manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Carrier
  6. •
  7. Air Conditioner
  8. •
  9. Carrier 50ZP036300 User manual

Carrier 50ZP036300 User manual

50ZP
10
SEER
Single
Packaged
Air
Conditioner
3-—5
Nominal
Tons
(Sizes
036—060)
turn
to
the
experts
UNIT
SHIPPED
DRY,
CHARGE
WITH
R-—22
REFRIGERANT
BEFORE
START—UP
Installation
NOTE:
Read
the
entire
instruction
manual
before
starting
the
installation.
TABLE
OF
CONTENTS
PAGE
SAFETY
CONSIDERATIONS
........
0.00.00
ce
eee
eee
1
General
2...
eee
eee
2
RECEIVING
AND
INSTALLATION
...............005
5-9
Check
Equipment
..
0.0.0...
00.
eee
eee
5
Identify
Unit
2...
ene
5
Inspect
Shipment
.....
0.0.0...
.
eee
eee
5
Provide
Unit
Support
..
2.0.0...
eee
ee
eee
5
Slab
Mount
2.00.0...
0.
0c
eee
5
Provide
Clearances
2.0...
0...
eee
eee
5
Place
Unit
2.0.0...
eee
ene
5
Select
and
Install
Ductwork...
0...
ee
5
Install
Flanges
for
Ductwork
Connections
(SOZP060
only)
.
5
Converting
Horizontal
Discharge
Units
to
Downflow
(Vertical)
Discharge
2.0.0...
ee
eee
eens
6
Charging
Unit
..
0.0...
0...
ee
6
Provide
for
Condensate
Disposal
..
2.0.0.0...
0.000.000
05
6
Install
Electrical
Connections
©...
0.0...
eee
8
High
Voltage
Connections
..
0.0.0...
0.0.0
e
eevee
eee
8
Routing
Power
Leads
into
Unit...
0.0.0.0...
0.
0.00000-
8
Connecting
Ground
Lead
to
Unit
Ground
..............
8
Routing
Control
Power
Wires
.
2.0.0.0...
0.000000
ee
eee
8
Special
Procedures
for
208-V
Operation
...............
9
PRE-START-UP
..
0.2...
eee
9
START-UP...
ee
10-11
MAINTENANCE
.....
0.0.00
.0.
000000
eee
eee
11-13
TROUBLESHOOTING
.............0.0
000000
eee
13
START-UP
CHECKLIST
................0.
0.0
.000005
13
NOTE:
TO
INSTALLER
-
Before
the
installation
,
READ
THESE
INSTRUCTIONS
CAREFULLY
AND
COMPLETELY.
Also,
make
sure
the
User’s
Manual
is
left
with
the
unit
after
installation.
SAFETY
CONSIDERATIONS
Improper
installation
adjustment,
alteration,
service,
maintenance,
or
use
can
cause
explosion,
fire,
electrical
shock,
or
other
conditions
which
may
cause
death,
personal
injury,
or
property
damage.
Consult
a
qualified
installer,
service
agency,
or
your
distributor
or
branch
for
information
or
assistance.
The
qualified
installer
or
agency
must
use
factory-authorized
kits
or
accessories
when
modifying
this
product
Refer
to
the
individual
instructions
packaged
with
the
kits
or
accessories
when
installing.
Instructions
2
°
e
L
Mf
MLL
ELE
LLL
a
fe
ML
|
LL
AKI
G
AE
Aa
MMM
AT
AI
AUC
LMM
Mt
\
ss
00001
Fig.
1
-
50ZP
(Size
036
Shown)
Follow
all
safety
codes.
Wear
safety
glasses,
protective
clothing,
and
work
gloves.
Use
quenching
cloth
for
brazing
operations.
Have
a
fire
extinguisher
available.
Read
these
instructions
thoroughly
and
follow
ail
warnings
or
cautions
included
in
literature
and
attached
to
the
unit.
Consult
local
building
codes,
the
current
editions
of
the
National
Electrical
Code
(NEC)
NFPA
70.
In
Canada
refer
to
the
current
editions
of
the
Canadian
Electrical
Code
CSA
C22.1.
Recognize
safety
information.
This
is
the
safety-alert
symbol
AY
When
you
see
this
symbol
on
the
unit
and
in
instructions
or
manuals,
be
alert
to
the
potential
for
personal
injury.
Understand
these
signal
words;
DANGER,
WARNING,
and
CAUTION.
These
words
are
used
with
the
safety-alert
symbol.
DANGER
identifies
the
most
serious
hazards
which
will
result
in
severe
personal
injury
or
death.
WARNING
signifies
hazards
which
could
result
in
personal
injury
or
death.
CAUTION
is
used
to
identify
unsafe
practices
which
may
result
in
minor
personal
injury
or
product
and
property
damage.
NOTE
is
used
to
highlight
suggestions
which
will
result
in
enhanced
installation,
reliability,
or
operation.
ELECTRICAL
SHOCK
HAZARD
Failure
to
follow
this
warning
could
result
in
personal
injury
or
death.
Before
installing
or
servicing
system,
always
turn
off
main
power
to
system
and
install
lockout
tag.
There
may
be
more
than
one
disconnect
switch.
11.57
16.06
[294.0]
[408.0]
p=
REQUIRED
CLEARANCE
TO
COMBUSTIBLE
MATL.
TOP
OF UNIT
DUCT
SIDE
OF
UNIT...
SIDE
OPPOSITE
DUCTS
BOTTOM
OF
UNIT
INCHES
[mm]
NEC.
REQUIRED
CLEARANCES.
INCHES
[rnm]
BETWEEN
UNITS,
POWER
ENTRY
SIDE...
ee
42,00
[1066.8]
°
UNIT
AND
UNGROUNDED
SURFACES,
POWER
ENTRY
SIDE
.36.00
[914.0]
UNIT
AND
BLOCK
OR
CONCRETE
WALLS
AND
OTHER
GROUNDED
SURFACES,
POWER
ENTRY
SIDE......000000...
42,00
[1066.8]
9.75
REQUIRED
CLEARANCE
FOR
OPERATION
AND
SERVICING
[247.6]
.
INCHES
[m
m|
CONDENSER
COIL
ACCESS
SIDE...
[
POWER
ENTRY
SIDE
00
[
ft
(EXCEPT
FOR
NEC
REQUIREMENTS)
UNIT
TOP
00
[1219.2]
SIDE
OPPOSITE
DUCTS
0
[762.0]
14.0 DIA.
LEGEND
[356.0]
REAR
VIEW
DUCT
OPENINGS
NEC
—
National
Electrical
Code
50.98
NOTES:
[1295.0]
.
Clearances
must
be
maintained
to
prevent
recirculation
of
air
from
outdoor
BOTTOM
OF
UNIT
fan
discharge,
with
the
exception
of
the
condenser
coil
(36.00
in
[914.0
mm],
A
removable
fence
or
barricade
requires
no
clearance,
EVAP,
COIL
i ¢
2,
Dimensions
are
in
inches.
Dimensions
in
[]
are
in
millimeters.
COND
H
COIL
oN
rt
m m m
31.99
[812.5]
BOTTOM
OF
UNIT
<<
BLOWER,
CONTROL
BOX
AND
EVAP.
ACCESS
PANEL
COMPRESSOR
PANEL
FIELD
ENTRY
TO
SERVICE
PORTS
COIL
272
21.61
[69.0]
[594.0]
1.75 DIA.
[44.5]
17.60
[447.0]
,
.
h
.
.
i
La.
20
[30.6]
19.61
2.50
LEFT
SIDE
VIEW
FRONT
VIEW
[498.1]
[63.5}
1.0540
1.DB
x
50
DEEP
[26.772
x
12.7]
RIGHT
SIDE
VIEW
Co00002
Fig.
2
-
Base
Unit
Dimensions,
50ZP036
UNIT
WEIGHT CENTER
OF
GRAVITY
IN.
(MM)
UNIT
ELECTRICAL
CHARACTERISTICS
ib
kg
X
Y
Zz
50ZP036
208/230-1-60,
208/230-3-60
234
406
(3:00)
(0.00)
(0.50)
bo
__
11.57
[294.0]
Eos
REQUIRED
CLEARANCE
TO
COMBUSTIBLE
MATL.
TOP
OF
UNIT...
DUCT
SIDE
OF
SIDE
OPPOSITE
DU:
BOTTOM
OF
UNIT........
INCHES
[mm]
2000
NEC.
REQUIRED
CLEARANCES.
INCHES
[mm]
BETWEEN
UNITS,
POWER
ENTRY
SIDE..
2.00
[1066.8}
UNIT
AND
UNGROUNDED
SURFACES,
POWER
ENTRY
‘SIDE
38.
00
[914.0]
UNIT
AND
BLOCK
OR
CONCRETE
WALLS
AND
OTHE
GROUNDED
SURFACES,
POWER
ENTRY
GE
42.00
[1066.8}
REQUIRED
CLEARANCE
FOR
OPERATION
AND
SERVICING
INCHES
[mm]
CONDENSER
COIL
ACCESS
SIDE
POWER
ENTRY
SIDE
(EXCEPT
FOR NEC
REQUIREMENT
UNIT
TOP
SIDE
OPPOSITE
DUCT:
30.00
[762.0]
«30.00
[762.0}
48.00
[1219.2]
9.75
0.00
[762.0]
[247.6]
LEGEND
J
#
NEC
-
National
Electrical
Code
14.0
DIA.
NOTES:
REAR
VIEW
[356.0]
1.
Clearances
must
be
maintained
to
prevent
recirculation
of
air
from
outdoor-
DUCT
OPENINGS
fan
discharge,
with
the
exception
of
the
condenser
coil
(36.00
in
[914.0
mm].
A
removable
fence
or
barricade
requires
no
clearance.
2.
Dimensions
are
in
inches.
Dimensions
in []
are
in
millimeters.
50.98
[1295.0]
BOTTOM
OF
UNIT
EVAPORATOR
COIL
CONDENSER
|
b
COIL
L
J
TT
||
|
Lota
F
||
If
31.99
|
i
[812.5]
|
iy
t6
BOTTOM
OF
UNIT
|
||
~
lI
e
ils
COM
\
BLOWER,
CONTROL
BOX
AND
EVAPORATOR
COIL
ACCESS
PANEL
2.72
21.64
[69.0]
[549.0]
0.88
DIA.
[22.2]
\
.
\_1.75
DIA.
-
25.60.
|
[650.2]
[44.5]
,
||
.
beg
/
19.61
2.50
_f
[498.1]
[63.5]
LEFT
SIDE
VIEW
FRONT
VIEW
1.0540
1.D.
x
.50
DEEP
[26.772
x
12.7]
RIGHT
SIDE
VIEW
C00003
Fig.
3
-
Base
Unit
Dimensions,
50ZP048
UNIT
WEIGHT CENTER
OF
GRAVITY
IN.
(MM)
UNIT
ELECTRICAL
CHARACTERISTICS
ib
kg
X
Y
Z
50ZP048
208/230-1-60,
208/230-3-60
308
440
(3:00)
(0.00)
(12.60)
DIMENSIONS
IN
[]
ARE
IN
mm
13.89
—
[352.7]
REQUIRED
CLEARANCE
TO
COMBUSTIBLE
MATL.
4.63
_.
13.89
e
(e211
INCHES
[mm]
[117.6]
[352.8]
153.7]
TOP
OF
UNIT
0
DUCT
SIDE
OF
UNIT..
0
SIDE
OPPOSITE
DUCTS...
0
BOTTOM
OF
UNIT
0
P
ia
=
NEC.
REQUIRED
CLEARANCES.
INCHES
[mm]
BETWEEN
UNITS,
POWER
ENTRY
SIDE...
eee
42,00
[1066.8]
UNIT
AND
UNGROUNDED
SURFACES,
POWER
ENTRY
SIDE
.36.00
[914.0]
|
UNIT
AND
BLOCK
OR
CONCRETE
WALLS
AND
OTHER
GROUNDED
SURFACES,
POWER
ENTRY
SIDE...
42.00
[1066.8]
I
ce
=
3
do
REQUIRED
CLEARANCE
FOR
OPERATION
AND
SERVICING
27-80
INCHES
[mm]
:
-
[708.0]
CONDENSER
COIL
ACCESS
SIDE...
...30.00
[762.0]
:
POWER
ENTRY
SIDE
»,..30,00
[762.0]
13.88
4
(EXCEPT
FOR
NEC
REQUIREMENTS)
[352.5]
7
4]
UNIT
TOP
48.00
[1219.2]
i
SIDE
OPPOSITE DUCTS
»,..30.00
[762.0]
i
.
.
|:
5.44
; a
LEGEND
*
-
i i
NEC
—
National
Electrical
Code
8.50
NOTES:
88.9
.
REAR
VIEW
f ]
1.
Clearances
must
be
maintained
to
prevent
recirculation
of
air
from
outdoor-
fan
discharge,
with
the
exception
of
the
condenser
coil
(86.00
in
[914.0
mm].
A
removable
fence
or
barricade
requires
no
clearance.
50.98
2.
Dimensions
are
in
inches.
Dimensions
in
[]
are
in
millimeters.
[1295.0]
BOTTOM
OF
UNIT
31.99
[812.5]
BOTTCK
OF
UNIT
NN
NS
S
SN,
N
.
AND
EVAP.
COIL
27200
21.61
-
69.0
[549.0]
COMPRESSOR
PANEL
\
F
5
1.75
DIA.
232)
iA.
[44.5]
\
,
\
i
_
a
oN
N/
\
34.13
[*
[867.0]
2960
|
[751.8]
1
1.20
LEFT
SIDE
VIEW
FRONT
VIEW
20S
|
geet
00
[25.4]
1,0540
1.D.
x
.50
DEEP~
(26.772
x
12.7]
RIGHT
SIDE
VIEW
coo004
Fig.
4
-
Base
Unit
Dimensions,
50ZP060
UNIT
WEIGHT CENTER
OF
GRAVITY
IN.
(MM)
UNIT
ELECTRICAL
CHARACTERISTICS
ib
kg
X
Y
Z
50ZP060
208/230-1-60,
208/230-3-60
344
156
(3:00)
(0.00)
(3:00)
4
CAUTION
CUT
HAZARD
Failure
to
follow
this
caution
may
result
in
personal
injury.
Sheet metal
parts
may
have
sharp
edges
or
burrs.
Use
care
and
wear
appropriate
clothing.
These
instructions
cover
minimum
requirements
and
conform
to
existing
national
standards
and
safety
codes.
In
some
instances,
these
instructions
exceed
certain
local
codes
and
ordinances,
especially
those
that
may
not
have
kept
up
with
changing
residential
construction
practices.
We
require
these
instructions
as
a
minimum
for a
safe
installation.
GENERAL
—
50ZP
cooling
units
are
fully
self-contained
and
designed
for
outdoor
installation.
See
Fig.
1.
As
shown
in
Fig.
2-4,
units
are
shipped
in
a
horizontal-discharge
configuration
for
installation
on
a
ground-level
slab.
All
units
can
be
field-converted
to
downflow
discharge
configurations
for
rooftop
applications
with
a
field-supplied
plenum
RECEIVING
AND
INSTALLATION
Step
1
—
Check
Equipment
IDENTIFY
UNIT
—
The
unit
model
number
and
serial
number
are
stamped
on
the
unit
identification
plate.
Check
this
information
against
shipping
papers.
INSPECT
SHIPMENT
—
Inspect
for
shipping
damage
while
unit
is
still
on
shipping
pallet.
If
unit
appears
to
be
damaged
or
is
torn
loose
from
its
securing
points,
have
it
examined
by
transportation
inspectors
before
removal.
Forward
claim
papers
directly
to
transportation
company.
Manufacturer
is
not
responsible
for
any
damage
incurred
in
transit.
Check
all
items
against
shipping
list.
Immediately
notify
the
nearest Carrier
Air
Conditioning
office
if
any
item
is
missing.
To
prevent
loss
or
damage,
leave
all
parts
in
original
packages
until
installation.
Step
2
—
Provide
Unit
Support
SLAB
MOUNT
—
Place
the
unit
on
a
rigid,
level
surface,
suitable
to
support
the
unit
weight.
The
flat
surface
should
extend
approximately
2-in.
(51
mm)
beyond
the
unit
casing
on
the
2
sides.
The
duct
connection
side
and
condensate
drain
connection
sides
should
be
flush
with
the
edge
of
the
flat
surface.
A
concrete
pad
or
a
suitable
fiberglass
mounting
pad
is
recommended.
A
6-in.
(152
mm)
wide
gravel
apron
should
be
used
around
the
flat
surface
to
prevent
airflow
blockage
by
grass
or
shrubs.
Do
not
secure
the
unit
to
the
flat
surface
except
where
required
by
local
codes.
The
unit
should
be
level
to
within
1/4
in.
(6
mm).
This
is
necessary
for
the
unit
drain
to
function
properly.
Step
3
—
Provide
Clearances
The
required
minimum
service
clearances
and
clearances
to
combustibles
are
shown
in
Fig.
2-4.
Adequate
ventilation
and
condenser
air
must
be
provided.
The
condenser
fan
pulls
air
through
the
condenser
coil
and
discharges
it
through
the
fan
on
the
top
cover.
Be
sure
that
the
fan
discharge
does
not
recirculate
to
the
condenser
coil.
Do
not
locate
the
unit
in
either
a
corner
or
under
an
overhead
obstruction.
The
minimum
clearance
under
a
partial
overhang
(such
as
a
normal
house
overhang)
is
48
in.
(1219
mm)
above
the
unit
top.
The
maximum
horizontal
extension
of
a
partial
overhang
must
not
exceed
48
in.
(1219
mm).
Do
not
place
the
unit
where
water,
ice,
or
snow
from
an
overhang
or
roof
will
damage
or
flood
the
unit.
The
unit
may
be
installed
on
wood
flooring
or
on
Class
A,
B,
or
C
roof
covering
materials.
Step
4
—
Place
Unit
Unit
can
be
moved
with
the
handholds
provided
in
the
unit
basepan.
Refer
to
Table
1
for
operating
weights.
Use
extreme
caution
to
prevent
damage
when
moving
the
unit.
Unit
must
remain
in
an
upright
position
during
all
moving
operations.
The
unit
must
be
level
for
proper
condensate
drainage;
the
ground-level
pad
must
be
level
before
setting
the
unit
in
place.
When
a
field-fabricated
support
is
used,
be
sure
that
the
support
is
level
and
that
it
properly
supports
the
unit.
Step
5
—
Select
and
Install
Ductwork
The
design
and
installation
of
the
duct
system
must
be
in
accordance
with:
*
the
standards
of
the
NFPA
(National
Fire
Protection
Association)
for
installation
of
nonresidence-type
air
conditioning
and
ventilating
systems;
¢
NFPA9OA
or
residence-type,
NFPA90B;
and/or
local
codes
and
residence-type,
NFPA
90B;
¢
and/or
local
codes
and
ordinances.
Select
and
size
ductwork,
supply-air
registers
and
return-air
grilles
according
to
ASHRAE
(American
Society
of
Heating,
Refrigeration,
and
Air
Conditioning
Engineers)
recommendations.
Use
the
duct
flanges
provided
on
the
supply-
and
return-air
openings
on
the
side
of
the
unit.
See
Fig.
2-4
for
connection
sizes
and
locations.
The
14-in.
(356
mm)
round
duct
collars
(size
036-048
units)
are
shipped
inside
the
unit
attached
to
the
indoor
blower.
They
are
field-installed
and
must
be
removed
from
the
indoor
cavity
prior
to
start-up,
even
if
they
are
not
used
for
installation.
INSTALL
FLANGES
FOR
DUCTWORK
CONNECTIONS
(S0ZP060
ONLY)
—
The
50ZP060
units
are
shipped
with flanges
which
must
be
field-installed
on
the
unit.
To
install
unit
flanges:
1.
Five
pieces
of
flange
are
shipped
on
the
return-air
opening
of
the
unit.
Remove
the
flanges
from
the
shipping
position.
See
Fig.
5.
Screws
are
field-supplied.
bo
.
One
piece
of
flange
is
used
as
it
is
shipped
(straight).
Bend
the
other
4
pieces
at
right
angles.
3.
Install
the
straight
flange
on
the
right
side
of
the
return-air
opening
in
holes
provided.
See
Fig.
6.
Flanges
should
stick
out
from
unit
to
allow
for
connection
of
ductwork.
4.
Install
2
hand-formed
flanges
onto
return
air
opening
in
holes
provided
to
form
a
rectangle
around
the
return
air
opening.
5.
Install
remaining
2
hand-formed
flanges
around
discharge
air
opening
in
holes
provided.
6.
Ductwork
can
now
be
attached
to
flanges.
When
designing
and
installing
ductwork,
consider
the
following:
UNIT
DAMAGE
HAZARD
Failure
to
follow
this
caution
may
result
in
damage
to
unit
components.
When
connecting
ductwork
to
units,
do
not
drill
deeper
than
3/4
in.
(19.1
mm)
in
shaded
area
shown
in
Fig.
7
or
coil
may
be
damaged.
e¢
All
units
should
have
field-supplied
filters
installed
in
the
return-air
side
of
the
unit.
Recommended
sizes
for
filters are
shown
in
Table
1.
¢
Avoid
abrupt
duct
size
increases
and
reductions.
Abrupt
change
in
duct
size
adversely
affects
air
performance.
Use
flexible
connectors
between
ductwork
and
unit
to
prevent
transmission
of
vibration.
Use
suitable
gaskets
to
ensure
weathertight
and
airtight
seal.
5
¢
Size
ductwork
for
cooling
air
quantity
(CFM).
¢
Insulate
and
weatherproof
all
external
ductwork.
Insulate
and
cover
with
a
vapor
barrier
all
ductwork
passing
through
conditioned
spaces.
Follow
latest
Sheet
Metal
and
Air
Conditioning
Contractors
National
Association
(SMACNA)
and
Air
Conditioning
Contractors
Association
(ACCA)
minimum
installation
standards
for
residential
heating
and
air
conditioning
systems.
¢
Secure
all
ducts
to
building
structure.
Flash,
weatherproof,
and
vibration-isolate
duct
openings
in
wall
or
roof
according
to
good
construction
practices.
Fig.
8
shows
a
typical
duct
system
with
5OZP
unit
installed.
FIVE
PIECES
OF
DUCT
FLANGE
ATTACHED
HERE
FOR
SHIPMENT
00005
Fig.
5
-
Shipping
Location
of
Duct Flanges
(Size
060
Only)
00006
Fig.
6
-
Flanges
Installed
on
50ZP060
Units
Converting
Horizontal
Discharge
Units
to
Downflow
(Vertical)
Discharge
CE
UA
Le:
ELECTRICAL
SHOCK
HAZARD
Failure
to
follow
this
warning
could
result
in
personal
injury
or
death.
Before
performing
service
or
maintenance
operations
on
the
system,
turn
off
main
power
to
unit
and
install
lockout
tag.
There
may
be
more
than
one
disconnect
switch.
Units
are
dedicated
side
supply
products.
They
are
not
convertible
to
vertical
air
supply.
A
field-supplied
plenum
must
be
used
to
convert
to
vertical
air
discharge.
Step
6
—
Charging
Unit
Unit
is
shipped
with
a
nitrogen
holding
charge
only.
Slowly
release
nitrogen
charge
from
unit
using
service
gages
and
using
a
vacuum
pump
evacuate
unit
to
500
microns
or
lower.
To
locate
charging
ports,
remove
top
panel
which
provides
access
to
control
box
and
blower.
Charging
ports
are
located
under
top
panel.
Charge
unit
by
weight
using
an
electronic
scale.
R-22
charge
quantity
can
be
found
in
table
1
and
on
unit
rating
plate.
Do
not
over
charge.
Step
7
—
Provide
for
Condensate
Disposal
NOTE:
Be
sure
that
condensate-water
disposal
methods
comply
with
local
codes,
restrictions,
and
practices.
Unit
removes
condensate
through
a
1-3/64
-in.
(26.6
mm)
ID
hole
which
is
located
at
the
end
of
the
unit.
See
Fig.
2-4
for
location
of
condensate
connection.
19.17"
3.92"
se)
(486.9
mm)
(99.6
mm)
a
nuvi
EY
aN
ay
NY,
Ae
i
SSS
p
i
aN
HAA
CD
C00007
Fig.
7
-
Area
Not
to
Be
Drilled
More
Than
3/4-in.
[@[s)
THERMOSTAT
"se
DISCONNECT
PER
NEC*
ie
COMPOSITE
pect
RUST-PROOF
—
col
RS
BASEPAN
——
~
CONDENSATE
CONNECTION
mmm
Power
Wiring
Control
Wiring
»>
Condenser
Airflow
:
>
Evaporator
Airflow
*Separate
disconnect
per
NEC
(National
Electrical
Code)
A10018
Fig.
8
-
Typical
Installation
Table
1
-
Physical
Data
UNIT 50ZP
036 048 060
SHIPPING
WEIGHT
(Ibs)
278
352 388
(kg)
126 160 176
COMPRESSOR
TYPE
Reciprocating
Scroll
Reciprocating
REFRIGERANT
R22
Charge
(Ib)
4.2
5.5
6.9
(kg)
1.9
25
3.4
REFRIGERANT
METERING
DEVICE
Acutrol™
Device
Piston
CONDENSER
COIL
Copper
Tubes,
Aluminum
Plate
Fins
Rows...Fins/in.
2.17
2.17 2.17
Face
Area
(sq
ft)
6.2 8.6
10.7
CONDENSER-FAN
Propeller
Propeller
MOTOR
CFM
2000 2600 2800
Nominal
Rpm
1100 1100 1100
Motor
Hp
1/4
1/4
1/4
Diameter
(in.)
20 20 20
(mm)
508
508 508
EVAPORATOR
COIL
Copper
Tubes,
Aluminum
Plate
Fins
Rows...Fins/in.
3...15 3...15
4.15
Face
Area
(sq
ft)
3.1
4.3
49
EVAPORATOR
FAN
MOTOR
Direct
Drive
Blower
Motor
Size
(in.)
10x8 10x9
10x10
(mm)
254
x
203
254
x
229 254
x
254
Nominal
CFM
1200 1650 1700
Rpm
Range
800-1050
1000-1100
950-1100
Number
of
Speeds
3
2
3
Factory
Speed
Setting
Low Low Low
Motor
Hp
1/2
3/4
1
CONNECTING
DUCT
SIZES
Round
Square
Supply
Air
(in.)
14
13.9x
13.9
(mm)
356
353
x
353
Return
Air
(in.)
14
13.9
x
27.8
(mm)
356
353
x
706
FIELD-SUPPLIED
RETURN-AIR
FILTERt
Throwaway
(in.)
24
x
24 24
x
30
(mm)
610
x
610
610
x
762
tRequired
filter
sizes
shown
are
based
on
the
AHRI
(Air
Conditioning,
Heating
and
Refrigeration
Institute)
rated airflow
at
a
velocity
of
300
ft/min
for
throwaway
type
or
450
ft/min
for
high
capacity
type.
Recommended
filters
are
1—in.
(25
mm)
thick.
1”
(25
mm)
MIN,
V
TRAP
OUTLET
Y
2”
(51
mm)
MIN.
A08001
Condensate
Trap
(Using
Tubing)
\
PN
l-in.
5
mm)
min.
i
TRAP
OUTLET
<¢—
A
2-in.
(51
mm)
min.
t
A09052
Condensate
Trap
(Using
PVC
Piping)
Fig.
9
-
Condensate
Trap
HIGH-VOLTAGE
~=LOW-VOLTAGE
POWER
WIRING WIRING
ENTRY
ENTRY
HOLE
HOLE
Fig.
10
-
Unit
Electrical
Connection
Entry
Holes
00010
Condensate
water
can
be
drained
directly
onto
the
roof
in
rooftop
installations
(where
permitted)
or
onto
a
gravel
apron
in
ground
level
installations.
Install
a
field-supplied
condensate
trap
at
end
of
condensate
connection
to
ensure
proper
drainage.
Make
sure
that
the
outlet
of
the
trap
is
at
least
1
in.
(25
mm)
lower
than
the
drain-pan
condensate
connection
to
prevent
the
pan
from
overflowing.
See
Fig.
9.
Prime
the
trap
with
water.
When
using
a
gravel apron,
make
sure
it
slopes
away
from
the
unit.
If
the
installation
requires
draining
the
condensate
water
away
from
the
unit,
install
a
2-in.
(51
mm)
trap
using
a
3/4
-in.
OD
tubing
or
pipe.
See
Fig.
9.
Make
sure
that
the
outlet
of
the
trap
is
at
least
1
in.
(25
mm)
lower
than
the
unit
drain-pan
condensate
connection
to
prevent
the
pan
from
overflowing.
Prime
the
trap
with
water.
Connect
a
drain
tube
using
a
minimum
of
3/4
-in.
PVC,
3/4
-in.
CPVC,
or
3/4
-in.
copper
pipe
(all
field
supplied).
Do
not
undersize
the
tube.
Pitch
the
drain
tube
downward
at
a
slope
of
at
least
1
in.
(25
mm)
for
every
10
ft
(3
m)
of
horizontal
run.
Be
sure
to
check
the
drain
tube
for
leaks.
Prime
trap
at
the
beginning
of
the
cooling
season
start-up.
Allowable
glues
for
condensate
trap
connection
are:
Standard
ABS,
CPVC,
or
PVC
cement.
Step
8
—
Install
Electrical
Connections
4
WARNING
ELECTRICAL
SHOCK
HAZARD
Failure
to
follow
this
warning
could
result
in
personal
injury
or
death.
The
unit
cabinet
must
have
an
uninterrupted,
unbroken
electrical
ground
to
minimize
the
possibility
of
personal
injury
if
an
electrical
fault
should
occur.
This
ground
may
consist
of an
electrical
wire
connected
to
the
unit
ground
screw
in
the
control
compartment,
or
conduit
approved
for
electrical
ground
when
installed
in
accordance
with
NEC,
ANSI/NFPA
70
American
National
Standards
Institute/
National
Fire
Protection
Association
(latest
edition)
(in
Canada,
Canadian
Electrical
Code
CSA
C22.1)
and
local
electrical
codes.
4
CAUTION
UNIT
COMPONENT
DAMAGE
HAZARD
Failure
to
follow
this
caution
may
result
in
damage
to
the
unit
being
installed.
1.
Make
all
electrical
connections
in
accordance
with
NEC
ANSI/NFPA
70
(latest
edition)
and
local
electrical
codes
governing
such
wiring.
In
Canada,
all
electrical
connections
must
be
in
accordance
with
CSA
standard
C22.1
Canadian
Electrical
Code
Part
1
and
applicable
local
codes.
Refer
to
unit
wiring
diagram.
bo
.
Use
only
copper
conductor
for
connections
between
field-supplied
electrical
disconnect
switch
and
unit.
DO
NOT
USE
ALUMINUM
WIRE.
3.
Be
sure
that
high-voltage
power
to
unit
is
within
operating
voltage
range
indicated
on
unit
rating
plate.
On
3-phase
units,
ensure
phases
are
balanced
within
2
percent.
Consult
local
power
company
for
correction
of
improper
voltage
and/or
phase
imbalance.
4.
Do
not
damage
internal
components
when
drilling
through
any
panel
to
mount
electrical
hardware,
conduit,
etc.
HIGH-VOLTAGE
CONNECTIONS
—
The
unit
must
have
a
separate
electrical
service
with
a
field-supplied,
waterproof
disconnect
switch
mounted
at,
or
within
sight
from
the
unit.
Refer
to
the
unit
rating
plate
for
maximum
fuse/circuit
breaker
size
and
minimum
circuit
amps
(ampacity)
for
wire
sizing.
The field-supplied
disconnect
may
be
mounted
on
the
unit
over
the
high-voltage
inlet
hole.
See
Fig.
2-4.
Operation
of
unit
on
improper
line
voltage
constitutes
abuse
and
may
cause
unit
damage
that
could
affect
warranty.
ROUTING
POWER
LEADS
INTO
UNIT
—
Use
only
copper
wire
between
disconnect
and
unit.
The
high-voltage
leads
should
be
in
a
conduit
until
they
enter
the
unit;
conduit
termination
at
the
unit
must
be
watertight.
Run
the
high-voltage
leads
through
the
hole
on
the
contro!
box
side
of
the
unit (see Fig.
10
for
location).
When
the
leads
are
inside
the
unit,
run
leads
to
the
control
box
(Fig.
11).
For
single-phase
units,
connect
leads
to
the
black
and
yellow
wires;
for
3-phase
units,
connect
the
leads
to
the
black,
yellow,
and
blue
wires
(see Fig.
12).
CONNECTING
GROUND
LEAD
TO
UNIT
GROUND
—
Refer
to
Fig.
11
and
12.
Connect
the
ground
lead
to
the
chassis
using
the
unit
ground
lug
in
the
control
box.
COMPRESSOR
CONTACTOR
TRANSFORMER
GROUND
INDOOR
OUTDOOR
FAN
MOTOR
HIGH
LUG FAN
AND
COMPRESSOR
VOLTAGE
RELAY START
CAPACITOR
LEADS
At10019
Fig.
11
-
Control
Box
Wiring
UNIT
GROUND
GROUND
~~
Teap
f
SINGLE-PHASE
|)
20
dg
Ke
3-PHASE
CONNECTIONS
CONNECTIONS
JTODISCONNECT),
_
A
YEL-
TO
DISCONNECT
|PER
NEC
PER
NEC
L------4
~
BLu-
C00012
Fig.
12
-
Line
Power
Connections
ROUTING
CONTROL
POWER
WIRES
—
Form
a
drip-loop
with
the
thermostat
leads
before
routing
them
into
the
unit.
Route
the
thermostat
leads
through
grommeted
hole
provided
in
unit (see
Fig.
10)
into
unit
control
box.
Connect
thermostat
leads
to
unit
control
power
leads
as
shown
in
Fig.
13.
Route
thermostat
wires
through
grommet
providing
a
drip-loop
at
the
panel.
Connect
low-voltage
leads
to
the
thermostat
as
shown
in
Fig.
13.
The
unit
transformer
supplies
24-v
power
for
complete
system.
Transformer
is
factory
wired
for
230-v
operation.
If
supply
voltage
is
208
v,
rewire
transformer
primary
as
described
in
the
Special
Procedures
for
208-v
Operation
section
below.
YEL—+
OOO0e
‘
[
UNIT
CONTROL
BOX
THERMOSTAT
AND
SUBBASE
c00018
Fig.
13
-
Control
Connections
SPECIAL
PROCEDURES
FOR
208-V
OPERATION
4
WARNING
ELECTRICAL
SHOCK
HAZARD
Failure
to
follow
this
warning
could
result
in
personal
injury
or
death.
Before
performing
service
or
maintenance
operations
on
the
system,
turn
off
main
power
to
unit
and
install
lockout
tag.
There
may
be
more
than
one
disconnect
switch.
1.
Remove
wirenut from
connection
of
ORG
wire
to
BLK
wire.
Disconnect
the
ORG
transformer-primary
lead
from
the
BLK
wire.
Save
wirenut.
See
unit
wiring
label.
bo
.
Remove
the
wirenut from
the
terminal
on
the
end
of
the
RED
transformer-primary
lead.
3.
Save
the
wirenut.
4.
Connect
the
RED
lead
to
the
BLK
wire
from
which
the
ORG
lead
was
disconnected.
Insulate
with
wirenut from
Step
1.
5.
Using
the
wirenut
removed
from
the
RED
lead,
insulate
the
loose
terminal
on
the
ORG
lead.
6.
Wrap
the
wirenuts
with
electrical
tape
so
that
the
metal
terminals
cannot
be
seen.
Indoor
blower-motor
speeds
may
need
to
be
changed
for
208-v
operation.
Refer
to
Indoor
Airflow
and
Airflow
Adjustments
section.
PRE-START-UP
CE
UA
Le:
FIRE,
EXPLOSION,
ELECTRICAL
SHOCK
HAZARD
Failure
to
follow
this
warning
could
result
in
personal
injury
or
death
and/or
property
damage.
1.
Follow
recognized
safety
practices
and
wear
protective
goggles
when
checking
or
servicing
refrigerant
system.
bo
.
Relieve
and
recover
all
refrigerant
from
system
before
touching
or
disturbing
anything
inside
terminal
box
if
refrigerant
leak
is
suspected
around
compressor
terminals.
3.
Never
attempt
to
repair
soldered
connection
while
refrigerant
system
is
under
pressure.
4.
Do
not
use
torch
to
remove
any
component.
System
contains
oil
and
refrigerant
under
pressure.
5.
To
remove
a
component,
wear
protective
goggles
and
proceed
as
follows:
a.
Shut
off
electrical
power
to
unit
and
install
lockout
tag.
b.
Relieve
and
reclaim
ail
refrigerant
from
system
using
both
high-
and
low-pressure
ports.
c.
Cut
component
connecting
tubing
with
tubing
cutter
and
remove
component
from
unit.
d.
Carefully
unsweat
remaining
tubing
stubs
when
necessary.
Oil
can
ignite
when
exposed
to
flame.
Use
the
Start-Up
Checklist
supplied
at
the
end
of
this
book
and
proceed
as
follows
to
inspect and
prepare
the
unit
for
initial
start-up:
1.
Remove
all
access
panels.
2.
Read
and
follow
instructions
on
all
DANGER,
WARNING,
CAUTION,
and
INFORMATION
labels
attached
to,
or
shipped
with,
unit.
Make
the
following
inspections:
a.
Inspect
for
shipping
and
handling
damages
such
as
broken
lines,
loose
parts,
disconnected
wires,
etc.
b.
Inspect
for
oil
at
all
refrigerant
tubing
connections
and
on
unit
base.
Detecting
oil
generally
indicates
a
refrigerant
leak.
Leak-test
all
refrigerant
tubing
connections
using
electronic
leak
detector,
or
liquid-soap
solution.
If
a
refrigerant
leak
is
detected,
see
following
Check
for
Refrigerant
Leaks
section.
c.
Inspect
all
field-
and
factory-wiring
connections.
Be
sure
that
connections
are
completed
and
tight.
d.
Inspect
coil
fins.
If
damaged
during
shipping
and
handling,
carefully
straighten
fins
with
a
fin
comb.
3.
Verify
the
following
conditions:
a.
Make
sure
that
outdoor-fan
blade
is
correctly
positioned
in
fan
orifice.
Top
edge
of
blade
should
be
3.125
in.
(79.4
mm)
down
from
condenser
outlet
grille.
See
Condenser
Fan
section.
b.
Make
sure
that
air
filter
is
in
place.
c.
Make
sure
that
condensate
drain
pan
and
trap
are
filled
with
water
to
ensure
proper
drainage.
d.
Make
sure
that
all
tools
and
miscellaneous
loose
parts
have
been
removed.
START-UP
Use
the
Start-Up
Checklist
supplied
at
the
end
of
this
book,
and
proceed
as
follows:
Step
1
—
Check
for
Refrigerant
Leaks
LOCATE
AND
REPAIR
REFRIGERANT
LEAKS
AND
CHARGE
THE
UNIT
AS
FOLLOWS:
1.
Using
both
high-
and
low-pressure
ports,
locate
leaks
and
reclaim
remaining
refrigerant
to
relieve
system
pressure.
2.
Repair
leak
following
accepted
practices.
NOTE:
Instail
a
filter
drier
whenever
the
system
has
been
opened
for
repair.
3.
Check
system
for
leaks
using
an
approved
method.
4.
Evacuate
refrigerant
system
and
reclaim
refrigerant
if
no
additional
leaks
are
found.
5.
Charge
unit
with
R-22
refrigerant,
using
a
volumetric-charging
cylinder
or
accurate
scale.
Refer
to
unit
rating
plate
for
required
charge.
Be
sure
to
add
extra
refrigerant
to
compensate
for
internal
volume
of
field-installed
filter
drier.
Step
2
—
Start-Up
Cooling
Section
and
Make
Adjustments
CHECKING
COOLING
CONTROL
OPERATION
—
Start
and
check
the
unit
for
proper
cooling
control
operation
as
follows:
1.
Place
room
thermostat
SYSTEM
switch
in
OFF
position.
Observe
that
blower
motor
starts
when
FAN
switch
is
placed
in
ON
position
and
shuts
down
when
FAN
switch
is
placed
in
AUTO
position.
.
Place
SYSTEM
switch
in
COOL
position
and
FAN
switch
in
AUTO
position.
Set
cooling
control
below
room
temperature.
Observe
that
compressor,
condenser
fan,
and
evaporator
blower
motors
start.
Observe
that
cooling
cycle
shuts
down
when
control
setting
is
satisfied.
bo
3.
When
using
an
automatic
changeover
room
thermostat,
place
both
SYSTEM
and
FAN
switches
in
AUTO.
positions.
Observe
that
unit
operates
in
Cooling
mode
when
temperature
control
is
set
to
“call
for
cooling”
(below
room
temperature).
Step
3
—
Refrigerant
Charge
Amount
of
refrigerant
charge
is
listed
on
unit
nameplate
(also
refer
to
Table
1).
Refer
to
Carrier
Refrigerant
Service
Techniques
Manual,
Refrigerants
section.
Unit
panels
must
be
in
place
when
unit
is
operating
during
charging
procedure.
NO
CHARGE
—
Use
standard
evacuating
techniques.
After
evacuating
system,
weigh
in
the
specified
amount
of
refrigerant
(refer
to
Table
1).
LOW
CHARGE
COOLING
—
Use
Cooling
Charging
Charts,
Fig.
14-16.
Vary
refrigerant
until
the
conditions
of
the
appropriate
chart
are
met.
Note
that
charging
charts
are
different
from
the
type
normally
used.
Charts
are
based
on
charging
the
units
to
the
correct
superheat
for
the
various
operating
conditions.
Accurate
pressure
gage
and
temperature
sensing
device
are
required.
To
measure
suction
pressure,
perform
the
following:
1.
Connect
the
pressure
gage
to
the
service
port
on
the
suction
line.
2.
Mount
the
temperature
sensing
device
on
the
suction
line
and
insulate
it
so
that
outdoor ambient
temperature
does
not
affect
the
reading.
Indoor-air
cfm
must
be
within
the
normal
operating
range
of
the
unit.
TO
USE
COOLING
CHARGING
CHARTS
1.
Take
the
outdoor ambient
temperature
and
read
the
suction
pressure
gage.
bo
.
Refer
to
appropriate
chart
to
determine
what
the
suction
temperature
should
be.
an
.
If
suction
temperature
is
high,
add
refrigerant.
If
suction
temperature
is
low,
carefully
recover
some
of
the
charge.
4.
Recheck
the
suction
pressure
as
charge
is
adjusted.
EXAMPLE:
(Fig.
14)
Outdoor
Temperature
«00...
cee
85°F
(29°C)
Suction
Pressure
.......
ccs
80
psig
Suction
Temperature
should
be
...........
70°F
(21°C)
(Suction
Temperature may
vary
+5°
F,
[2.8°C])
If
Chargemaster©
charging
device
is
used,
temperature
and
pressure
readings
must
be
accomplished
using
the
charging
chart.
Step
4
—
Indoor
Airflow
and
Airflow
Adjust-
ments
NOTE:
|
For
cooling
operation,
the
recommended
airflow
is
350
to
450
CFM
for
each
12,000
Btuh
of
rated
cooling
capacity.
Table
2
shows
dry
coil
air
delivery
for
horizontal
discharge
units.
Tables
3-4
show
pressure
drops.
NOTE:
Be
sure
that
all
supply-
and
return-air
grilles
are
open,
free
from
obstructions,
and
adjusted
properly.
CUANDO:
ELECTRICAL
SHOCK
HAZARD
Failure
to
follow
this
warning
could
result
in
personal
injury
or
death.
Disconnect
electrical
power
to
the
unit
and
install
lockout
tag
before
changing
blower
speed.
There
may
be
more
than
one
disconnect
switch.
Airflow
can
be
changed
by
changing
the
lead
connections
of
the
blower
motor.
Units
50ZP036,048,
and
060
blower
motors
are
factory
wired
for
low
speed
operation.
FOR
208/230-V
—
The
motor
leads
are
color-coded
as
follows:
3-SPEED
black
=
high
speed
2-SPEED
black
=
high
speed
blue
=
medium
speed
red
=
low
speed
red
=
low
speed
To
change
the
speed
of
the
blower
motor (BM),
remove
the
fan
motor
speed
leg
lead
from
the
indoor
(evaporator)
fan
relay
(IFR)
and
replace
with
lead
for
desired
blower
motor
speed.
Insulate
the
removed
lead
to
avoid
contact with
chassis
parts.
10
OUTDOOR
TEMP
oe
8G
115
46
105
41
95 35
85
29
75
24
65
18
65
13
45
7
_
SUCTION
LINE
PRESSURE,
(PSIG
..
65
Zé
oO
wo
x
qa
oa
as
x
WW
a
2
na
wn
lu
oe
oO
uw
2
a
Zz
So
=
Os
2
wo
50
4
10
16
21
SUCTION
LINE
TEMPERATURE
(°C)
00017
Fig.
14
-
Cooling
Charging
Chart,
50ZP036
Units
OUTDOOR
TEMP
7B
8G
115
46
105
41
95 35
mn
AQ
85
29
75
24
65
18
S
65
13
45
7
ts
OS
B
SUCTION
LINE
PRESSURE
(KILOPASCALS)
we
S
ui
:
SUCTION
LINE
PRESSURE,
(PSIG
&
3
50 &G
70
4
10
16
21
ar
32
SUCTION
LINE
TEMPERATURE
(°C)
co0019
Fig.
15
-
Cooling
Charging
Chart,
50ZP048
Units
Step
5
—
Unit
Controls
All
compressors
have
the
following
internal-protection
controls.
HIGH-PRESSURE
RELIEF
VALVE
—
This
valve
opens
when
the
pressure
differential
between
the
low
and
high
side
becomes
excessive.
COMPRESSOR
OVERLOAD
—
This
overload
interrupts
power
to
the
compressor
when
either
the
current
or
internal
temperature
become
excessive,
and
automatically
resets
when
the
internal
temperature
drops
to
a
safe
level.
This
overload
may
require
up
to
60
minutes
(or
longer)
to
reset;
therefore,
if
the
internal
overload
is
suspected
of
being
open,
disconnect
the
electrical
power
to
the
unit
and
check
the
circuit
through
the
overload
with
an
ohmmeter
or
continuity
tester.
OUTDOOR
TEMP
oF
2G
125
52
115
46
105
41
95 35
85
29
75
24
65
18
65
13
45
7
SUCTION
LINE
PRESSURE
(KILOPASCALS)
_
SUCTION
LINE
PRESSURE,
(PSIG),
50
4
10
16
21
SUCTION
LINE
TEMPERATURE
(°C)
c00020
Fig.
16
-
Cooling
Charging
Chart,
50ZP060
Units
Step
6
—
Sequence
of
Operation
FAN
OPERATION
—
The
FAN
switch
on
the
thermostat
controls
indoor
fan
operation.
When
the
FAN
switch
is
placed
in
the
ON
position,
the
IFR
(indoor-fan
relay)
is
energized
through
the
G
terminal
on
the
thermostat.
The
normally-open
contacts
close,
which
then
provide
power
to
the
indoor
(evaporator)
fan
motor
(IFM).
The
IFM
will
run
continuously
when
the
FAN
switch
is
set
to
ON.
When
the
FAN
switch
is
set
to
AUTO,
the
thermostat
deenergizes
the
IFR
(provided
there
is
not
a
call
for
cooling).
The
contacts
open
and
the
IFM
is
deenergized.
The
IFM
will
be
energized
only
when
there
is
a
call
for
cooling.
NOTE:
Units
are
equipped
with
a
time-delay
relay.
The
indoor
fan
remains
on
for
30
seconds
after
G
or
Y
is
deenergized.
COOLING
—
On
a
call
for
cooling,
the
compressor
contactor
(C)
and
the
IFR
are
energized
through
the
Y
and
G
terminalis
of
the
thermostat.
On
units
with
a
compressor
time-delay
relay,
there
is
a
5-minute
(+45
sec)
delay
between
compressor
starts.
Energizing
the
compressor
contactor
supplies
power
to
the
compressor
and
the
outdoor
(condenser)
fan
motor
(OFM).
Energizing
the
IFR
provides
power
to
the
IFM.
When
the
need
for
cooling
has
been
satisfied,
the
OFM,
compressor,
and
IFM
(FAN
on
AUTO)
are
deenergized.
If
the
unit
is
equipped
with
a
30-second
delay,
the
indoor
fan
will
remain
energized
for
30
seconds
after
the
compressor
is
deenergized
(030
and
060
units
only).
MAINTENANCE
To
ensure
continuing
high
performance,
and
to
reduce
the
possibility
of
premature
equipment
failure,
periodic
maintenance
must
be
performed
on
this
equipment.
This
cooling
unit
should
be
inspected
at
least
once
each
year
by
a
qualified
service
person.
To
troubleshoot
cooling
of
units,
refer
to
Troubleshooting
chart
in
back
of
book.
NOTE:
TO
EQUIPMENT
OWNER:
Consult
your
local
dealer
about
the
availability
of
a
maintenance
contract.
11
CE
UA
Le:
PERSONAL
HAZARD
Failure
to
follow
this
warning
could
result
in
personal
injury
or
death
and
possible
unit
component
damage.
INJURY
AND
UNIT
DAMAGE
The
ability
to
properly
perform
maintenance
on_
this
equipment
requires
certain
expertise,
mechanical
skills,
tools
and
equipment.
If
you
do
not
possess
these,
do
not
attempt
to
perform
any
maintenance
on
this
equipment,
other
than
those
procedures
recommended
in
the
Owner’s
Manual.
The
minimum
maintenance
requirements
for
this
equipment
are
as
follows:
1.
Inspect
air
filter(s)
each
month.
Clean
or
replace
when
necessary.
bo
.
Inspect
indoor
coil,
outdoor
coil,
drain
pan,
and
condensate
drain
each
cooling
season
for
cleanliness.
Clean
when
necessary.
3.
Inspect
blower
motor
and
wheel
for
cleanliness
each
cooling
season.
Clean
when
necessary.
4,
Check
electrical
connections
for
tightness
and
controls
for
proper
operation
each
cooling
season.
Service
when
necessary.
5.
Check
the
drain
channel
in
the
top
cover
periodically
for
blockage
(leaves,
insects).
Clean
as
needed.
Cn
UA
LO:
ELECTRICAL
SHOCK
HAZARD
Failure
to
follow
these
warnings
could
result
in
personal
injury
or
death:
1.
Turn
off
electrical
power
and
install
lockout
tag
to
the
unit
before
performing
any
maintenance
or
service
on
this
unit.
There
may
be
more
than
one
disconnect
switch.
i)
.
Use
extreme
caution
when
removing
panels
and
parts.
an
.
Never
place
anything
combustible
either
on
or
in
contact
with
the
unit.
Step
1
—
Air
Filter
IMPORTANT:
Never
operate
the
unit
without
a
suitable
air
filter
in
the
return-air
duct
system.
Always
replace
the
filter
with
the
same
dimensional
size
and
type
as
originally
installed.
See
Table
1
for
recommended
filter
sizes.
Inspect
air
filter(s)
at
least
once
each
month
and_
replace
(throwaway-type)
or
clean
(cleanable-type)
at
least
twice
during
each
cooling
season
or
whenever
the
filters
become
clogged
with
dust
and
lint.
Replace
filters
with
the
same
dimensional
size
and
type
as
originally
provided,
when
necessary.
Step
2
—
Unit
Top
Removal
(Condenser-Coil
Side)
NOTE:
When
performing
maintenance
or
service
procedures
that
require
removal
of
the
unit
top,
be
sure
to
perform
ail
of
the
routine
maintenance
procedures
that
require
top
removal,
including
coil
inspection
and
cleaning,
and
condensate
drain
pan
inspection
and
cleaning.
CE
UA
Le:
ELECTRICAL
SHOCK
HAZARD
Failure
to
follow
this
warning
could
result
in
personal
injury
or
death.
Disconnect
electrical
power,
and
install
lockout
tag
to
the
unit
before
removing
top.
There
may
be
more
than
one
disconnect
switch.
Only
qualified
service
personnel
should
perform
maintenance
and
service
procedures
that
require
unit
top
removal.
Refer
to
the
following
top
removal
procedures:
1.
Remove
7
screws
on
unit
top
cover
surface.
(Save
all
screws.)
bo
.
Remove
2
screws
on
unit
top
cover
flange.
(Save
all
screws.)
3.
Lift
top
from
unit
carefully.
Set
top
on
edge
and
make
sure
that
top
is
supported
by
unit
side
that
is
opposite
duct
(or
plenum)
side.
4.
Carefully
replace
and
secure
unit
top
to
unit,
using
screws
removed
in
Steps
1
and
2,
when
maintenance
and/or
service
procedures
are
completed.
Step
3
—
Evaporator
Blower
and
Motor
For
longer
life,
operating
economy,
and
continuing
efficiency,
clean
accumulated
dirt
and
grease
from
the
blower
wheel
and
motor
annually.
CUANDO:
ELECTRICAL
SHOCK
HAZARD
Failure
to
follow
this
warning
could
result
in
personal
injury
or
death.
Disconnect
electrical
power,
and
install
lockout
tag
to
the
unit
before
cleaning
and
lubricating
the
blower
motor
and
wheel.
There
may
be
more
than
one
disconnect
switch.
To
clean
the
blower
wheel:
1.
Access
the
blower
assembly
as
follows:
a.
Remove
top
access
panel.
b.
Remove
3
screws
that
hold
blower
orifice
ring
to
blower
housing.
Save
screws.
c.
Loosen
setscrew(s)
which
secure
wheel
to
motor
shaft.
2.
Remove
and
clean
blower
wheel
as
follows:
a.
Lift
wheel
from
housing.
When
handling
and/or
cleaning
blower
wheel,
be
sure
not
to
disturb
balance
weights
(clips)
on
blower
wheel
vanes.
b.
Remove
caked-on
dirt
from
wheel
and
housing
with
a
brush.
Remove
lint
and/or
dirt
accumulations
from
wheel
and
housing
with
vacuum
cleaner,
using
a
soft
brush
attachment.
Remove
grease
and
oil
with
a
mild
solvent.
c.
Reassemble
blower
into
housing.
Place
upper
orifice
ring
on
blower
to
judge
location
of
the
blower
wheel.
Blower
wheel
should
be
approximately
0.2-in.
(5
mm)
below bottom
of
orifice
ring
when
centered
correctly.
Be
sure
setscrews
are
tightened
on
motor
and
are
not
on
round
part
of
shaft.
d.
Set
upper
orifice
ring
in
place
with
3
screws
removed
in
step
1.
e.
Replace
top
access
panel.
Step
4
—
Condenser
Coil,
Evaporator
Coil,
and
Condensate
Drain
Pan
Inspect
the
condenser
coil,
evaporator
coil,
and
condensate
drain
pan
at
least
once
each
year.
Proper
inspection
and
cleaning
requires
the
removal
of
the
unit
top.
See
Unit
Top
Removal
section
above.
The
coils
are
easily
cleaned
when
dry;
therefore,
inspect and
clean
the
coils
either
before
or
after
each
cooling
season.
Remove
all
obstructions
(including
weeds
and
shrubs)
that
interfere
with
the
airflow
through
the
condenser
coil.
Straighten
bent
fins
with
a
fin
comb.
If
coated
with
dirt
or
lint,
clean
the
coils
with
a
vacuum
cleaner,
using
a
soft
brush
attachment.
Be
careful
not
to
bend
the
fins.
If
coated
with
oil
or
grease,
clean
the
coils
with
a
mild
detergent-and-water
solution.
Rinse
coils
with
clear
water,
using
a
garden
hose.
Be
careful
not
to
splash
water
on
motors,
insulation,
wiring,
or
air
filter(s).
For
best
results,
spray
condenser-coil
fins
from
inside
to
outside
the
unit.
On
units
with
an
outer
and
inner
condenser
coil,
be
sure
to
clean
between
the
coils.
Be
sure
to
flush
all
dirt
and
debris
from
the
unit
base.
Inspect
the
drain
pan
and
condensate
drain
line
when
inspecting
the
coils.
Clean
the
drain
pan
and
condensate
drain
by
removing
all
foreign
matter
from
the
pan.
Flush
the
pan
and
drain
tube
with
clear
water.
Do
not
splash
water
on
the
insulation,
motor,
wiring,
or
air
filter(s).
If
the
drain
tube
is
restricted,
clear
it
with
a
“plumbers
snake”
or
similar
probe
device.
Ensure
that
the
auxiliary
drain
port
above
the
drain
tube
is
also
clear.
Step
5
—
Condenser
Fan
&
CAUTION
UNIT
OPERATION
HAZARD
Failure
to
follow
this
caution
may
result
in
damage
to
unit
components.
Keep
the
condenser
fan
free
from
all
obstructions
to
ensure
proper
cooling
operation.
Never
place
articles
on
top
of
unit.
1.
Shut
off
unit
power
supply.
bo
.
Remove
condenser-fan
assembly
(grille,
motor,
motor
cover,
and
fan)
by
removing
screws
and
flipping
assembly
onto
unit
top
cover.
an
.
Loosen
fan
hub
setscrews.
.
Adjust
fan
height
as
shown
in
Fig.
17.
a
ot
.
Tighten
setscrews.
on
.
Replace
condenser-fan
assembly.
Bh
Cy
ms
t
MTR
ee
3.125
in.
c00021
Fig.
17
-
Condenser-Fan
Adjustment
Step
6
—
Electrical
Controls
and
Wiring
Inspect
and
check
the
electrical
controls
and
wiring
annually.
Be
sure
to
turn
off the
electrical
power
to
the
unit.
Remove
the
top
panel
to
locate
all
the
electrical
controls
and
wiring.
Check
all
electrical
connections
for
tightness.
Tighten
all
screw
connections.
If
any
smoky
or
burned
connections
are
noticed,
disassemble
the
connection,
clean
all
the
parts,
restrip
the
wire
end
and
reassemble
the
connection
properly
and
securely.
After
inspecting
the
electrical
controls
and
wiring,
replace
all
the
panels.
Start
the
unit,
and
observe
at
least
one
complete
cooling
cycle
to
ensure
proper
operation.
If
discrepancies
are
observed
in
operating
cycle,
or
if
a
suspected
malfunction
has
occurred,
check
each
electrical
component
with
the
proper
electrical
instrumentation.
Refer
to
the
unit
wiring
label
when
making
these
checkouts.
NOTE:
Refer
to
the
Sequence
of
Operation
section,
as
an
aid
in
determining
proper
control
operation.
Step
7
—
Refrigerant
Circuit
Inspect
all
refrigerant
tubing
connections
and
the
unit
base
for
oil
accumulations
annually.
Detecting
oil
generally
indicates
a
refrigerant
leak.
If
oil
is
detected
or
if
low
cooling
performance
is
suspected,
leak-test
all
refrigerant
tubing
using
an
electronic
leak-detector,
or
liquid-soap
solution.
If
a
refrigerant
leak
is
detected,
refer
to
Check
for
Refrigerant
Leaks
section
If
no
refrigerant
leaks
are
found
and
low
cooling
performance
is
suspected,
refer
to
Refrigerant
Charge
section.
Step
8
—
Evaporator
Airflow
The
cooling
airflow
does
not
require
checking
unless
improper
performance
is
suspected.
If
a
problem
exists,
be
sure
that
all
supply-
and
return-air
grilles
are
open
and
free
from
obstructions,
and
that
the
air
filter
is
clean.
When
necessary,
refer
to
Indoor
Airflow
and
Airflow
Adjustments
section
to
check
the
system
airflow.
Step
9
—
Metering
Devices
The
036
size
uses
fixed
orifices
located
in
the
inlet
header
to
the
evaporator
coil.
The
048
and
060
use
a
single
piston
located
in
the
brass
body connected
to
the
feeder
tubes.
Step
10
—
Liquid
Line
Strainer
The
liquid
line
strainer
(to
protect
metering
device)
is
made
of
wire
mesh
and
is
located
in
the
liquid
line
on
the
inlet
side
of
the
metering
device.
TROUBLESHOOTING
Refer
to
the
Troubleshooting
Chart
(Table
5)
for
troubleshooting
information.
START-UP
CHECKLIST
Use
the
Start-Up
Checklist
at
the
back
of
this
manual.
Table
2
-
Dry
Coil
Air
Delivery*
Horizontal
Discharge
(Deduct
10%
for
208
Volt
Operation)
Unit
Motor
Air
External
Static
Pressure
(IN.
W.C.)
Speed
|
Delivery
0.1
0.2
0.3 0.4 0.5
0.6
0.7
0.8 0.9
Low
Watts
450 435 420 400 380 335 326
311
-
Cfm
1231
1218 1204 1120 1008
950
863
751
-
036
Med
Watts
470 450 445 410 388 359 338
321
-
Cfm
1302 1264 1205
1163
1081
940
873 783
-
High
Watts
660 635 610 575 540 505 485 460
-
Cfm
1700 1660
1581
1450 1297 1190 1095
999
-
Low
Watts
- -
801
760 730 688 650 600 570
048
Cfm
- -
1898
1841
1757 1682 1564 1429 1365
High
Watts
- -
870 842 818 782 696 632 628
Cfm
- -
2000
1903
1799 1718 1625 1446
1333
Low
Watts
890 850 810 790 735 680 580 480 422
Cfm
1834 1820
1791
1762
1703
1640 1415 1159
950
060
Med
Watts
1040 1018 1000
950 890 835 790 650 580
Cfm
2230
2102
2025
1960
1901
1855 1752 1468
1121
Watts
1073
1038
1001
958 896 840 800
691
575
High
Cfm
2230 2202
2160 2122
2052
1926
1791
1588 1202
*
Air
delivery
values
are
based
on
operating
voltage
of
230
v
dry
coil,
without
filter.
Deduct
wet
coil,
filter
pressure
drops
to
obtain
external
static
pressure
avail-
able
for
ducting.
See
Tables
3-4.
NOTES:
1.
Do
not
operate
the
unit
at
a
cooling
airflow
that
is
less
than
350
cfm
for
each
12,000
Btuh
of
rated
cooling
capacity.
Evaporator
coil
frosting
may
occur
at
airflows
below
this
point.
2.
Dashes
indicate
portions
of
the
table
that
are
beyond
the
blower
motor
capacity
or
are not
recommended.
Table
3
—
Wet
Coil
Pressure
Drop
UNIT
SIZE
50ZP
AIRFLOW
(CFM)
PRESSURE
DROP
(IN.
W.C.)
1000
0.07
1200
0.09
036
1400
0.11
1600
0.12
1400
0.07
048
1600
0.08
1800
0.09
1700
0.07
1800
0.08
060
2100
0.09
2300
0.10
Table
4
—
Filter
Pressure
Drop
(IN.
W.C.)
UNIT
SIZE
50ZP
FILTER
SIZE
IN.
(mm)
CFM
,
1000 1100 1200 1300 1400
24
x
24
036
(B10
x
610)
0.09 0.09
0.10
0.11
0.12
24
x
30
048,
060
(B10
x
762)
- - -
0.08
0.09
UNIT
SIZE
50ZP
FILTER
SIZE
IN.
(mm)
crM
,
1500 1600 1700 1800 1900
2000 2100 2200 2300
24
x
24
036
(B10
x
610) 0.14 0.15
- - - - - - -
24
x
30
048,
060
(B10
x
762) 0.10
0.11
0.12
0.13
0.14 0.15 0.16 0.17 0.18
14
SCHEMATIC
if
23
TY
208/230-1-60
MAXIMUM
WIRE
EQUIP
GND
oe
SIZE
2
AWG
Powe
ax
ns
SUPPL
YEL
ve
YEL
BLK
SEE
NOTE
5
Tf
RED
THERMOSTAT
SUB-BASE
\()
EE
Sa
BLK
BLK
|
YEL
YEL
orm
BLK
cAP2
¢
KEY
HCE)
BRN
|
eT
BLK
or
¢
ye EL
BLU
OVERLOAD
PROTECTOR
YER
L—
BLK
VEL
COMP
nL
BLU
wt
|
COMPRESSOR
PLUG
CIF
USED)
sv
BLU
(060
ONLY)
PS
(042
ONLY)
(024,036,048
8
060)
ALL
EXCEPT
048
——_»—_
6
RED
Daly
ia
iM
(930
&
042)
a
a
Gyo
am
OT
CAPI
GRN-YEL
Ah
HD
CoB)
C230)
GRN-YEL
TRANT
poy
Cl}
BRN
é
BRN
—
GEN
ee
y
TL
VEL
wT
dD
(SEE
NOTER2)
tomtom
BRN
24¥
SPLICE
BOX
BRN
mn
€
T
®
a
'
+
BRK—]
24v
SPLICE
TINER
Boe
Br
BRN
—€
FDR:8
re
CoG
on
1FR:3
BRN———®
COM,
TRAN
~~
BRN
HRI
BRN
TOR:B
OR
TFR:3
LEGEND
COMPONENT
ARRANGEMENT
4D
_
FIELD
SPLICE
C
CONTACTOR,
COMPRESSOR
CAP
CAPACITOR
Cry
MARKED
WIRE
COMP
COMPRESSOR
MOTOR
at
CH)
TERMINAL
MARKED)
EQUIP
EOUTPHENT
BRN
FL
FUSE
LINK
&®
°
TERMINAL
(UNMARKED)
Fu
FUSE
GND
GROUND
i
TERMINA
K
COMP
fy
ERMINAL
BLOC
HR
HEATER
RELAY
(STRIP
HEAT)
TNDOOR
FAN
e
SPLICE
IFM
INDOOR
FAN
MOTOR
BLOWER
HOUSING
IFR
INDOOR
FAN
RELAY
CW
SPLICE
(MARKED)
eno
IP
INTERNAL
PROTECTOR
os
wa
FACTORY
WIRING
OFM
QUTDOOR
FAN
MOTOR
cae
OT
QUADRUPLE
TERMINAL
a
FTELD
CONTROL
WIRING
$8
SLOW
BLOW
FUSE
_&
@ @
FIELD
POWER
WIRING
ST
START
THERMISTOR
po
NBL
SE
8
ae
TB
TERMINAL
BLOCK
Fovalll
o
“~~~
ACCESSORY
OR
OPTIONAL
WIRING
Typ
TIME
DELAY
RELAY
©
e
TO
INDICATE
COMMON
TH
TRERMOSTAT-REATING
POTENTIAL
ONLY:
TRAN
TRANSFORMER
a
ag
(030,036,042
&
060)
NOT
10
REPRESENT
WIRING
ae:
|
|
TOR
CAP2
NOTES
0)
RUN
&
OFM
cart
1.IF
ANY
OF
THE
ORIGINAL
WIRE
FURNISHED
5
IFM
CAP
MUST
BE
REPLACED,
IT
MUST
BE
REPLACED
EQUIP
GND
WITH
TYPE
90°C
WIRE
OR
ITS
EQUIVALENT
=
6oO
2.SEE PRICE
PAGES
FOR
THERMOSTAT
24V
SPLICE
AND
SUBBASE
PART
NUMBERS
FAN
SEQUENCE
FOR
TDR
Box
3.
SET
HEAT
ANTICIPATOR
AT
.6
,
4,USE
75°C
COPPER
CONDUCTORS
ONLY.
|
\
S.W1/H2
TS
CONNECTED
ONLY
IF
EXTERNAL
+
|
ore
HEATING
SOURCE
IS
USED.
5 ;
+30
DISCONNECT
24V
POWER
ENTRY
@
ENERGIZED
DE
-ENERGIZED
PER NEC
(024
&
048)
cer
cl
R
SOZP
500869)
-
A11083
Fig.
18
-
50ZP
208/230-1
Wiring
Diagram
SCHEMATIC
-
208/230-3-60
MAXIMUM
WIRE
EQUIP
GND
=
BLK
BLK
SIZE
2
AWG
F
Tt
c
ELD
BLK
Blk
———17T}}
BLK
carat
or
POWEP
_ft
YEL YEL
xis
Hap—
vet
YEL
FO-BRN
SUPPLY
Tt
BLU
YEL
or
BLK
BLU:
COMP
YEL
IFR
OVERLOAD
PROTECTOR
BLU
a
a
(036,048
&
060?
ALL
EXCEPT
048
3
{30
St
rep
BL
-
BLU
u
(036,042
&
060)
en
\_
ver.
=
ia
>
\ien
5
pe-eei
(042)
oT
CAPI
een
YEL—
L__ver
BLK
SEE
CoM
-
NOTE.
4
TRANI
GRN-YEL
f
—-----
-—|-—
780
8
¢—
BRN
-
oc
RED
RED
~~
(036,042
&
060)
Dav
SPLICE
—
_
™Le
a]|
BOX
(036,042
&
060)
z
TDR:B
YEL
vet
oC)
BCP
oe
ER
BRN—®
Cou,
TRAN
—_L.»
_
tL.»
comon+-
3
(SEE
NOTE*2)
y—BRN
_
_
_
_ _
BRN—O
HRI
BRN:
BRN—O
TOR;
3
OR
1FR;3
24v
SPLICE
BOX
LEGEND
COMPONENT
ARRANGEMENT
_—SD_
FIELD
SPLICE
C
—_
CONTACTOR,
COMPRESSOR
CAP
CAPACITOR
__(%)
MARKED
WIRE
COMP
COMPRESSOR
MOTOR
CQ)
TERMINAL
(MARKED)
EQUIP
EQUIPMENT
FL
FUSE LINK
@
oO
TERMINAL
(UNMARKED)
FU
FUSE
GND
GROUND
COHP
TERMINAL
BLOCK
HR
HEATER
RELAY
(STRIP
HEAT)
INDOOR
FAN
e
SPLICE
IFH
INDOOR
FAN
MOTOR
BLOWER
HOUSING
—
«—<4
|
Ce
SPLICE
cHaRKED)
IFR
INDOOR
FAN
RELAY
6ND
IP
_
INTERNAL
PROTECTOR
[Fa
FACTORY
WIRING
OFM
OUTDOOR
FAN
MOTOR
Toes
_
OT
QUADRUPLE
TERMINAL
|
L
FIELD
CONTROL
WIRING
oe
etow
Blow Fuse
"7
©
——
__
FIELD POWER
WIRING
TB
TERMINAL
BLOCK
o 8
TOR
TIME
DELAY
RELAY
6
@
VEL
—-—
ACCESSORY
OR
OPTIONAL
WIRING
ti
THERMOSTAT-HEATING
UW
©
TO
INDICATE
COMMON
TRAN
TRANSFORMER
g
——
POTENTIAL
ONLY:
B
A
(036,042
&
060)
NOT
TO
REPRESENT
WIRING
TOR
NOTES
f
auy{t)
caP2
cart 1.1F
ANY
OF
THE
ORIGINAL
WIRE
FURNISHED
;
1 |
OFM CAP
IFM
CAP
MUST
BE
REPLACED,
IT
NUST
BE
REPLACED
FOUIP
GND
t
WITH
TYPE
90°C
WIRE
OR
1TS
EQUIVALENT.
=
2.SEE
PRICE
PAGES
FOR
THERMOSTAT
24V
SPLICE
AND
SUBBASE
PART
NUMBERS.
F
Fi
TOR
il
OX
3.USE
75°C
COPPER
CONDUCTORS
ONLY.
oA
SEQUENCE
FOR
TO
}
4.W1/W2
TS
CONNECTED
ONLY
IF
a.3
| |
EXTERNAL
HEATING
SOURCE
IS
USED.
:
0
T
T#30
=
6 6
Disconnect
24V
POWER ENTRY
ENERGIZED
DE-ENERG|ZED
|
per
NEC
502P500668
[A
A11578
Fig.
19
-
50ZP
208/230-3
Wiring
Diagram
16
Table
5
—
Troubleshooting
Chart
SYMPTOM
CAUSE
REMEDY
Compressor
and
outdoor
fan
will
not
start
Power
failure
Call
power
company
Fuse
blown
or
circuit
breaker
tripped
Replace
fuse
or
reset
circuit
breaker
Defective
contactor,
transformer,
control
relay,
or
high-pressure,
or
low-pressure
switch
Replace
component
Insufficient
line
voltage
Determine
cause
and
correct
Incorrect
or
faulty
wiring
Check
wiring
diagram
and
rewire
correctly
Thermostat
setting
too
low/too
high
Reset
thermostat
setting
Compressor
will
not
start
but
condenser
fan
runs
Faulty
wiring
or
circuit
Loose
connections
in
compressor
Check
wiring
and
repair
or
replace
Compressor
motor
burned
out,
seized,
or
internal
overload
open
Determine
cause
Replace
compressor
Defective
run
capacitor,
overload,
or
PTC
(positive
temperature
coefficient)
thermistor
Determine
cause
and
replace
One
leg
of
3-phase
power
dead
Replace
fuse
or
reset
circuit
breaker
Determine
cause
Low
input
voltage
Determine
cause
and
correct
Compressor
cycles
(other
than
normally
sat-
isfying)
cooling/heating
calls
Refrigerant
overcharge
or
undercharge
Recover
refrigerant,
evacuate
system,
and
re-
charge
to
capacities
shown
on
rating
plate
Defective
compressor
Replace
and
determine
cause
Insufficient
line
voltage
Determine
cause
and
correct
Blocked
outdoor
coil
Determine
cause
and
correct
Defective
run/start
capacitor,
overload
or
start
relay
Determine
cause
and
replace
Faulty
outdoor
fan
motor
or
capacitor
Replace
Restriction
in
refrigerant
system
Locate
restriction
and
remove
Compressor
operates
continuously
Dirty
air
filter
Replace
filter
Unit
undersized
for
load
Decrease
load
or
increase
unit
size
Thermostat
temperature
set
too
low
Reset
thermostat
setting
Low
refrigerant
charge
Locate
leak,
repair,
and
recharge
Air
in
system
Recover
refrigerant,
evacuate
system,
and
re-
charge
Outdoor
coil
dirty
or
restricted
Clean
coil or
remove
restriction
Excessive
head
pressure
Dirty
air
filter
Replace
filter
Dirty
indoor
or
outdoor
coil
Clean
coil
Refrigerant
overcharged
Recover
excess
refrigerant
Air
in
system
Recover
refrigerant,
evacuate
system,
and
re-
charge
Indoor
or
outdoor
air
restricted
or
air
short-cycling
Determine
cause
and
correct
Head
pressure
too
low
Low
refrigerant
charge
Check
for
leaks, repair
and
recharge
Restriction
in
liquid
tube
Remove
restriction
Excessive
suction
pressure
Refrigerant
overcharged
Recover
excess
refrigerant
Suction
pressure
too
low
Dirty
air
filter
Replace
filter
Low
refrigerant
charge
Check
for
leaks, repair
and
recharge
Metering
device
or
low
side
restricted
Remove
source
of
restriction
Insufficient
coil
airflow
Check
filter-replace
if
necessary
Temperature
too
low
in
conditioned
area
Reset
thermostat
setting
Outdoor
ambient
below 55°F
(13°C)
Install
low-ambient
kit
Filter
drier
restricted
Replace
17
START-UP
CHECKLIST
(REMOVE
AND
STORE
IN
JOB
FILE)
I.
PRELIMINARY
INFORMATION
Model
No
Serial
No
Il.
PRE-START-UP
_____
Verify
that
all
packing
materials
have
been
removed
from
unit.
____
Verify
that
condensate
connection
is
installed
per
installation
instructions.
_____
Check
ail
electrical
connections
and
terminals
for
tightness.
_____
Check
wire
proximity
to
refrigerant tubes
and
sheet
metal
edges.
____
Check
that
indoor
(indoor)
air
filter
is
clean
and
in
place.
_____
Verify
that
unit
installation
is
level.
_____
Check
fan
wheel
propeller
for
location
in
housing
and
setscrew
tightness.
Ii.
START-UP
Supply
Voltage:
L1-L2
L2-L3 L3-L1
Compressor
Amps:
L1(C)
L2(S)
L3(R)
Indoor
Fan
Amps:
Outdoor
Fan
Amps:
TEMPERATURE-Cooling
Mode
Outdoor
Air
Temperature:
DB
WB
Return-Air
Temperature:
DB
WB
Cooling
Supply
Air:
DB
WB
PRESSURES-Cooling
Mode
Refrigerant
Suction
psig
Suction
Line
Temp*
Refrigerant
Discharge
psig
Discharge
TempTt
*Measured
at
suction
inlet
to
compressor
TMeasured
at
liquid
line
leaving
outdoor
coil
Copyright
2011
Carrier
Corp.
+
7310
W.
Morris
St.
*
Indianapolis,
IN
46234
Printed
in
U.S.A.
Edition
Date:
12/14
Manufacturer
reserves
the
right
to
change,
at
any
time,
specifications
and
designs
without
notice
and
without
obligations.
18
Catalog
No:
50ZP-—08SI
Replaces:
50ZP-—07Sl

This manual suits for next models

2

Other Carrier Air Conditioner manuals

Carrier WeatherMaster 50HC14 User manual

Carrier

Carrier WeatherMaster 50HC14 User manual

Carrier 50HG014-028 User manual

Carrier

Carrier 50HG014-028 User manual

Carrier 42WHC016 User manual

Carrier

Carrier 42WHC016 User manual

Carrier CRTWOPOS012A00 User manual

Carrier

Carrier CRTWOPOS012A00 User manual

Carrier 48ES---A User manual

Carrier

Carrier 48ES---A User manual

Carrier Xpower 40KQM User manual

Carrier

Carrier Xpower 40KQM User manual

Carrier 40KMC User manual

Carrier

Carrier 40KMC User manual

Carrier 48FC Series User guide

Carrier

Carrier 48FC Series User guide

Carrier 38CKS Operation manual

Carrier

Carrier 38CKS Operation manual

Carrier 50FF 020 Manual

Carrier

Carrier 50FF 020 Manual

Carrier Base 50ZPA User manual

Carrier

Carrier Base 50ZPA User manual

Carrier 42TSV052P1 User manual

Carrier

Carrier 42TSV052P1 User manual

Carrier Air V User manual

Carrier

Carrier Air V User manual

Carrier WeatherExpert 48LC B14 Series User manual

Carrier

Carrier WeatherExpert 48LC B14 Series User manual

Carrier 42UQV050M Series User manual

Carrier

Carrier 42UQV050M Series User manual

Carrier 38BR Instructions and recipes

Carrier

Carrier 38BR Instructions and recipes

Carrier i-cool series User manual

Carrier

Carrier i-cool series User manual

Carrier 40GVC / 38GVC Operation manual

Carrier

Carrier 40GVC / 38GVC Operation manual

Carrier MODULINE 37HS User manual

Carrier

Carrier MODULINE 37HS User manual

Carrier 50TJ016-028 Dimensions and installation guide

Carrier

Carrier 50TJ016-028 Dimensions and installation guide

Carrier 42XPF User manual

Carrier

Carrier 42XPF User manual

Carrier Atmosphera 42EM series User manual

Carrier

Carrier Atmosphera 42EM series User manual

Carrier 40VMM User manual

Carrier

Carrier 40VMM User manual

Carrier 90MA/MF/MU Setup guide

Carrier

Carrier 90MA/MF/MU Setup guide

Popular Air Conditioner manuals by other brands

Soleus Air SG-WAC-10ESE-F operating instructions

Soleus Air

Soleus Air SG-WAC-10ESE-F operating instructions

Danby DAC145EB6WDB-6 owner's manual

Danby

Danby DAC145EB6WDB-6 owner's manual

Hyundai HRP-S09WH Service manual

Hyundai

Hyundai HRP-S09WH Service manual

Tosot GWH09AFCXB-A3DNA2B/I user manual

Tosot

Tosot GWH09AFCXB-A3DNA2B/I user manual

Lennox EMEA FLEXAIR 85 Installation, operating and maintenance

Lennox EMEA

Lennox EMEA FLEXAIR 85 Installation, operating and maintenance

Samsung AJ035NB1DEH/SA User & installation manual

Samsung

Samsung AJ035NB1DEH/SA User & installation manual

Hitachi RAK-18PED instruction manual

Hitachi

Hitachi RAK-18PED instruction manual

THERMOBILE Coolmobile 21 user manual

THERMOBILE

THERMOBILE Coolmobile 21 user manual

Mitsubishi Electric CITY MULTI CMY-Q100VBK installation manual

Mitsubishi Electric

Mitsubishi Electric CITY MULTI CMY-Q100VBK installation manual

Haier HSU18VCA Operation manual

Haier

Haier HSU18VCA Operation manual

INVENTOR A2VI-18 owner's manual

INVENTOR

INVENTOR A2VI-18 owner's manual

GREE ELECTRIC MULTI18HP230V1BO Service manual

GREE ELECTRIC

GREE ELECTRIC MULTI18HP230V1BO Service manual

Whirlpool RH123A1 Use and care guide

Whirlpool

Whirlpool RH123A1 Use and care guide

Frigidaire FAA055N7A Factory parts catalog

Frigidaire

Frigidaire FAA055N7A Factory parts catalog

Toshiba RAS-10JKCVP Series owner's manual

Toshiba

Toshiba RAS-10JKCVP Series owner's manual

Klimaire KTIM 012 installation manual

Klimaire

Klimaire KTIM 012 installation manual

FGE FARELEK 112503 manual

FGE

FGE FARELEK 112503 manual

LG PQDSBC1 installation manual

LG

LG PQDSBC1 installation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.