Mounting/Piping/DPU Installation ................................................................. 9
Electrical Connection .................................................................................... 9
Switch Use.................................................................................................... 9
Startup ........................................................................................................ 10
Switch Wiring .............................................................................................. 10
Section 3—Maintenance and Calibration....................................................11
Tools............................................................................................................ 12
Bezel/Lens Assembly or Cover Installation and Removal........................... 12
Pointer Installation and Removal ................................................................ 13
Pointer Installation .................................................................................. 13
Pointer Removal...................................................................................... 14
Scale Plate Installation and Removal ......................................................... 14
Indicator Calibration.................................................................................... 15
Drive Arm Tightness Test......................................................................... 17
Drive Arm Stop Adjustment ..................................................................... 17
Switch Calibration ..................................................................................... 18
Calibration Setup..................................................................................... 18
Linkage Calibration Procedure ............................................................... 19

Safety
Before installing this product, become familiar with the installation instruc-
tions presented in Section 3, Appendix A and all safety notes throughout.
! WARNING:Thissymbolidentiesinformationaboutpracticesorcircum-
stancesthatcanleadtopersonalinjuryordeath,propertydamage,or
economic loss.
CAUTION: Indicatesactionsorprocedureswhichifnotperformedcorrectly
mayleadtopersonalinjuryorincorrectfunctionoftheinstrument
orconnectedequipment.
IMPORTANT: Indicates actions or procedures which may affect instrument operation or
may lead to an instrument response that is not planned.
Changing Switch Set Point ......................................................................... 20
Denitions of Terms................................................................................. 20
Best Practices for Set Points................................................................... 20
Changing Set Point of an In-Service Instrument (Not Recommended for
Nuclear Qualied Units) .......................................................................... 21
Changing Set Point of an Out-of-Service Instrument .............................. 22
Range Changes ...................................................................................... 22
Troubleshooting ......................................................................................... 23
Section4—AssemblyDrawingandPartsList........................................... 25
Section5—DimensionalDrawings ............................................................. 33
AppendixA—Model224DPU ....................................................................A-1
DPU Description ........................................................................................A-1
Specications .........................................................................................A-1
Theory of Operation ...............................................................................A-3
DPU Installation .........................................................................................A-4
General...................................................................................................A-4
Mounting.................................................................................................A-5
Piping .....................................................................................................A-5
Piping Diagrams.....................................................................................A-6
Startup..................................................................................................A-12
DPU Maintenance....................................................................................A-12
DPU Cleaning and Inspection ..............................................................A-13
Changing the DPU Range....................................................................A-14
Replacing the Bellows Unit Assembly (BUA) .......................................A-14
DPU Troubleshooting...............................................................................A-15
DPU Assembly Drawing and Parts List....................................................A-17
DPU Dimensional Drawing ......................................................................A-19

3
Model 580A Differential Pressure Switch Section 1
Section 1—Introduction
General
The 580A Differential Pressure Switch actuates single or dual signal circuits
when predetermined limits of ow or level are exceeded. The DPU is con-
nected to the process or vessel by tubing or piping. Changes in differential
pressure (DP) at the DPU produce a mechanical output which moves a pointer
and switch actuation controls.
For ow measurements, the instrument is connected to the high-pressure
and low-pressure sides of a primary device in the process run. Normally the
primary device will be an orice plate, venturi, or ow tube.
For liquid level measurement applications, the instrument is connected to
measure changes in differential pressure caused by variations in hydrostatic
pressures of the liquid in a tank.
The 580A switch is available in three model variations:
• Indicating Switch (Model 580A-0). This model, shown on the manual
cover, has a thick tempered plate glass lens and provides a visual indica-
tion of the difference in the two monitored pressures.
• Blind Switch (Model 580A-2).This model has a solid metal cover and
provides no visual indication of differential pressure.
• Blind Switch with Internal Indicator. Unlike the indicating model with
the glass lens, there is no externally visible indicator. However, internally,
components are the same as in Model 580A-0. With the cover removed, a
user can use the internal indicator to determine DPU input pressure when
making adjustments to the switch setpoints.
The Model 580A uses two independently adjustable single-pole double-throw
(SPDT) snap-acting switches that are rated for high temperatures. Both sides
of the switches are wired, enabling the switches to serve both normally-open
and normally-closed applications. The direct-set switch contacts are adjustable
over a scale range of 10-90% nominal. Switches and all adjustments are read-
ily accessible when the cover is removed (see Figures 1.1 and 1.2, page 4).
The 580A Switches (indicating and blind) are qualied per IEEE 323-1974,
IEEE 344-1975, IEEE 381-1977and NUREG 0588, Rev. 1 for either Func-
tional and/or Pressure Boundary Integrity service in limited harsh environ-
ment applications.
The switch case is drawn stainless steel with a sealed glass header for the
electrical interface with the switches. No additional conduit seals are required
to ensure the integrity of the instrument.

4
Section 1 Model 580A Differential Pressure Switch
Left Switch
Right Switch
Pointer
Left Switch
Lock Screw
Plunger Screw
Actuating Cam
Left Switch
Adjustment
Assembly*
Switch Adjust Linkage
Plunger Screw
Right Switch
Lock Screw
Drive Arm
Stop Bracket
Movement Assembly
Terminal Strip
Switch Adjust Linkage
Right Switch
Adjustment
Assembly*
Range Adjust
* Switch Adjustment Assembly includes crank, index shaft, and index pointer.
Figure 1.1—580A (with indicator), internal components
Left Switch Right Switch
Left Switch
Lock Screw
Plunger Screw
Actuating Cam
Left Switch
Adjustment
Assembly*
Switch Adjust Linkage
Plunger Screw
Right Switch
Lock Screw
Terminal Strip
Switch Adjust Linkage
Right Switch
Adjustment
Assembly*
Cam Actuator
* Switch Adjustment Assembly includes crank, index shaft, and index pointer.
Figure 1.2—580A (without indicator), internal components
The cam rotates counterclockwise with increased pressure. In Figure 1.3, page
5, the LOW switch (typically set to alarm at decreasing pressure) is set at 25%
differential pressure while the HIGH switch (typically set to alarm at increas-
ing pressure) is set at 75% differential pressure.

5
Model 580A Differential Pressure Switch Section 1
1000
50
Zero DP
1000
50
Maximum DP
RED
Y ELLO W
BLU E
BLAC K
GREEN
WHI T E
1000
50
SW I T CH "A"
(LEFT )
SW I T CH "B"
(RIGHT)
CAM
TERM I NAL
BLO C K IN
CAS E
BO T H S W IT C HES RELAX ED
SWITCH
P
LUNGER
SC REW
Mid-point DP
HIGHLOW
SW I TC H "A" AC TUAT ED/S W I TC H "B" RELAX ED
SW I T CH "A" RELAX ED/S WI T C H "B" AC TUAT ED
SWITCH CLOSED
CONTA CTS
OPEN
CONTA CTS
GREEN/WHITE GREEN/BLACK
A (LEFT)
B (RIGHT)
YELLOW/BLUE YELLOW/RED
SWITCH CLOSED
CONTA CTS
OPEN
CONTA CTS
GREEN/WHITE GREEN/BLACK
A (LEFT)
B (RIGHT)
YELLOW/RED YELLOW/BLUE
SWITCH CLOSED
CONTA CTS
OPEN
CONTA CTS
GREEN/WHITEGREEN/BLACK
A (LEFT)
B (RIGHT)
YELLOW/BLUE YELLOW/RED
SW I T CH "A"
(LEFT )
SW I T CH "B"
(RIGHT)
SW I T CH "A"
(LEFT )
SW I T CH "B"
(RIGHT)
Notes:
1. CAM ROTATES COUNTER-CLOCKWISE WITH INCREASED DIFFERENTIAL PRESSURE
2. EACH SWITCH MAY BE SET AT ANY POINT FROM 10% TO 90% OF DP RANGE
3. WIRES: No. 22 AWG (Internal) and No. 18 AWG (External)
Figure 1.3—Switch wiring connections and actuation example
Wiring
Each switch is wired internally to a glass-sealed header using No. 22 AWG
ethylene tetrauoroethylene (Tefzel®) insulated wire for radiation service per
IEEE Standard 393-1974. Externally, from the header, permanently color
coded No. 18 AWG Tefzel®wires exit through a female conduit connection.
Differential Pressure Unit (DPU)
For detailed information on the Model 224 DPU, see Appendix A, page A-1.

6
Section 1 Model 580A Differential Pressure Switch
Specications
General
Actuating Unit (DPU) ...................... Model 224 DPU
Dial Size ......................................... 6 inches (150 mm)
Service Conditions (Normal)........... 40°F (4.4°C) to +180°F (+82.2°C) @ <90% R.H.
Switch Repeatability ....................... ±1% of calibrated span
Switch Set-point Range.................. 10 to 90% of calibrated span
Switch Deadband ........................... ±10% of calibrated span (maximum)
Switch Type .................................... Mechanical, Snap-Acting; both switches are SPDT
Activation........................................ Increasing or decreasing scale
Switch Contact Rating:
5.0 Amps @ 125 VAC
5.0 Amps @ 250 VAC
3.0 Amps @ 30 VDC (resistive)
1.0 Amp @ 30 VDC (inductive w/arc suppression)
0.4 Amp @ 125 VDC (resistive)
0.2 Amp @ 125 VDC (inductive w/arc suppression)
Input Range.................................... 0-30" WC to 0-650 psid
Indicator Accuracy .......................... ±2.0% of calibrated span (for ranges to 400 psid)1,2
Indicator Repeatability.................... ±0.5% of calibrated span
Safe Working Pressure................... 500, 1000, 1500, 3000, or 6000 psig
Maximum Overrange...................... To safe working pressure
Process Connections...................... 1/4" x 1/4", 1/4" x 1/2", 1/2" x 1/4" and 1/2" x 1/2"
(top x bottom)
Electrical Connections.................... Female, 3/4" NPT, 20 ft., color-coded Tefzel®
insulated 18 AWG wire (40 ft. leads available by
special order)
Torque Tube Rotation ..................... 8° (nominal)
1± 2.5% of calibrated span for ranges between 400 and 600 psid; ±6% for ranges over
600 psid.
2Additional 2% is applicable near the switch setpoints (±10% span).
Nuclear Qualications
The following nuclear qualication applications are based on Cameron Engi-
neering Report 9A-CR3-580A-29 and 9A-CR3-580A31.
Design Basis Event (DBE) Performance Error1(% of calibrated span):
Radiation (1 x 107Rads) ................ ±10%
Seismic (12.5 Gs):
During Event................................... ±10%
Following Event .............................. ±5%
Harsh Environment (≤ 200°F):
During Event................................... ±10%
Following Event .............................. ±10%
1Includes the cumulative effect of accelerated aging.

7
Model 580A Differential Pressure Switch Section 1
Application Specications
Model 580A switches were subjected to IEEE 323-1974/344-1975 quali-
cation testing, which found the devices suitable for functional service in a
limited harsh environment. The service conditions associated with the limited
qualications are:
• 22 year qualied service life1 normal conditions of 104°F and 0 psig
• Radiation exposure to 1 x 107 Rads (TID)
• 85 days @maximum DBE conditions of 200°F, 10 psig ambient pressure
and ≥ 95% R.H.
• Seismic qualications:
– OBE @ 6.25 Gs (series of 5)
– SSE @ 12.5 Gs
– 5% critical damping
– No resonance in frequencies below 33 Hz
• Mechanical aging included:
– 25,000 pressure cycles during accelerated aging
– 12,500 electrical cycles during accelerated aging
– Vibration cycling using 0.2 G sinusoidal sweeps over the 1 to 200
Hz range at 1.0 octave/min.
1 Qualied Life: This equipment contains some organic material. The qualied life will be
governed by factors such as environmental temperature, radiation exposure, and activa-
tion energy.
Storage Specications
Storage per ANSI N45.2.2-1978 Level B at 70°F (21°C) ±20°F (±11°C) in
factory sealed package for 2.5 years maximum will not affect installed service
life.

8
Section 1 Model 580A Differential Pressure Switch

9
Model 580A Differential Pressure Switch Section 2
Section 2—Installation
The instrument should be inspected at time of unpacking to detect any dam-
age that may have occurred during shipment.
IMPORTANT: The DPU was checked for accuracy at the factory. Do not change any of
the settings during examination or accuracy could be affected.
For applications requiring special cleaning/precautions, a polyethylene bag
is used to protect the instrument from contamination. This bag should be
removed only under conditions of extreme cleanliness.
Mounting/Piping/DPUInstallation
Mount the instrument with four customer-supplied 5/16-in. (8-mm) bolts,
Grade 5 or greater, torqued to 17 ft/lbs. Mounting structures should be
designed to avoid resonance and/or minimize resulting amplication below
33 Hz. Response spectra at mounting surface of the instrument shall not
exceed those in the R3-580A-29 Qualication Report. Interfacing process
tubing and conduit shall be supported by the same mounting as the DP instru-
ment base in order to minimize relative motion of the DP instrument and
connections.
Dimensional drawings are provided on Section 5—Dimensional Drawings,
page 33.
See Appendix A, page A-1, for Model 224 DPU installation and mainte-
nance information.
Electrical Connection
Units are supplied with dual alarm switches. The direct-set switch contacts
are adjustable over 10% to 90% of the scale range.
The high switch and low switch set point adjustment procedures are covered
in Changing Switch Set Point, page 20.
For physical location of switches, see Figures 1.1 and 1.2, page 4.
SwitchUse
Switch contact life is inuenced by various application conditions such as
temperature, humidity, airborne contamination, vibration, amount of plunger
travel, cycling rate, and rate of plunger travel (and others), as well as by the
electrical (circuit) characteristics.

10
Section 2 Model 580A Differential Pressure Switch
IMPORTANT: Arc suppression for inductive loads will prolong the life of the switch
contacts.
Startup
For startup procedures, warnings, and other information on the Model 224
DPU, see Appendix A, page A-1.
IMPORTANT: To ensure the unit calibration is within factory-set calibration tolerances,
perform the Calibration Check procedure on page 12.
SwitchWiring
IMPORTANT: Figure 2.1 shows switch contacts in the relaxed (shelf) condition, the low
switch set to trip at a position below the pointer scale position, and the
high switch set to trip at a position above the pointer scale position. NO
= Normally Open in (shelf) condition. NC = Normally Closed in (shelf)
condition. C= Common.
LOW & HIGH SPDT SWITCHES
NO NOC CNC NC
RED
YELLOW
BLUE
RED
YELLOW
BLUE
WHITE
GREEN
BLACK
WHITE
GREEN
BLACK
1 2 3 4 5 6 7 8 9 10
Figure 2.1—Low/high SPDT switch diagrams
Table2.1—SwitchWireColorCoding
580ACurrentCongurations
NO C NC
Low Red Yellow Blue
High Black Green White

11
Model 580A Differential Pressure Switch Section 3
Section 3—Maintenance and Calibration
The following checks are recommended for preventive maintenance:
• Periodically inspect the alarm switch mechanism to verify that all mount-
ing screws are seated properly.
• Inspect linkage for wear.
• Inspect integrity of electrical circuits. Tighten as necessary.
When repairs are necesssary, review this section for maintenance procedures
such as bezel/lens installation and removal, pointer installation and removal,
indicator calibration, switch calibration, and switch set point changes. Refer
to Figure 3.1 as needed for component identication.
SWITCH LOCKS
ZERO ADJUST
POINTER STOP
3/4 NPT (INTERNAL)
CONDUIT CONNECTOR
20 FT (6.1 M) LG
18 AWG EXT LEADS STANDARD;
40 FT (12.2 M) LG LEADS OPTIONAL
SWITCH ADJUST 1/8 (3.2)
HEX 1/8 DP
TO ADJUST SWITCH SETTING
REMOVE SCREWS AND COVER
RANGE ADJUST
POINTER
Figure 3.1—Model 580A adjustment controls
IMPORTANT: Never perform maintenance/repair on the Model 580A differential pres-
sure switch without rst reviewing all procedures and warning/caution
notices in this manual. See Appendix A, page A-1,for related warning/
caution notices and instructions for the Model 224 DPU.

12
Section 3 Model 580A Differential Pressure Switch
Tools
The following tools are recommended for general maintenance of the Model
580A differential pressure switch.
Table 3.1—Tools
Equipment Purpose
Pointer Puller Pointer removal
Small Screwdriver Calibration adjustment
Medium Screwdriver Bezel removal and replacement
1/4" and 1/8" Open-end Wrenches Zero (1/4") and Range (1/8") adjustments
1/8 Hex Allen Wrench Switch set point adjustment
Bezel/LensAssemblyorCoverInstallationandRemoval
To remove the bezel/lens assembly or cover, loosen the eight screws on the
front and lift the assembly or cover from the enclosure.
To reinstall the bezel/lens assembly (580A-0 only), install the O-ring in the
groove of the case, assemble the bezel, lens, and lens gasket, and realign the
screw holes with the holes in the case. Then, reinstall the screws in the bezel
to secure all components to the case. Torque the screws per Table 4.3, page
31.
To reinstall the cover (580A-2), install the O-ring in the groove of the case
and realign the screw holes in the cover with the holes in the case. Reinstall
the screws in the cover to secure it to the case. Torque the screws per Table
4.3, page 31.
Calibration Check
To ensure the unit calibration is within factory-set calibration tolerances,
perform the following procedure.
IMPORTANT: Review all Model 224 DPU procedures and WARNINGS/NOTICES in
Appendix A, page A-1, before performing this procedure.
1. Mount the instrument in an approximately level position and connect to a
standard pressure source.
2. If the zero indication is incorrect, adjust it as follows:
a. Remove the bezel/lens assembly or cover.
b. Using a 1/4" open-end wrench (included in calibration toolkit, Part
No. 9A-0288-1032B), hold the hexagon pointer hub xed and rotate
the pointer with ngers until the pointer indicates zero on the scale.
See Figure 3.2, page 13.

13
Model 580A Differential Pressure Switch Section 3
c. Replace the bezel/lens assembly.
HUB
Pointer "slipped"
rotated on hub
Hub held in place
with 1/4" wrench
Figure 3.2—"Slipping" pointer
3. To test for reverse travel, connect the pressure source to the low-pressure
(LP) housing and vent the HP housing. Apply pressure to approximately
150% of the DP range. The pointer should move approximately 5% to
10% below zero.
4. To test for overtravel, connect the pressure source to the HP housing and
vent the LP housing. Apply pressure to approximately 150% of DP range.
The pointer should move approximately 5% to 10% above the full scale
mark.
5. Apply 0, 50, and 100% of full scale pressure. If the indication is within
specied limits, no adjustments are necessary. If the indication is not
within specied limits, perform a complete calibration (see Indicator
Calibration, page 15).
6. Make sure the instrument zero indication is correct; otherwise, repeat
step 2.
7. Verify the switch set points (refer to Changing Switch Set Point, page
20).
PointerInstallationandRemoval
During adjustment and calibration of the unit, it may be necessary to remove
and reinstall the pointer. See the following procedures for instructions. Note
that the scale plate is split to allow it to be removed without pulling the
pointer.
Pointer Installation
1. Position the pointer on the movement shaft with the pointer set at zero
scale. Obtain 75% to 90% pointer hub engagement on the movement
pinion shaft. The pinion shaft must not extend through the pointer hub. It
may be necessary to enlarge the hub hole using a tapered broach (includ-
ed in the calibration toolkit, Part No. 9A-0288-1032B).

14
Section 3 Model 580A Differential Pressure Switch
2. Lightly tap the pointer hub with a hand-set or other at-end tool. Use
perpendicular blows to avoid bending the shaft.
3. Check the calibration of the indicating switch over its entire range (refer
to Indicator Calibration, page 15). If the indicating switch is correctly
calibrated, secure the pointer to the movement shaft by tapping the hub
with a hand-set or other at-end tool.
4. Test the pointer for tightness by moving the pointer from the zero to the
50% position manually, and then letting the pointer return freely to zero.
If the pointer indicates a shift, tap the pointer hub to tighten it to the
shaft.
Pointer Removal
The pointer is removed with a pointer puller shown in Figure 3.3. This tool is
included in the calibration toolkit, Part No. 9A-0288-1032B.
To remove the pointer, perform the following steps:
1. Slide the pointer puller along the pointer until the pin protruding from the
tip of the screw in the pointer puller is directly over the movement shaft
and the arms of the pointer puller are directly under the pointer.
2. Gently turn the knurled head of the screw clockwise, pushing the pin
against the movement shaft and lifting the pointer with the arms. Finger
pressure should be sufcient to pull the pointer free. If more pressure is
required, an Allen wrench (inserted into head of the screw) can be used.
However, care should be exercised to avoid breaking the pin.
HUB
MOVEMENT SHAFT
POINTER
HUB
POINTER PULLER
Figure 3.3—Pointer puller (Part No. 9A-0163-0005B)
ScalePlateInstallationandRemoval
During adjustments and calibration of the unit, it may be necessary to remove
and reinstall the scale plate. The scale plate is split to allow removal without
pulling the pointer. It is held in place by ve screws (Item 40 in Figure A.1,
page A-2) and two mounting tabs at 12 o'clock and 6 o'clock positions. The
scale plate halves rest against the top tab (12 o'clock), and slide beneath the
bottom tab (6 o'clock).

15
Model 580A Differential Pressure Switch Section 3
To remove the scale plate, move the pointer to the 12 o'clock position, remove
the screws from the scale plate, and gently guide the scale plate halves from
beneath the bottom mounting tab. Screws are located at 12, 3 and 9 o'clock
positions and near the center of the plate which overlays a narrow bracket.
To reinstall the scale plate, repeat the installation steps in reverse order, as
follows. Holding the pointer in the 12 o'clock position, place the scale plate
halves against the top mounting tab and guide the bottom edges behind the
bottom tab. Replace the screws in the top tab and in the center of the scale
plate. No screw is used with the bottom tab.
Indicator Calibration
If the DPU assembly is replaced on a Model 580A differential pressure switch
with indicator, the indicator must be recalibrated. This procedure does not ap-
ply to the 580A-2 blind switch without indicator.
IMPORTANT: Review all Model 224 DPU procedures and WARNINGS/NOTICES in
Appendix A, page A-1, before performing this procedure.
1. Securely mount the instrument in an approximately level position and
connect the DPU, as described in Mounting, page A-5.
2. Remove the bezel/lens assembly or cover.
3. Align the linkage between the drive arm and the movement at 50% differ-
ential pressure (DP) as shown in Figure 3.3. Inspect parts for straightness
and pivot-t without binding.
Figure 3.4—Range/linearity adjustment (50% DP)
4. Check the pointer for zero indication. If necessary, set the pointer to zero
by slipping the pointer on the hub, per step 2 of Calibration Check, page
12.
5. Apply 100% pressure. If the pointer exceeds full-scale, adjust the range
adjust screw with a 1/8-in. open-end wrench to lengthen the movement
range arm..

16
Section 3 Model 580A Differential Pressure Switch
6. Release pressure. Set the pointer to zero, by slipping the pointer on the
hub, per step 2 of Calibration Check, page 12.
7. Repeat steps 4 and 5, as necessary, to obtain the correct zero/full-scale.
8. Apply 50% DP. If the pointer indicates 50%, proceed to step 9. If the
pointer does not indicate 50% scale, adjust linearity as follows.
a. Loosen the drive arm screw (Figure 3.5) and move the arm to shift
the pointer in the direction of the error a distance of about 10 times
the linearity error.
b. To prevent interference, check to see that the drive arm clears the
end of torque-tube housing by approximately 0.030 in. before re-
tightening the drive arm screw.
c. While supporting the block/shaft, tighten the clamp screw until it is
snug to the shaft.
d. Still supporting the block/shaft, tighten the clamp screw an addition-
al 1/3 to 1/2 turn. (This screw can normally turn one full revolution
before breaking.)
e. Perform the Drive Arm Tightness Test described on page 17 before
returning the instrument to service.
1/8” WRENCH
(PN 9A-0163-0044C)
CLAMP SCREW
DRIVE ARM
LINK SINTERED
CLAMP BLOCK
TO TIGHTEN
.03 (approx)
M224
SHAFT
Figure 3.5—Drive arm to torque tube connection
9. Release pressure and reset the pointer to zero. Check the span. If the gear
in the movement reaches a limit of travel as a result of linearity adjust-
ment (step 8), slip the range arm along the gear approximately 5 degrees
from the normal 37.5 degree angle to approximately 43 degrees (see
step 3). To slip the range arm, apply pressure to the range arm with the
thumb, while holding the gear rmly in place. Retest the pointer response
at 50%, 0%, and 100% of full-scale differential pressure, and adjust the
linkage until the readings are acceptable.

17
Model 580A Differential Pressure Switch Section 3
10. Apply 0%, 25%, 50%, 75%, 100%, 75%, 50%, 25%, and 0% of full-scale
differential pressure consecutively to the instrument without overshoot.
Lightly tap the indicator to overcome friction. The pointer should accu-
rately indicate each applied pressure.
11. Test the instrument repeatability by applying 0%, 50%, 0%, 50% of full-
scale differential pressure. The indicator should accurately indicate each
applied pressure.
12. Set the drive arm stop to prevent the pointer from striking the post lock
on the scale.
13. Test the pointer for tightness per the pointer installation instructions on
Pointer Installation, page 13.
14. If the drive arm screw has been loosened, check for tightness by perform-
ing the Drive Arm Tightness Test described below.
15. Reassemble the unit per the cover installation instructions on Bezel/Lens
(or Cover) Installation and Removal, page 12.
Drive Arm Tightness Test
This procedure tests the tightness of the drive arm's connection to the torque
tube by applying torque developed by the DPU onto a xed drive arm. Ap-
ply pressure slowly, as torque is being applied to the connection through the
torque tube drive shaft.
1. With the pointer at normal 0% torque tube rotation position (0% on a
normal 0 to 100% scale unit), adjust the drive arm stop bracket (or use
alternate means) to prevent the pointer from moving (the stop bracket
interferes with drive arm movement).
IMPORTANT: On reverse acting/split range units, it will be necessary to pressurize the
DPU to move the pointer to the minimum scale position. On suppressed
units, it will be necessary to apply pressure to establish a reference point
to check for "zero" shift.
2. Pressurize the DPU to full scale DP (100% of full scale range) to apply 8
degrees of equivalent torque to the connection.
3. Observe the shift in the "zero" indication following DPU depressuriza-
tion (as required) and drive arm stop bracket readjusting (to allow free
movement of drive arm and pointer). A downscale (counter-clockwise)
shift in "zero" of greater than 1/2% indicates drive arm slippage, neces-
sitating further clamp block tightening.
Drive Arm Stop Adjustment
1. Apply sufcient pressure to the high-pressure housing to deect the
pointer against the full range post lock on the scale plate.
2. Slide the upper drive arm stop bracket against the drive arm and tighten
the drive arm stop bracket screw.

18
Section 3 Model 580A Differential Pressure Switch
3. Apply sufcient pressure to the low pressure housing to deect the
pointer against the zero stop post lock on the scale plate.
4. Bend the zero drive arm stop against the drive arm.
5. Verify calibration as applicable.
SwitchCalibration
Before performing a complete calibration of the switch, perform a calibration
check (See Calibration Check, page 12). If the instrument is out of calibra-
tion, remove the bezel/lens and scale plate and inspect the switch mechanism
(Figure 3.6) to verify the following:
• The roller rotates without wobble or binding.
• The cam does not touch the roller side shields.
• The actuator arm moves freely on its pivot.
• All switch mounting screws are tight.
• Linkages are straight and do not bind at the pivots.
Correct any problems that are observed. If no problems are observed, proceed
with a complete calibration.
SWITCH
ACTUATOR ARM
STOP
SCREW
PLUNGER
SCREW
CAM ROLLER
CAM
Figure 3.6—Switch mechanism
Calibration Setup
1. Connect an output device (lamp or buzzer) to the switch output leads.
2. Connect a test voltage to the switch input terminals on the terminal strip.
(A low voltage is recommended for safety.)
3. Unlock the switch plate and move the plate until the roller is positioned
at the top of the cam.
4. Advance the plunger screw until the switch actuates, then advance the
plunger screw an additional 60° (one at).
5. Exercise the switch roller across the top of the cam to verify steady
operation. Advance the stop screw to touch the switch, then back out the
screw 1.5 turns (9 ats).

19
Model 580A Differential Pressure Switch Section 3
Linkage Calibration Procedure
The switch linkage should be calibrated whenever the Model 580A switch has
been rebuilt.
To calibrate the switch linkage, perform the following steps. Refer to Figure
3.7 as needed.
1. Loosen the three linkage screws and turn the crank to the 12 o’clock
position.
2. Use a 1/8-inch Allen wrench to hold the index shaft and slip the index
pointer to 0 on the switch index. Tighten the screw on the crank to the
mid-slot position to set the crank radius.
3. Turn the index pointer to index number "1" on the outer edge of the
switch index.
4. Apply 10% differential pressure and adjust the switch plate until the
switch actuates. Lock the two linkage screws.
5. Rotate the index pointer to index number “9.” Apply 90% differential
pressure and adjust the crank radius until the switch actuates.
6. Recheck 10% and 90% set points. Adjust the crank radius and the index
pointer until both set points are accurate within a 2% tolerance (nominal).
Figure 3.7—Linkage arrangement
7. If the switch is to be eld-set at low differential pressure values (1% or
2% of pressure range), check the crank to prevent a 12 o'clock position.
Otherwise, the minimum set point position will be restricted and the set
point may become reversed.
8. Adjust the low switch to actuate at the desired pressure by applying test
pressures in a decreasing direction, in discrete steps. Allow the unit and

20
Section 3 Model 580A Differential Pressure Switch
the pressure system to stabilize. Then change the pressure by a small
amount. The magnitude of the pressure change is determined by the
desired accuracy of the test. Tighten the lock screw before testing the
switch performance.
IMPORTANT: The high switch is usually set to actuate at increasing pressure. When
calibrating the high switch, apply test pressure in an increasing direction.
This amount of loading will prevent cam-runout of a similar condition.
IMPORTANT: Excessive plunger loading (more than 3 ats) may cause the roller to
drag on the cam. Cam friction will be apparent by excessive hysteresis,
erratic pointer readings, and inconsistent switch response.
9. Check the switch deadband, (actuate to reset) by applying differential
pressure, rst in a decreasing direction, then in an increasing direction
(opposite for high switch direction). Observe pressures. To reduce the
deadband, advance the plunger screw by no more than two ats.
10. Adjust the high switch to actuate at the desired pressure. The procedure is
the same as for the low switch.
ChangingSwitchSetPoint
(Tools: Screwdriver, 1/8-in. hex Allen wrench)
Denitions of Terms
Set Point. The measured pressure at which the snap-switch actuates and
thereby changes the states of the N.O. and N.C. contacts. For example, the set
point of the low switch is 24 psid with decreasing pressure.
Deadband. The difference in measured pressures between switch-actuation
and switch-reset. Deadband is usually expressed as percentage of full scale
(% of F.S.). Deadband is not adjustable. For example, the switch in the
example above was found to reset at 26.4 psid with increasing pressure. The
deadband was 2.4 psi, or 4% of the full scale for a unit calibrated 0 to 60 psid.
Best Practices for Set Points
1. Always check the set point after tightening switch lock screws.
2. Switch setpoints may be set at any point of the scale range, except in a
location that will prevent the deadband from enabling the switch to reset
itself. For example, the high switch (right side of scale) may be set at
full scale, but should not be set near zero. The low switch may be set at
zero, but should not be set near full scale. (Observe deadband values for
specic models).
3. If switch performance is unsatisfactory (set point does not repeat, dead-
band is excessive, pointer exhibits hysteresis, contacts are unstable, etc.),
This manual suits for next models
1
Table of contents
Other Cameron Switch manuals
Popular Switch manuals by other brands

Siemens
Siemens 3VW9011-0AG01 operating instructions

Weco
Weco ESS LV-HUB XP manual

Link electronics
Link electronics Vertical Blanking Insertion IEC-787 Specification sheet

NETGEAR
NETGEAR GS105v5 installation guide

Endress+Hauser
Endress+Hauser Liquiphant FTL64 operating instructions

H3C
H3C S6890 Series OpenFlow Command Reference