INSTALLATION MANUAL
GENERAL DESCRIPTION
This device is a conventional beacon that mounts on the low profile base.
This beacon is designed to flash every 2 seconds (0.5 Hz).
IMPORTANT GUIDELINES
Apply the guidelines below:
-be sure to install the beacon according to local standards and regulations;
-this product is designed for indoor use only;
-beacon should only be installed in environments where ambient temperature and humidity fall into the ranges specified in the
TECHNICAL SPECIFICATIONS table;
-only install in suitable environments, avoiding:
situations in which condensation exists;
situations in which corrosive gases exist;
situations in which obstacles exist, which could impede visual indication of the beacon;
hazardous areas;
-connect the adaptor base according to the scheme provided by this manual;
-constructor recommends that the minimum period of maintenance should be 1 year and that the following should be taken into
account:
a regular operation test should be performed;
a visual check for contamination and mechanical damage should be made.
TECHNICAL SPECIFICATIONS
L20-CBE1002-7200 (vA.1)
ADAPTOR BASE INSTALLATION
1) Select the position on the ceiling where you want to install the beacon.
2) Install the adaptor base in the selected ceiling position by inserting the screws in the
circles indicated in figure 1.
WIRING
The adaptor base has to be connected to a sounder / powered circuit and NOT to a zone.
BEACON PLACEMENT
1) Position the beacon centrally on its adaptor base ensuring it is level.
2) Rotate clockwise applying gentle pressure. The beacon will drop into its keyed location.
3) Continue to rotate clockwise a few degrees until the beacon has fully engaged in the adaptor base.
4) When the beacon is firmly engaged, check the alignment of the raised reference mark on the beacon and on the base (figure 4).
CEASEFIRE INDUSTRIES PRIVATE LTD., E6, UPSIDC Industrial area, Selaqui, Dehradun, Pin Code - 248001, Uttarakhand, India
12
Figure 1
Power supply range from 15 V to 40 V
Current draw in activated state 10 mA at 24 V
Power consumption in activated state 240 mW at 24 V
Installation location Ceiling
Maximum allowed height from ground 3 m as certified per EN 54-23
Horizontal coverage diameter 7.5 m at 3 m from the ground
as certified per EN 54-23
Coverage volume 132 m3at 3 m from the ground
as certified per EN 54-23
Category rating C-3-7.5 as certified per EN 54-23
Flash rate 0.5Hz 1 flash every 2 seconds
Flash color White
Temperature range -30 °C to +70 °C
Max humidity 85% RH no condensation
IP 21C
POWER (+)
POWER (-)
SHIELD SHIELD
Figure 2
Figure 3
Figure 4
WARNINGS AND LIMITATIONS
Our devices use high quality electronic components and plastic materials that are highly resistant to environmental deterioration.
However, after 10 years of continuous operation, it is advisable to replace the devices in order to minimize the risk of reduced
performance caused by external factors. Ensure that this device is only used with compatible control panels. Detection systems
must be checked, serviced and maintained on a regular basis to confirm correct operation.
Smoke detectors may respond differently to various kinds of smoke particles, thus application advice should be sought for spe cial
risks. Detectors cannot respond correctly if barriers exist between them and the fire location and may be affected by special envi-
ronmental conditions.
Refer to and follow national codes of practice and other internationally recognized fire engineering standards.
Appropriate risk assessment should be carried out initially to determine correct design criteria and updated periodically.
WARRANTY
All devices are supplied with the benefit of a limited 3 years warranty relating to faulty materials or manufacturing defects, effective
from the production date indicated on each product.
This warranty is invalidated by mechanical or electrical damage caused in the field by incorrect handling or usage.
Product must be returned via your authorized supplier for repair or replacement together with full information on any problem identi-
fied.
Full details on our warranty and product’s returns policy can be obtained upon request.
TI-002271
CONVENTIONAL BEACON FLASH RATE 2HZ 928x/02
CEASEFIRE INDUSTRIES
PRIVATE LTD.
E6, Upsidc Industrial Area, Selaqui, Dehradun, Pin Code-
248001, Uttarakhand, India
19
CO0210CPR20140107
EN 54-23:2010
Fire alarm devices - Visual Alarm Device (VAD)
TI-002271
For use in compatible fire detection and alarm system.
Intended for use in and around buildings.
Type A - for indoor use only
Category rating: C-3-7.5
Duration of operation: Pass
Provision for external conductors: Pass
Flammability of materials: Pass
Enclosure protection: Pass
Access: Pass
Manufacturer's adjustments: Pass
On-site adjustment of behaviour: Pass
Requirements for software controlled devices: Pass
Coverage volume: Pass
Variation of light output: Pass
Minimum and maximum light intensity: Pass
Light colour: White
Light temporal pattern / frequency of flashing: Pass / 0.5 Hz
Marking and data: Pass
Synchronization: Pass
Durability -
Temperature resistance: Pass
Humidity resistance: Pass
Shock and vibration resistance: Pass
Corrosion resistance: Pass
Electrical stability: Pass
ANTI -TAMPER LOCK
The beacon should be locked to its base as a deterrent to intentional
removal performed by non authorized personnel.
To do this tear off the little locking element from the internal border of the
base and insert it in to its base recess as illustrated in figure 5.
To unlock the detector, insert the tip of a screwdriver into the side slot of
the base by exerting only a light pressure (figure 4), and release the
beacon by turning it anticlockwise.
TESTING
In order to test the functionality of the installed conventional beacon, the following test must be performed: activate an alarm condi-
tion on the control panel: beacon’s power supply line will be activated and, consequently, the beacon’s outputs.
Check that the beacons operate and flash as expected.
After the test has been performed the control panel must be reset from its alarm condition.
If the test fails for one or more devices, check if mistakes were made during installation or panel’s operation and correct them.
Test again.
If the beacon’s functionality is hopeless send back the device to your distributor for repair or substitution.
We suggest to test all device’s functionality after the installation has been completed.
MAINTENANCE
-Disable the fire security system in order to avoid unwanted fault warnings from the control panel.
-Remove the beacon from its base.
-Inspect the beacon at ground level and in good light.
-If the beacon shows any kind of impurity, clean up well its external surface with a clean, damp and lint-free cloth, especially the
lens’ visual output area.
-If the beacon shows cracks or breaks, especially in correspondence to the lens’ visual output area, substitute it with a new one.
-Reinstall the beacon.
-Retest the beacon.
Avoid to paint over the beacon or inhibit in any other way the flashing output’s intensity and area coverage.
Beacon must always be kept clean and in excellent conditions.
Figure 5
L20-CBE1002-7200 (vA.1)
CEASEFIRE INDUSTRIES PRIVATE LTD., E6, UPSIDC Industrial area, Selaqui, Dehradun, Pin Code - 248001, Uttarakhand, India
34
2831
+2*(+!#5/&$5$!.$%'-$5!,,5
$!.$%'-$5*#0./-'$.5 -'1!/$5')'/$#5
(+/5+55 $"+*#5 (++-5 $"/+-5 5
+'#!5 -$!/$-5 +'#!5 3,-$..2!45
+'#!5 55 //!-5 -!#$.&5*#'!5
/55 55
2225"$!.$%5'5-$2+-(#5"+)5+((+250.5+*5
!((5+0-5 -$$5+/('*$55
55 555555
+-5"!((5555

   

Other Ceasefire Security Sensor manuals

Ceasefire PRO-SENSE TI-002267 User manual

Ceasefire

Ceasefire PRO-SENSE TI-002267 User manual

Ceasefire INTELLI-SENSE TI-002229 User manual

Ceasefire

Ceasefire INTELLI-SENSE TI-002229 User manual

Ceasefire INTELLI-SENSE TI-002216 User manual

Ceasefire

Ceasefire INTELLI-SENSE TI-002216 User manual

Popular Security Sensor manuals by other brands

Optek AF45 instruction manual

Optek

Optek AF45 instruction manual

CTI CS-100 Calibration guide

CTI

CTI CS-100 Calibration guide

Renkforce 1270202 operating instructions

Renkforce

Renkforce 1270202 operating instructions

Alarmtech GD 335 instruction manual

Alarmtech

Alarmtech GD 335 instruction manual

Banner ES-FA-9AA instruction manual

Banner

Banner ES-FA-9AA instruction manual

Viking PB-1 product manual

Viking

Viking PB-1 product manual

DELTA DORE TYXAL DOI PVC installation guide

DELTA DORE

DELTA DORE TYXAL DOI PVC installation guide

Camp Safety SWIFTY VEST manual

Camp Safety

Camp Safety SWIFTY VEST manual

Apollo 58000-300APO installation guide

Apollo

Apollo 58000-300APO installation guide

Honeywell C7061A Product data

Honeywell

Honeywell C7061A Product data

Basalte SENTIDO RS485 installation manual

Basalte

Basalte SENTIDO RS485 installation manual

Azbil AUD300C1000 Series user manual

Azbil

Azbil AUD300C1000 Series user manual

Canon CXDI-Pro Instructions for use

Canon

Canon CXDI-Pro Instructions for use

EnviroTech Alarms LEAK-STOP Installation and operation manual

EnviroTech Alarms

EnviroTech Alarms LEAK-STOP Installation and operation manual

ASAHI CSR-3005E instruction manual

ASAHI

ASAHI CSR-3005E instruction manual

Global Fire Equipment GFE-S Series Installation Wiring Diagram

Global Fire Equipment

Global Fire Equipment GFE-S Series Installation Wiring Diagram

C.P. Electronics EBDSPIR-AT-DD installation guide

C.P. Electronics

C.P. Electronics EBDSPIR-AT-DD installation guide

Black Box EME1TH00C user manual

Black Box

Black Box EME1TH00C user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.