Celco Spider67 User guide

Spider67 I/O Module
----Profinet System Manual
ELCO (Tianjin) Electronics Co., Ltd
04/2019
Version 1.5

Spider67 Profinet–Extensible industrial fieldbus I/O System 2 / 62
Preface
1. Scope of this manual:
This manual applies to the ELCO Profinet Spider67 distributed I/O device.
The information in this manual enables you to run the Spider67 module on
Profinet in a distributed I/O device.
2. Basic knowledge requirements
This manual presumes a general knowledge in the field of automation
engineering and describes the components based on the data valid at the time of
its release.
ELCO reserves the right of including a product information for each new
component, and for each component of a later version.
3. Guide
This manual describes the hardware of the Profinet Spider67 distributed I/O
device.
Covered topics are:
Installation and wiring
Commissioning and diagnostics
Components
Article numbers
Technical specifications
4. Technical support:
This manual describes the characteristics and the usage of a Spider67 distributed
I/O device.
Please contact your local ELCO representative or dial 400-608-4005 if you have
any questions about the products described in this manual.
Additional information about ELCO products is available:
http://www.elco-holding.com/
5. Disclaimer of liability:
We have reviewed the contents of this publication to ensure consistency with the
hardware and software described. Since variance cannot be precluded entirely,
we cannot guarantee full consistency. However, the information in this
publication is reviewed regularly and any necessary corrections are included in
subsequent editions.

Spider67 Profinet–Extensible industrial fieldbus I/O System 3 / 62
CONTENTS
PREFACE .................................................................................................................................2
1. PRODUCT OVERVIEW....................................................................................................5
1.1 Introduction .................................................................................................................................5
1.2 Applications .................................................................................................................................5
1.3 Features .......................................................................................................................................5
1.4 Type .............................................................................................................................................6
2. TECHNICAL CHARACTERISTICS.................................................................................8
2.1 Gateway.......................................................................................................................................8
2.2 I/O module...................................................................................................................................9
2.3 Extension cable ..........................................................................................................................10
2.4 Hardware ...................................................................................................................................11
2.4.1 Technical data of gateway ........................................................................................................11
2.4.2 Digital IO Module......................................................................................................................12
2.4.3 Analog IO Module.....................................................................................................................13
2.4.4 RTD and TC Module ..................................................................................................................14
2.5 LED display.................................................................................................................................15
3. INSTALLING.................................................................................................................... 17
3.1 Mounting dimensions ................................................................................................................17
3.1.1 Gateway dimensions ................................................................................................................17
3.1.2 Module dimensions ..................................................................................................................18
3.2 Mounting position and dimensions............................................................................................19
3.3 Assigning names in PROFINET IO devices ...................................................................................20
3.3.1 Assigning names by Step7 ........................................................................................................20
3.3.2 Assigning names by Portal........................................................................................................21
3.4 Wiring Spider67..........................................................................................................................23
3.4.1 Connecting Spider67 to protective earth (PE) .........................................................................23

Spider67 Profinet–Extensible industrial fieldbus I/O System 4 / 62
3.4.2 Spider67 power supply.............................................................................................................23
3.4.3 Spider67 BUS connection .........................................................................................................25
3.4.4 Spider67 digital signal connection ...........................................................................................26
3.4.5 Spider67 analog signal..............................................................................................................29
4.1 Installation of configuration files................................................................................................33
4.2 Signal address assignment..........................................................................................................35
4.3 Instruction of Analog Value ........................................................................................................38
4.4 Module Startup Process .............................................................................................................43
4.5 Module configuration by Step7 ..................................................................................................44
4.6 Module configuration by Portal..................................................................................................52
5. ALARM DIAGNOSIS...................................................................................................... 59
5.1 LED fault indicator......................................................................................................................59
5.2 Diagnostic information...............................................................................................................61

Spider67 Profinet–Extensible industrial fieldbus I/O System 5 / 62
1. Product overview
1.1 Introduction
Spider67 from ELCO supports modern installation methods with a new and
revolutionary expandable I/O system. The simple and easy to install Fieldbus
system Spider67 is especially suitable for applications in rough environments.
1.2 Applications
Recently, the wide-range usage of industrial fieldbus I/O products brought deep
impact to the automation industry. The traditional centralized control method
was replaced by intelligent distribution devices. Besides that, more devices were
transferred from cabinets directly to the site. Therefore the reason lies in saving
costs, reducing the operation time and shorten the maintenance period. It also
optimizes the system procedure.
ELCO Spider67 exactly complies this tendency and represents a revolutionary
new generation of I/O solutions. Spider67 is an expandable industrial fieldbus I/O
product with protection class IP67. It supports standard industrial bus protocol
gateways (such as Profibus-DP, Profinet, EtherCAT, CC-Link) and diversified
extended I/O configuration modules and can easily be connected to PLC systems.
Compared to the traditional IP67 I/O products, Spider67 expanded modules
include digital modules, analog modules and high-speed counting modules etc.
Regarding its functions, Spider67 can meet most of the requirements, e.g.
processing concentrated / dispersed switch signals etc. At the same time, this
product series offers flexible connection cable and can directly be mounted on a
cage lifter or rotational device.
1.3 Features
IP67 protection class leading to convenient mounting
Compact design minimizes mounting space requirement
Standard connection, fast, safe and reliable
Various input and output signals
Flexible I/O configuration with a combination of analog, digital, and function
modules
LED status indication, fast function diagnosis
Can be combined with Spider67 system at random

Spider67 Profinet–Extensible industrial fieldbus I/O System 6 / 62
1.4 Type
No.
Type
Description
1
SPPN-GW-001
Profinet substation interface module
1 male 7/8”power supply
2 female, M12 D-Code fieldbus interface
4 female, M12 B-Code extended interface
2
SPDB-0800D-001
SPDB-0800D-003
8 PNP/NPN switches or dry contact
4-female, M12 A-Code interface
3
SPDB-0800D-011
SPDB-0800D-013
8 PNP/NPN switches or dry contact
8-female, M8 interface, 3-pin
4
SPDB-0404D-001
SPDB-0404D-003
4 PNP/NPN switches or dry contact
4DI4DO, 0.5A each channel
4-female, M12 A-Code interface
5
SPDB-0404D-011
SPDB-0404D-013
4 PNP/NPN switches or dry contact
4DI4DO, 0.5A each channel
8-female, M8 interface, 3-pin
6
SPDB-08UP-001
8DI+DO, configurable
4-female, M12 A-Code interface
7
SPDB-08UP-011
8DI+DO, configurable
8-female, M8 interface, 3-pin
8
SPDB-0008D-001
8DO, 0.5A each channel
4-female, M12 A-Code interface
9
SPDB-0008D-011
8DO, 0.5A each channel
8-female, M8 interface, 3-pin
10
SPDB-0006D-001
8DO, 2A each channel
1-male, M12 A-Code interface
3-female,M12 A-Code interface
11
SPDB-0300A-001
3AI
0~20mA, 4~20mA, ±20mA optional
3-female, M12 A-Code interface
12
SPDB-0300A-002
3AI
0~10V, ±10V optional
3-female, M12 A-Code interface

Spider67 Profinet–Extensible industrial fieldbus I/O System 7 / 62
13
SPDB-0003A-001
3AO
0~20mA, 4~20mA, ±20mA optional
3-female, M12 A-Code interface
14
SPDB-0003A-002
3AO
0~10V, ±10V optional
3-female, M12 A-Code interface
15
SPDB-0400A-005
4AI RTD
PT100,PT200,PT500,PT1000,Ni100,
Ni1000,150/300/600/3000Ω
4-female, M12 A-Code interface
16
SPDB-0400A-006
4AI Thermocouple
B,E,J,K,N,R,S,T
4-female, M12 A-Code interface
17
BB6S30P01Dxxx
BB6S30P01Mxxx
Pre-wired extensible cable
PVC, 5-core shielded, outer diameter 6.5mm
Customized length, D=cm,M=dm
18
BB6S30P03Dxxx
BB6S30P03Mxxx
Pre-wired extensible cable(drag chain)
PUR, 5-core shielded, outer diameter 6.5mm
Customized length, D=cm,M=dm
19
BB6S30P09Dxxx
BB6S30P09Mxxx
Pre-wired extensible cable(long distance
communication)
PVC, 5-core shielded, outer diameter 8mm
Customized length, D=cm,M=dm
20
BB6S06
Extension terminal resistance
Connecting to the last I/O module

Spider67 Profinet– Extensible industrial fieldbus I/O System 8 / 62
2. Technical characteristics
2.1 Gateway
The following picture is the schemac of Spider67 gateway.
Each gateway occupies one sub-staon address, maximum 4 strings, up to 6 I/O
modules / string, extending distance up to 100 m.
In order to achieve the PROFINET network communicaon requirements based on
the industrial Ethernet, Spider67 gateway, as the slave staon of PROFINET, can
assign the device name and the corresponding IP address via the configuraon tool,
it also can automacally assign IP addresses by PLC according to the network
topology. Each Spider67 gateway can connect up to 24 I/O modules via extended
port; sort the modules for 1~24 according to the sequence of the connected
extension port and the gateway distance from near to far, and configure in
programming soware Step7(see secon 4.4). If the module is connected to the
extended port not up to 6, then the number of the following module will be moved
Power interface:
24VDC, 2 independent power supply
Power supply for system and extensible module
Extension interface
4×M12,6 for each interface
Seng/Display
Set address and rate
Display operang status and fault message
Communicaon interface
Standard interface based on different protocols

Spider67 Profinet–Extensible industrial fieldbus I/O System 9 / 62
ahead, such as P0 port connect 3 modules, then the serial number of the first
module of P1 port is 4, by analogy, the serial number is the module number that you
connected.
2.2 I/O module
The picture is the schematic of a Spider67 I/O module.
I/O modules of Spider67 are serial connected, and are connected to In of 1st module
by extension cable, then Out of 1st module to In of 2nd, up to 6 modules.
Spider67 I/O modules are designed by the same housing dimensions, including
digital, analog, input and output, only 2 different interfaces, 4-M12 and 8-M8. M12
A-Code, 2 digital or 1 analog are available. M8, 3-pin, 1 digital is available.
Extension interface
In/out, serial
1 cable for communication and power supply
I/O interface:
4×M12
8×M8

Spider67 Profinet–Extensible industrial fieldbus I/O System 10 / 62
2.3 Extension cable
Spider67 extension cable is used between gateways and I/O modules. The overall
cable length from the extension interface to the last module is less than 100m .
P01 series cable is the standard extension cable. P09 series long distance
communication cable is recommended if the extension distance is over 10m or
high load current, P03 series flexible communication cable is especially used for
bending lifespan like drag chain (see 1.4)
Terminal resistance is recommended to eliminate reflection and echo, which are
used to prevent discontinuous extensible cable resistance or interference caused
by long distance communication. As Spider67 is installed terminal resistance,
users need to connect a resistance to Out of the last module of each extension
interface.

Spider67 Profinet–Extensible industrial fieldbus I/O System 11 / 62
2.4 Hardware
2.4.1 Technical data of gateway
Type
SPPN-GW-001
Extensible channel
4 (P0~P3)
Extensible module/channel
4
Extension distance
Max. 100m
Profinet input
D-Code M12(Female)
Profinet output
D-Code M12(Female)
Extension channel
B-Code M12(Female)
Power input
7/8”(Male,)
UMOD
24VDC (18~30V)
USP
24VDC (18~30V)
Operation current
<200mA
Max. output current
6A/channel,total for gateway 8A
Operation temperature
-25℃…70℃
Storage temperature
-40℃…85℃
Shock resistance grade
Comply with IEC60068-2-6
EMC
EN 61000-6-2
Protection class
IP67
Operating life
100,000 hours

Spider67 Profinet–Extensible industrial fieldbus I/O System 12 / 62
2.4.2 Digital IO Module
Type
SPDB-0800D-001
SPDB-0800D-011
SPDB-0800D-003
SPDB-0800D-013
SPDB-0404D-001
SPDB-0404D-011
SPDB-0404D-003
SPDB-0404D-013
SPDB-08UP-001
SPDB-08UP-011
SPDB-0008D-001
SPDB-0008D-011
SPDB-0006D-001
Input points
8
4
Max 8
0
0
Output points
0
4
Max 8
8
6
Extension input
B-Code M12(Male)
Extension output
B-Code M12(Female)
Input and output
Signal
A-Code M12(Female)
Maximum output
current
Each channel 0.5A,module 4A
Each channel 2A,
Module 8A
Input response
frequency
30Hz
Output voltage
USP -0.7V
Signal type
PNP/NPN
Input point
Supply current
Holding current 200mA,Action current 400mA
Normal input
voltage
24VDC (10~30V)
Operation
temperature
-25℃…70℃
Storage
temperature
-40℃…85℃
Anti-vibration
Class
IEC60068-2-6
Anti-interference
EMC
EN 61000-6-2
Protection class
IP67
Operating life
100,000 hours

Spider67 Profinet–Extensible industrial fieldbus I/O System 13 / 62
2.4.3 Analog IO Module
Model
SPDB-0300A-001
SPDB-0300A-002
SPDB-0003A-001
SPDB-0003A-002
Input points
3
3
0
0
Output points
0
0
3
3
Extension input
B-Code M12(Male)
Extension
output
B-Code M12(Female)
Input and
output Signal
A-Code M12(Female)
Input range
0~20mA
4~20mA
-20~20mA
0~5V
0~10V
-5~5V
-10~10V
Null
Null
Output range
Null
Null
0~20mA
4~20mA
0~5V
0~10V
-5~5V
-10~10V
Internal
impedance
<125Ω
<100kΩ
>450Ω
>1kΩ
Resolution
14Bit
Measurement
accuracy
±0.3%
Input point
Supply current
Max. 200mA
Operation
temperature
-25℃…70℃
Storage
temperature
-40℃…85℃
Anti-vibration
Class
IEC60068-2-6
EMC
EN 61000-6-2
Protection class
IP67
Operating life
100,000 hours

Spider67 Profinet–Extensible industrial fieldbus I/O System 14 / 62
2.4.4 RTD and TC Module
Model
SPDB-0400A-005
SPDB-0400A-006
Input points
4
Output points
0
Extension input
B-Code M12(Male)
Extension
output
B-Code M12(Female)
Input and
output Signal
A-Code M12(Female)
Input range
PT100,PT200,PT500,PT1000
Ni100,Ni1000
0~150/300/600/3000Ω
Type B,E,J,K,N,R,S,T
Output range
Null
Null
Internal
impedance
250Ω
1MΩ
Resolution
14Bit
Measurement
accuracy
±0.2%
Input point
Supply current
Max. 200mA
Operation
temperature
-25℃…70℃
Storage
temperature
-40℃…85℃
Anti-vibration
Class
IEC60068-2-6
EMC
EN 61000-6-2
Protection class
IP67
Operating life
100,000 hours

Spider67 Profinet–Extensible industrial fieldbus I/O System 15 / 62
2.5 LED display
Gateway display
Extension
communication
indication
Extension power supply
indication
Gateway status indication
Profinet indication
Umod indication
Profinet indication
Usp indication

Spider67 Profinet–Extensible industrial fieldbus I/O System 16 / 62
I/O module display
Address assignment
input indication
Extension
communication
indication
Address assignment
output indication
Module status
indication
Signal/status indication

Spider67 Profinet–Extensible industrial fieldbus I/O System 17 / 62
3. Installing
3.1 Mounting dimensions
3.1.1 Gateway dimensions

Spider67 Profinet–Extensible industrial fieldbus I/O System 18 / 62
3.1.2 Module dimensions

Spider67 Profinet–Extensible industrial fieldbus I/O System 19 / 62
3.2 Mounting position and dimensions
Spider67 can be mounted in any position.
The following table shows the mounting dimensions of Spider67 gateway and I/O
module.
Gateway
I/O module
Mounting width
60mm
30mm
Mounting height
165mm
155mm
Mounting depth
39mm (without connector)
33.5mm (without connector)

Spider67 Profinet–Extensible industrial fieldbus I/O System 20 / 62
3.3 Assigning names in PROFINET IO devices
Each Profinet protocol of a Spider67 distributed I/O device is assigned to a unique
device ID (i.e. MAC address) at the factory, while the addressing to each Spider67
device is based on the device name during configuration and according to the user
program. Therefore, it is necessary to assign names for gateway of each Spider67 I/O
devices before the configuration and debugging.
3.3.1 Assigning names by Step7
It is convenient to assign names and IP addresses in PROFINET IO devices through
SIEMENS Step7 software, please carry out the following steps:
1) Provide power for the Spider67 gateway and connect it to engineering computer
in the same network via a switch or cable connection.
2) In the Step7 software HW-Config, select PLC > Ethernet > Edit Ethernet Node
3) In the pop-up window, click Browse button, select the Spider67 gateway via the
MAC address to assign device name and confirm.
4) Assign the device name for Spider67 module by clicking button Assign Name in the
dialog "Edit Ethernet Node".
5) Assign the new IP address directly to Spider67 module by clicking the button
Other manuals for Spider67
1
This manual suits for next models
1
Table of contents
Popular Control Unit manuals by other brands

S&T
S&T Kontron SDML-WLU0 Series user guide

Blindleistungsregler
Blindleistungsregler TSM-AT quick start guide

Hirschmann
Hirschmann Rotarus PK 10-16 instruction manual

Keysight
Keysight N7562A user guide

Leviton
Leviton SPLCH installation instructions

LOVATO ELECTRIC
LOVATO ELECTRIC EXP10 31 quick start guide