RECEIVING AND INSTALLATION
Step 1 — Check Equipment
IDENTIFYUNIT —The unit model number and serial num-
ber are stamped on unit identification plate. Check this
information against shipping papers and job data.
INSPECT SHIPMENT— Inspect for shipping damage while
unit is still on shipping pallet. If unit appears to be damaged
or is torn loose from its anchorage, have it examined by trans-
portation inspectors before removal. Forward claim papers
directly to transportation company. Manufacturer is not re-
sponsible for any damage incurred in transit.
Check all items against shipping list. Immediately notify
the nearest Carrier Air Conditioning office if any item is
missing.
To prevent loss or damage, leave all parts in original pack-
ages until installation.
Step 2 — Provide Unit Support
ROOF CURB — Install accessory roof curb in accordance
with instructions shipped with curb. See Fig. 6 for roof curb
dimensions. Install insulation, cant strips, roofing, and flash-
ing. Ductwork must be attached to curb.
IMPORTANT: The gasketing of the unit to the roof
curb is critical for a watertight seal. Install gasketing
material supplied with the roof curb. Improperly ap-
plied gasketing can also result in air leaks and poor
unit performance.
Curb should be level to within
1
⁄
4
inch. See Fig. 7. This
is necessary for unit drain to function properly. Refer to
accessory roof curb installation instructions for additional
information as required.
To remove wood support under unit (with base rail only),
loosen 4 screws above rigging holes and slide assembly out
through rectangular hole.
SLAB MOUNT — Place the unit on a solid, level concrete
pad that is a minimum of 4 in. thick with 2 in. above grade.
The slab should be flush on the front of the unit (to allow
condensate drain installation) and should extend 2 in. on the
three remaining sides of the unit. See Fig. 8. Install a 6-in.
gravel apron in front of outdoor-air inlets to prevent obstruc-
tion of airflow by grass or shrubs. Do not secure the unit to
the slab except when required by local codes.
To remove wood support under unit (with base rail only),
loosen 4 screws above rigging holes and slide assembly out
through rectangular hole.
FLUSH MOUNT — Place side of unit with duct panel
flush against transition. On units with optional base rails, the
skirt on duct-panel side of unit can be removed or relocated
to allow unit to be mounted flush against transitions that ex-
tend below basepan of unit. To move skirt, proceed as
follows:
1. Remove 4 screws holding skirt to base rail. Retain screws.
2. Remove skirt or slide skirt inwards until alternate clear-
ance holes align with base rails.
3. Secure with screws removed in Step 1. Holes align with
base rails.
To remove wood support under unit (with base rail only),
loosen 4 screws above rigging holes and slide assembly out
through rectangular hole.
Step 3 — Field Fabricate Ductwork — Secure all
ducts to roof curb and building structure on vertical dis-
charge units. Do not connect ductwork to unit. For horizon-
tal applications, attach ductwork to flanges on horizontal
discharge openings. All ductwork should be secured to the
flanges. Insulate and weatherproof all external ductwork, joints,
and roof openings with counter flashing and mastic in ac-
cordance with applicable codes.
Ducts passing through an unconditioned space must be
insulated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return
should be ducted through the roof deck to comply with ap-
plicable fire codes.
A minimum clearance is not required around ductwork.
Cabinet return-air static shall not exceed −.25 in. wg.
Step 4 — Provide Clearances — The required mini-
mum operating and service clearances are shown in
Fig. 2-5. Adequate combustion, ventilation, and outdoor air
must be provided.
Do not restrict outdoor airflow. An air restriction at ei-
ther the outdoor-air inlet or the fan discharge can be det-
rimental to compressor life.
The outdoor fan pushes air through the outdoor coil and
discharges it through the bank of louvers in the top cover,
the decorative grille on the right side of the unit, and the
compressor access panel. Be sure that the fan discharge does
not recirculate to the outdoor coil. Do not locate the unit in
either a corner or under an overhead obstruction. The mini-
mum clearance of a partial overhang (such as a normal house
overhang) is 48-inches. The maximum horizontal extension
of a partial overhang must not exceed 48 inches.
Provide a minimum clearance of 42 in. for the control box
side next to a block wall or any other grounded surface. Pro-
vide a minimum clearance of 42 in. between the control box
side of unit and any electrically powered device, for ex-
ample, another unit.
Do not place the unit where water, ice, or snow from an
overhang or roof will damage or flood the unit. Do not in-
stall the unit on carpeting, tile, or other combustible mate-
rials. The unit may be installed on wood flooring or on
Class A, B, or C roof covering materials.
Step 5 — Rig and Place Unit
When installing the unit on a rooftop, be sure the roof
will support the additional weight. Refer to Fig. 2-5 for
corner weight information.
Use spreader bars or crate top when rigging the unit. The
units must be rigged for lifting as shown in Fig. 9. Refer to
Table 1 for operating weight and to Fig. 2-5 for corner weights.
MAXIMUM ALLOWABLE
DIFFERENCE (in.)
A-B B-C A-C
1
⁄
21
⁄
41
⁄
4
Fig. 7 — Unit Leveling Tolerances
7