Casambi CBU-PWM4-4 User manual

CBU-PWM4-4 USA & Canada
Bluetooth controllable 4ch PWM dimmer
casambi.com
Dimensions
Description
CBU-PWM4-4 is a Bluetooth controllable, Casambi enabled four
channel PWM dimmer for constant voltage LED loads, such as
LED strips and constant voltage LED modules. It is connected
between a 12-24 VDC Class 2 power supply and a constant
voltage LED load.
CBU-PWM4-4 can control up to four channels making it an
ideal partner for RGBW and tunable white (TW) applications.
The maximum combined output current is 4 A which can be
freely divided between 1 -4 channels. CBU-PWM4-4 is protected
against overvoltage, overcurrent and short circuit situations.
CBU-PWM4-4 can be controlled with Casambi app which
can be downloaded free of charge from Apple App Store
and Google Play Store.
Different Casambi enabled products can be used as a simple one
luminaire direct control to a complete and full-featured light control
system where up to 127 units (Classic) or 250 units (Evolution)
form automatically an intelligent mesh network.
Project:
Reference type:
Item code:
Date:
Notes:
!
Warning!
Hazardous voltages. Risk of
electric shock or fire. Only qualified
professionals should make the
connections. Disconnect the
mains power supply and verify
its absence prior to installation.
Length 2.2 in
Width 1.2 in
Heigth 0.7 in
INPUT 12-24 VDC
OUTPUT 12-24 VDC
Max. 6 A total
*Tc point is on bottom side Dimensions are in mm.

Range
The range between two CBU-PWM4-4s or between a
CBU-PWM4-4 and a smart phone can vary a lot depending on
obstacles and surrounding material. In open-air the range between
two CBU-PWM4-4s is 200 ft, but surroundings may affect the
range, so testing is highly recommended.
Casambi uses mesh network technology so each CBU-PWM4-4
acts also as a repeater. When testing the network, it is important to
test that each unit can be controlled from any point of the network
covered area.
Project:
Reference type:
Item code:
Date:
Notes:
casambi.com
Compatible devices:
iPhone 4S or later
iPad 3 or later
iPod Touch 5th gen or later
Android 4.4 or later devices
produced after 2013 with full BT 4.0 support
Casambi uses mesh network technology so each CBU-PWM4-4 acts also as
a repeater. Longer ranges can be achieved by using multiple Casambi units.
1) Range is highly dependant on the surrounding and obstacles, such as
walls and building materials.
50 m 1)
Up to
30 m 1)
Technical data
Input
Voltage range: 12-24 VDC, Class 2
Max. input current: 4 A
No-load standby power: < 0,3 W
Output
Output voltage: same as input voltage
Max. output power: 96 W @ 24 VDC
48 W @ 12 VDC
Max. output current: 4 A (can be freely divided between
the channels)
Min. load requirement: 0 W
Dimming method: Pulse Width Modulation (PWM)
Radio transceiver
Operating frequencies: 2.4-2.483 Ghz
Maximum output power: typ. +0 dBm, +/- 3 dBm
Operating conditions
Ambient temperature, ta: -13...+113°F (-25...+45°C)
Max. case temperature, tc: +167°F (+75°C)
Storage temperature: -13...+167°F (-25...+75°C)
Max. relative humidity: 0...80%, non-cond.
Connectors
Wire range, solid & stranded: 0.5 - 1.5 mm2
14 - 22 AWG
Wire strip length: .25” (6 - 7 mm)
Tightening force: 0.4 Nm / 2.6 Lb-in
Mechanical data
Dimensions: 2.2 x 1.2 x 0.7 inch
72.6 x 30.0 x 18.0 mm
Weight: 0.8 oz (23 g)
FCC ID: 2ALA3-CBUASR
IC: 22496-CBUASR
UL: UL Listed
UL Plenum Rated (UL 2043)

Warning
Changes or modifications not expressly approved by Casambi
Technologies Oy could void the user’s authority to operate the
equipment.
Project:
Reference type:
Item code:
Date:
Notes:
Wiring diagram, RGBW
casambi.com
12-24 VDC Class 2
power supply
RGBW LED strip
+: common (+)
1: red (-)
2: green (-)
3: blue (-)
4: white (-)
1 2 34
INPUT 12-24 VDC
OUTPUT 12-24 VDC
Max. 6 A total
Use Class 2 power supply
OUTPUT 12-24 VDC
max. 4 A total
213 4
4ch PWM controller
CBU-PWM4-4
INPUT 12-24 VDC, 4 A
Wiring diagram, tunable white
Wiring diagram, 1-4 separate channels
TW LED strip
+: common (+)
1: warm (-)
2: cool (-)
3: warm (-)
4: cool (-)
+: common (+)
1: channel 1 (-)
2: channel 2 (-)
3: channel 3 (-)
4: channel 4 (-)
12 34
INPUT 12-24 VDC
OUTPUT 12-24 VDC
Max. 6 A total
Use Class 2 power supply
OUTPUT 12-24 VDC
max. 4 A total
213 4
4ch PWM controller
CBU-PWM4-4
INPUT 12-24 VDC, 4 A
12-24 VDC Class 2
power supply
12 34
INPUT 12-24 VDC
OUTPUT 12-24 VDC
Max. 6 A total
Use Class 2 power supply
OUTPUT 12-24 VDC
max. 4 A total
21 34
4ch PWM controller
CBU-PWM4-4
INPUT 12-24 VDC, 4 A
12-24 VDC Class 2
power supply
Installation
Connect a Class 2 power supply with 12-24 VDC output voltage
to the input connector of CBU-PWM4-4. Make sure not to use a
constant current LED driver and make sure that the cable polarity
is correct.
The product has one shared positive output connector (+) and
each of the four channels have its own negative connector
(-). This is the most typical case with multichannel LED strips.
Connect the LED load wires accordingly.
CBU-PWM4-4 can be configured having different types of outputs,
such as 4 channel RGBW, 3 channel RGB and 2 channel
TW. Also, it is possible to configure 1-4 jointly and individually
dimmable channels. These configurations can be made by the
end user from Casambi App. As default, CBU-PWM4 is
delivered with RGBW configuration.
CBU-PWM4-4 is a UL Listed Open-Type device which means that
it will have to be used together with a Class 2 power supply with
maximum output power of 100 VA. The product can be installed
outside of junction box. Make sure to comply with National
Electric Code in installation and when selecting installation wires.

NOTES
Project:
Reference type:
Item code:
Date:
Notes:
casambi.com
Compliance Statement
This device complies with part 15 of the FCC Rules. Operation is subject to the
following two conditions:
(1) This device may not cause harmful interference, and
(2) this device must accept any interference received, including interference that
may cause undesired operation.
Radiation Exposure Statement for FCC
This device complies with FCC radiation exposure limits for an uncontrolled
environment. This device shall be installed and operated with a minimum
distance of 0.8” (2cm) between users or bystanders and the device.
FCC Interference Statement
This equipment has been tested and found to comply with the limits for a
Class B digital device, pursuant to Part 15 of the FCC Rules. These limits
are designed to provide reasonable protection against harmful interference in
a residential installation.
This equipment generates, uses and can radiate radio frequency energy and, if
not installed and used in accordance with the instructions, may cause harmful
interference to radio communications.
However, there is no guarantee that interference will not occur in a particular
installation. If this equipment does cause harmful interference to radio or
television reception, which can be determined by turning the equipment off
and on, the user is encouraged to try to correct the interference by one of the
following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to
which the receiver is connected.
• Consult the dealer or an experienced radio/TV technician for help.
Radiation Exposure Statement for Canada
This device complies with Industry Canada’s licence-exempt RSSs.
Operation is subject to the following two conditions:
(1) This device may not cause interference
(2) This device must accept any interference, including interference that may
cause undesired operation of the device.
This equipment is exempt from the routine RF exposure evaluation requirements
of RSS-102. This equipment should be installed and operated with a minimum
distance of 20 cm between the antenna and the user or bystanders.
Le présent appareil est conforme aux CNR d’Industrie Canada applicables
aux appareils radio exempts de licence. L’exploitation est autorisée aux deux
conditions suivantes:
(1) l’appareil ne doit pas produire de brouillage;
(2) l’utilisateur de l’appareil doit accepter tout brouillage radioélectrique subi,
même si le brouillage est susceptible d’en compromettre le fonctionnement.
Ce matériel n’est pas sujet à l’évaluation habituelle d’exposition RF selon
RSS102. Ce matériel devrait être installé et exploité en gardant une distance
minimale de 20 cm entre l’antenne et l’utilisateur ou les spectateurs.
Other Casambi Controllers manuals
Popular Controllers manuals by other brands

KMC Controls
KMC Controls MEP-4 Series Application guide

Swagelok
Swagelok PRS15 user manual

Belimo
Belimo AFRB24-SR Wiring diagrams

Emerson
Emerson dixell WING XW260L Installing and operating instructions

Emerson
Emerson dixell WING XW260K Installing and operating instructions

RADEMACHER
RADEMACHER DuoFern 3500 30 64 Installation and commissioning manual