ccei NIVA 3 User manual

OPERATING INSTRUCTIONS
RNS-1, RNS-2 and
NIVA 3 Module
level regulation module
Réf : PF10L006 / PF10L002 / PF10L009
Table des matières
1. Technical specifications ......................................................................................................... 2
2. Pack contents ......................................................................................................................... 3
3. Installation ............................................................................................................................. 3
3.1. Connection to electricity ............................................................................................. 3
4. Device operation - function description ................................................................................. 6
4.1. Available features (depending on the version) ............................................................. 6
5. Installing the accessories ........................................................................................................ 7
5.1. MFP-2 floater (RNS-1) ............................................................................................... 7
5.2. SE-3 sensor (RNS-2) ................................................................................................... 7
5.3. SE-1 sensors (Niva-3) ................................................................................................. 8
A. Declaration of conformity ................................................................................................... 8
Read these instructions carefully before installing, commissioning and using
this product
MPNT0417 v1.0EN (02/01/2020)

OPERATING INS-
TRUCTIONS RNS-1, RNS-2 and NIVA 3 Module v1.0EN
1. Technical specifications
Power supply voltage 230V AC - 50Hz
Dimensions: 220 x 200 x 150 mm
Protection factor IP-55
Level sensor
Depending on the model:
• 1 MFP2 (SF140008) floater = RNS-1
• 1 SE-3 (SF140005) sensor = RNS-2
• 3 SE-1 (SF140017) sensors = NIVA-3
Outputs 1 24V AC - 6VA output for solenoid
1 dry contact output to manage pump prohibition
Forced operation output and corresponding indicator not active on
RNS-1, RNS-2 and NIVA 3 Module
2

OPERATING INS-
TRUCTIONS RNS-1, RNS-2 and NIVA 3 Module v1.0EN
2. Pack contents
1 module RNS-1, RNS-2 and NIVA 3 Module
1 24V solenoid
1levelsensor(differentdependingonthemodel)
1 screen filter (max pressure 4 bars)
1 Technical manual (this document)
3. Installation
3.1. Connection to electricity
Installation of this project involves a hazard of electric shocks. We strongly
recommend you contract a professional installer. Incorrect installation places
you in danger and may irreversibly damage the product and the equipment
connected to it.
For safety reasons and in compliance with the NF C15-100 standard, the box in
which the RNS-1, RNS-2 and NIVA 3 Module is installed must be
• either at 3.50 m from the pool edge. This distance takes into account the dis-
tance around obstacles. If the RNS-1, RNS-2 and NIVA 3 Module control
box is installed behind a wall, the distance will include the length of the path
taken to move around the wall to reach the box.
• or in an in-ground space immediately next to the swimming pool. In this case
the space must be accessible via a hatch which requires a tool to open it.
• downstream of a high sensitivity ground fault protection (30mA) in com-
pliance with the NF C15-100 standard
3

OPERATING INS-
TRUCTIONS RNS-1, RNS-2 and NIVA 3 Module v1.0EN
A. Pump prohibition (see below for more details)
B. 24V output for solenoid
C. Level sensor connection supplied with the box.
The connection differs depending on the level sensor being used. The lower part of the image (C)
describes the possible connections.
4

OPERATING INS-
TRUCTIONS RNS-1, RNS-2 and NIVA 3 Module v1.0EN
3.1.1. Pump prohibition connection
3.1.1.1. To a CCEI brand electric box
The electric boxes manufactured by CCEI are fitted with a pre-connected terminal block marked
ABCD for automatic level regulators.
•A and B: filtration pump forced operation (not used for RNS-1, RNS-2 and NIVA 3 Module)
•C and D: pump prohibition
All that remains to do is to remove the "shunt" between C and D on the filtration box and to connect
the 2 wires from the "Pump prohibition" output of the RNS-1, RNS-2 and NIVA 3 Module box
instead.
3.1.1.2. On a standard electric box
If the electric box is not pre-fitted for automatic level regulation, connect directly to the filtration
contact . The following information is given as an indication only. It is imperative to follow the
instructions for your pool electric box or to first contact your box manufacturer.
Pump prohibition:
Connect the Pump prohibition terminal block to terminal block A1 on the filtration contact
•A: existing wires in the filtration box
•B: filtration contact installed in the box
•C: wire to add to connect the pump prohibition to the box RNS-1, RNS-2 and NIVA 3 Module
Disconnect the wire or wires arriving on the A1 terminal block from the filtration contact and send
them to a terminal on the "Pump prohibition" screw terminal on the RNS-1, RNS-2 and NIVA
3 Module box. Then use another wire to connect the other "Pump prohibition" screw terminal to
terminal A1 on the filtration contact.
5

OPERATING INS-
TRUCTIONS RNS-1, RNS-2 and NIVA 3 Module v1.0EN
4. Device operation - function description
4.1. Available features (depending on the version)
4.1.1. Timer
In order to make the system insensitive to lapping water, the electronic system times level change
detection. The system only opens the filling solenoid when the detected level remains below the
threshold for 10 seconds.
Similarly, the solenoid will close when the level has stabilised over the threshold for 5 seconds.
4.1.2. Pump prohibition output
The RNS-1, RNS-2 and NIVA 3 Module has a Pump prohibition output that is used to prevent the
pump from running if there is not enough water.
4.1.3. Filling solenoid output
Using this output, the RNS-1, RNS-2 and NIVA 3 Module sends alternating 24V when filling is
required. Connect this output to the solenoid supplied with the module. When filling is active, the
LED lights.
4.1.3.1. Filling fault
If the high level is not reached after 3 hours, the box switches to monitoring mode for 30 minutes
and the indicator lights orange (green + red LEDs). After 30 minutes, if the level has still
not been reached, filling is cut and the pump prohibition remains active as a safety measure. The
indicator switches to red.
In this situation, check the level sensor and the filling solenoid. Turn the device off and on again
to reset the fault.
6

OPERATING INS-
TRUCTIONS RNS-1, RNS-2 and NIVA 3 Module v1.0EN
5. Installing the accessories
5.1. MFP-2 floater (RNS-1)
The MFP-2 floater is fixed in the skimmer. Pre-
ferably use silicone or neoprene adhesive and
make sure not to block the removal of the filte-
ring basket.
A. Floater
The device acts as an "on-off" switch. The floa-
ter height varies with the water level and when it
is below the horizontal position (as in the photo
for example), it activates filling and pump pro-
hibition.
Oncethe level hasbeen reached, thedevice stops
filling and restarts the filtration pump.
5.2. SE-3 sensor (RNS-2)
The SE-3 sensor is fixed in the skimmer. Prefe-
rably use silicone or neoprene adhesive.
A. High level
B. Low level
C. Ref. level
If the water level is above the high level (A), fil-
trationis authorised and automaticfilling is stop-
ped.
If the water level is below the low level (B), the
device stops filtration (pump prohibition) and
activates filling until the high level is reached
(A).
7

OPERATING INS-
TRUCTIONS RNS-1, RNS-2 and NIVA 3 Module v1.0EN
5.3. SE-1 sensors (Niva-3)
The 3 SE-3 sensors are placed in the skimmer, separately from
each other. We recommend installing them in a channel or a
PVC pipe to isolate them from the wall and keep them separate.
The sensors must be fixed at the required height to prevent them
from moving and avoid any pull on their wire. The sensor wires
must be guided so that they do not tangle.
A. High level (to connect to terminal 3)
B. Low level (to connect to terminal 4)
C. Ref. level (to connect to terminal M)
If the water level is above the high level (A), filtration is autho-
rised and automatic filling is stopped.
If the water level is below the low level (B), the device stops
filtration (pump prohibition) and activates filling until the high
level is reached (A), or stops after 3 hours (see Fault section)
A. Declaration of conformity
CCEI S.A.S (FR 47 40 35 21 693) declares that product RNS-1, RNS-2
and NIVA 3 Module is compliant with the safety and electromagnetic compati-
bility requirements of European directives E.M.C (2014/30/UE), Low voltage
(2014/35/UE), RoHS (2011/65/UE), WEEE (2002/96/CE) and REACH (1907/2006).
Emmanuel Baret
Marseille, on 02/01/2020
Distributor's stamp
Date of sale: . . . . . . . . . . . . . . . . . . . . . . . Batch N°: . . . . . . . . . . . . . . . . . . . . . . . . . . .
8
Other manuals for NIVA 3
1
This manual suits for next models
5
Table of contents
Other ccei Control Unit manuals
Popular Control Unit manuals by other brands

MIT
MIT KLA15 Series Translation of the original installation and maintenance manual

Omron
Omron trajexia CJ1W-MCH72 System configuration

WAGO
WAGO 750-492/040-001 manual

Toshiba
Toshiba IK-HR1CS instruction manual

TFT
TFT AXD1ST-NX-T Instructions for installation, operation and maintenance

Rosslare
Rosslare AC-C31 instruction manual