Installation Guide
10
69-2565—05
Fan Sequence Operations(SetupFunction0347,0348,0349):Thethermostatcomesfactorydefault
withthefanrampingalgorithmenabled(ISU347).ThisgivestheusertheabilitytoselectAuto-Lo-
Med-HioptioninISU348orAutoonlyoptioninISU348.Autosetsthethermostatintothefanramping
algorithmmodeandautomaticallysetsthesufcientspeedforPIcontrol.Autoalsoautomatically
shutsthefanoffwhenthereisnotacallforheatingorcooling.IftheuserdecidestodisableISU347,
thenthefanwillonlyhaveLo-Med-Hioptionavailable.
IfISU347isnotenabled,thenISU348doesnotappearasauserselectionchoice.
IfISU347isenabled,thenISU349isavailableasaselectionchoice.Theusercanselecteithera2
houror4hourtimerfanresetfunction.Thefanwillresetfromaconstantspeedtoautomodeafter
thetimeperiodexpires.IfISU347isnotenabled,thenISU349doesnotappearasauserselection
choice.
Auto Changeover(SetupFunction0300):WhensettoAuto,thethermostatautomaticallyselectsheat-
ingorcoolingdependingontheindoortemperature.
Compressor Protection(SetupFunction0580):Forcesthecompressortowaitafewminutesbefore
restarting,topreventdamage.Duringthistime,themessage“Wait”ashesonthedisplay.
Special Programmable Mode Functions
InstallerSetup0160allowsthethermostattobeconguredforeitheramodewithaprogrammable7
dayscheduleorasanon-programmablethermostat.
Preoccupancy purge(ISU0185):Thisfeatureisavailableonlywhenthethermostatisconguredas
aprogrammablescheduleandwhenafanisused.Thefanwillrun1-3hoursbeforetheoccupied
schedulestartingtimetocirculateair.
Override Button, Temporary Override(DurationLimitISU0535):Whileintheprogrammablesched-
ulemode,anoverridebuttonisavailabletoperformtemporaryoverridecontrol.Thedefaultoverride
timecanbeconguredthroughISU0535.LockoutcongurationviaISU0670canproviderestrictions
onaccesstosetpointchanges,systemchanges,andschedulechanges.
No remote setback:Theremotesetbackfeatureonlyworksinthenonprogrammablemode.
Special Non-Programmable Mode Functions
Override (Optional):Theoverridefeatureisoptionalinthenon-programmablemode.Theoverride
canbeconguredthroughISU0342.Whentheoverrideisactivatedinthenon-programmablemodeit
willtemporarilyoverridetoanewsetpointuntiltheendtimeexpires.
Remote Setback:RemoteSetbackisavailable(ISU0340).Occupancysensors,manualtimeclock
inputs,andDDCnightsetbackcanbeusedtoprovideinputstosetbackthethermostat.Unoccupied
heating(ISU0343)andunoccupiedcooling(ISU0346)setpointsareavailabletocongurethesetback
setpoints.
Special functions