Centork 482 Series Mounting instructions

Centork quarter-turn
electric actuators series 480
centronik units with Profibus DP
Installation and maintenance
user manual


Installation and maintenance user’s manual Pag 1
THIS USER MANUAL HAS BEEN DEVELOPED FOR ELECTRIC
ACTUATOR 482, 483, 484 AND 485 SERIES WITH PROFIBUS-DP, AND
CENTRONIK UNIT
CAUTION
Electric actuators are a high value devices. In order to prevent damage in their
handling, setting and use it is essential to follow and observe all the points in this user
manual, operate under actuators’ designated use, and observe health and safety rules,
standards and directives, as other national regulations as well.
Electric actuators must be handled with care and caution.
IMPORTANT NOTE
The contents in this manual is subject to change due to the quality improvement without
individual notice

Pag 2 Installation and maintenance user’s manual
Index
1CENTORK ELECTRIC ACTUATORS: INTRODUCTION......................................................................... 6
2SAFETY INSTRUCTIONS ........................................................................................................................ 6
3TRANSPORT AND STORAGE................................................................................................................. 7
3.1 Transport .......................................................................................................................................... 7
3.2 Storage and commissioning ............................................................................................................. 7
4CONDITIONS OF SERVICE FOR ELECTRIC ACTUATORS.................................................................. 8
4.1 Electric actuator: Main description and purpose .............................................................................. 8
4.2 Operation modes: OFF, LOCAL and REMOTE mode ..................................................................... 8
4.2.1 OFF mode. ................................................................................................................................... 8
4.2.2 LOCAL mode. .............................................................................................................................. 8
4.2.3 REMOTE mode............................................................................................................................ 9
4.3 Temperature range........................................................................................................................... 9
4.4 Actuator and motor duty service....................................................................................................... 9
4.5 IP protection degree ....................................................................................................................... 10
4.6 Painting and protection against corrosion ...................................................................................... 10
5ABOUT PROFIBUS-DP .......................................................................................................................... 11
5.1 General description ........................................................................................................................ 11
5.2 Network overview ........................................................................................................................... 11
5.3 Technical features for PROFIBUS-DP ........................................................................................... 12
6CENTORK PROFIBUS-DP INTERFACE OVERVIEW........................................................................... 13
6.1 Mechanical overview ...................................................................................................................... 13
6.2 Protocol & Supported Functions..................................................................................................... 13
6.3 Physical Interface ........................................................................................................................... 13
6.4 Configuration & Indications ............................................................................................................ 13
6.5 Data Exchange............................................................................................................................... 13
7MOUNTING TO THE VALVE.................................................................................................................. 14
7.1 Pre-Installation Inspection .............................................................................................................. 14
7.2 ACTUATOR MOUNTING ...............................................................................................................14
8ELECTRICAL CONNECTIONS .............................................................................................................. 15
8.1 Wiring diagram (electric manoeuvre) .............................................................................................15
8.2 Terminal plan and wiring ................................................................................................................ 15
9PRELIMINARY TEST AND SETTINGS.................................................................................................. 16
9.1 Handwheel and Declutching........................................................................................................... 17
9.2 DIP-SWITCHES configuration........................................................................................................ 17
9.2.1 Operation mode ......................................................................................................................... 17
9.2.2 Digital or Relay Outputs configuration (only in ON/OFF duty)................................................... 18
9.2.3 Actuator and valve (Sense of rotation)....................................................................................... 18
9.2.4 Posicion transmitter range (only in Modulating duty and ON/OFF duty with display) ............... 19
9.2.5 Remote mode selection ............................................................................................................. 19

Installation and maintenance user’s manual Pag 3
9.3 Mechanical Travel Stop Adjustment ...............................................................................................20
9.4 Limit Switch Setting.........................................................................................................................20
9.5 Torque Switch Setting.....................................................................................................................20
9.6 Mechanical Position indicator Setting .............................................................................................21
9.7 Potentiometer setting ......................................................................................................................21
9.8 TPS 4-20 mA transmitter setting.....................................................................................................21
9.9 CENTRONIK setting procedure (only in Modulating and ON/OFF with display duty) ....................22
9.9.1 Setting mode – Password...........................................................................................................23
9.9.2 Control input signal (only in Modulating duty).............................................................................23
9.9.3 Polarity (only in Modulating duty)................................................................................................24
9.9.4 Zero and span for Control input and TPS (only in Modulating duty) ..........................................24
9.9.5 Digital outputs .............................................................................................................................26
9.9.6 Rest time.....................................................................................................................................26
9.9.7 Valve opening curves (only in Modulating duty).........................................................................27
9.9.8 Emergency shut down ................................................................................................................28
9.9.9 Fieldbus safe mode (BF) ............................................................................................................29
9.9.10 Deadband (only in Modulating duty).......................................................................................29
9.9.11 Autolearn (only in Modulating duty)........................................................................................30
9.9.12 Close tightly (only in Modulating duty)....................................................................................30
9.9.13 Blinker.....................................................................................................................................31
9.9.14 Control input and TPS setting ................................................................................................32
9.9.15 Data logging ...........................................................................................................................32
9.9.16 New Password........................................................................................................................33
9.10 LOCAL mode: Control and displays elements................................................................................33
9.10.1 Lockable selector....................................................................................................................33
9.10.2 Push-buttons ..........................................................................................................................34
9.10.3 LED indications.......................................................................................................................34
10 FIELDBUS CONFIGURATION................................................................................................................35
10.1 Fieldbus Connector .........................................................................................................................35
10.1.1 Centork connector ..................................................................................................................35
10.1.2 D-SUB connector pinout (OPTIONAL)..................................................................................35
10.2 Configuration...................................................................................................................................36
10.2.1 CENTRONIK unit configuration..............................................................................................36
10.2.2 Baudrate .................................................................................................................................36
10.2.3 Termination.............................................................................................................................36
10.2.4 Node Address.........................................................................................................................36
10.2.5 GSD file ..................................................................................................................................37
10.2.6 Indications ..............................................................................................................................37
11 FIELDBUS PROGRAMMING ..................................................................................................................38
11.1 MODULATING CENTRONIK units .................................................................................................38
11.1.1 Status .....................................................................................................................................40
11.1.1.1 Selector-dip....................................................................................................................40
11.1.1.2 P1...................................................................................................................................40
11.1.1.3 P2...................................................................................................................................40
11.1.1.4 Remote inputs................................................................................................................40
11.1.1.5 Remote outputs .............................................................................................................40
11.1.1.6 Phase.............................................................................................................................40
11.1.1.7 Overtravel OP ................................................................................................................40
11.1.1.8 Overtravel CL.................................................................................................................40
11.1.1.9 Nominal input.................................................................................................................40
11.1.2 Parameter group1...................................................................................................................41
11.1.2.1 Nominal input type .........................................................................................................41
11.1.2.2 Nominal input (mA) ........................................................................................................41
11.1.2.3 Polarity ...........................................................................................................................41

Pag 4 Installation and maintenance user’s manual
11.1.2.4 Nominal input zero ........................................................................................................ 41
11.1.2.5 % opening zero ............................................................................................................. 41
11.1.2.6 Nominal input span ....................................................................................................... 41
11.1.2.7 % opening span ............................................................................................................ 41
11.1.2.8 Rest time .......................................................................................................................42
11.1.2.9 Autolearn.......................................................................................................................42
11.1.2.10 Relay 1 .......................................................................................................................... 42
11.1.2.11 Relay 2 .......................................................................................................................... 42
11.1.2.12 Relay 3 .......................................................................................................................... 43
11.1.2.13 Relay 4 .......................................................................................................................... 43
11.1.2.14 Relay 5 .......................................................................................................................... 43
11.1.2.15 Internal Dead Band OP (Opening)................................................................................ 44
11.1.2.16 External Dead Band OP(Opening)................................................................................ 44
11.1.2.17 Internal Dead Band CL (Closing) .................................................................................. 44
11.1.2.18 External. Dead Band CL (Closing)................................................................................ 44
11.1.2.19 Blinker ........................................................................................................................... 44
11.1.3 Parameter group2.................................................................................................................. 45
11.1.3.1 Close tightly...................................................................................................................45
11.1.3.2 Tightly Value ................................................................................................................. 45
11.1.3.3 BF Mode........................................................................................................................ 45
11.1.3.4 BF Time.........................................................................................................................45
11.1.3.5 Curve Type.................................................................................................................... 45
11.1.3.6 ESD Mode..................................................................................................................... 46
11.1.3.7 ESD............................................................................................................................... 46
11.1.4 Records (Data logging)..........................................................................................................46
11.1.4.1 Num Op Limit ................................................................................................................ 46
11.1.4.2 Num Cl Limit.................................................................................................................. 46
11.1.4.3 Num Op torque.............................................................................................................. 47
11.1.4.4 Num Cl torque ............................................................................................................... 47
11.1.4.5 Num Hours .................................................................................................................... 47
11.1.4.6 Num Powering............................................................................................................... 48
11.1.5 Writing and reading code samples ........................................................................................ 48
11.2 ON /OFF with position display CENTRONIK units........................................................................ 49
11.2.1 Status..................................................................................................................................... 51
11.2.1.1 Selector-dip ................................................................................................................... 51
11.2.1.2 P1.................................................................................................................................. 51
11.2.1.3 P2.................................................................................................................................. 51
11.2.1.4 Remote inputs ............................................................................................................... 51
11.2.1.5 Remote outputs............................................................................................................. 51
11.2.1.6 Phase ............................................................................................................................ 51
11.2.2 Records (Data logging)..........................................................................................................52
11.2.2.1 Num Op Limit ................................................................................................................ 52
11.2.2.2 Num Cl Limit.................................................................................................................. 52
11.2.2.3 Num Op torque.............................................................................................................. 52
11.2.2.4 Num Cl torque ............................................................................................................... 53
11.2.2.5 Num Hours .................................................................................................................... 53
11.2.2.6 Num Powering............................................................................................................... 53
11.2.3 Reading and writing examples .............................................................................................. 54
11.3 ON/OFF CENTRONIK units ........................................................................................................... 55
11.3.1 Status..................................................................................................................................... 56
11.3.1.1 Selector-dip ................................................................................................................... 56
11.3.1.2 P1.................................................................................................................................. 56
11.3.1.3 P2.................................................................................................................................. 57
11.3.1.4 Remote inputs ............................................................................................................... 57
11.3.1.5 Remote outputs............................................................................................................. 57
11.3.1.6 Phase ............................................................................................................................ 57
11.3.2 Reading and writing examples .............................................................................................. 58
12 trouble shooting....................................................................................................................................... 59
12.1 Front panel indication fault ............................................................................................................. 59

Installation and maintenance user’s manual Pag 5
12.2 Actuator does not operate in LOCAL mode ....................................................................................59
12.3 Actuator does not operate correctly in REMOTE mode..................................................................59
12.4 Actuator turn in the wrong sense ....................................................................................................59
12.5 Digitals outputs does not work ........................................................................................................60
12.6 Fieldbus communication .................................................................................................................60
12.6.1 Troubleshooting diagram........................................................................................................60
12.6.2 Front mounting LED’s.............................................................................................................60
12.6.3 Watchdog LED .......................................................................................................................61
13 MAINTENANCE.......................................................................................................................................62
13.1 After commissioning........................................................................................................................62
13.2 Maintenance for service..................................................................................................................62
13.3 Electric actuator’s service life..........................................................................................................62
13.4 Fuse replacement ...........................................................................................................................62
14 TECHNICAL SUPPORT ..........................................................................................................................63
NOTES .............................................................................................................................................................72

Pag 6 Installation and maintenance user’s manual
1 CENTORK ELECTRIC ACTUATORS: INTRODUCTION
The electric actuator is a device designed to be coupled to a general purpose industrial valve, to carry
out its movement. The movement is stopped by limit switching or by torque switching. Other applications
should be consulted CENTORK before. CENTORK is not liable for any possible damages resulting from
use in other than designated applications. Such risk lies entirely on the user.
2 SAFETY INSTRUCTIONS
The scope of this manual is to enable a competent user to install, operate, adjust and inspect a
CENTORK electric actuator. These instructions must be observed, otherwise a safe operation of the
actuator in no longer warrantee.
When handling electric equipment, the health and safety standards (EN 60.204, 73/23/EEC
directives) and any other national legislation applicable must be observed.
As electric device, during electrical operation certain parts inevitably carry lethal
voltages and currents (ELECTRICAL RISKS).
Works on the electrical system or equipment must only be carried out by a skilled electrician
himself or by specially instructed personnel, in accordance with the applicable electrical
engineering rules, health and safety Directives and any other national legislation applicable.
Electric actuators are powerful apparatus. A negligence handling might cause severe
damages to valves, people, and actuator as well. Under no circumstances should
any modification or alteration be carried out on the actuator as this could very well
invalidate the conditions which the device was designed.
Under operation, motor enclosure surfaces can reach high temperatures (up to
100ºC). Protection measures should be taken into acount in order to prevent people
and goods from it.

Installation and maintenance user’s manual Pag 7
3 TRANSPORT AND STORAGE
3.1 Transport
− CENTORK electric actuators must be transported in sturdy packing. During transport measures
should be adopt in order to prevent impacts, hits. CENTORK delivers its actuators ex-work.
− Hits or impacts against wall, surfaces or objects might cause severe damage on Electric actuator.
In this cases, after such events, a technical inspection must be done by CENTORK technicians.
− Do not attach to the handwheel ropes or hooks to lift by hoist.
− The valve-actuator unit can NOT be lifted/manipulated employing any lifting point of the actuator;
Actuator has beend designed and sized in order to motorize industrial valves, and withstand the
forces and torque required.
− Each Actuator is delivered with a set of technical documentation (User manual, datasheet,
diagrams…) which has to be carefully stored.
3.2 Storage and commissioning
− Store in a clean, cool, dry and ventilated place. For other storage conditions or, and long
time periods (More than 5 months) contact to manufacturer.
− Check that electrical connection cover and switching and signalling unit cover and are correctly
closed ant tight.
− Cable entries on electrical connection cover must be sealed. Protection plug
supplied by CENTORK are only adequate for storing in dry and ventilated
places, for short period of time. In other conditions protection plug must be
replaced with metallic plug sealed with PTFE tape.
− Do not store the actuator directly on the ground!
− Cover it to protect it from dust and dirt. Cover the machined parts with
suitable protection against corrosion.
− Do not handle it by picking it up by the handwheel.
− Just when commissioning, CENTORK recommend a visual inspection in order to detect any
anomaly caused during the transport, and during the storage as well. Checking should
include a visual inspection of electric compartment, and switching and signalling unit .
− Each Actuator is delivered with a set of technical documentation (User manual, datasheet,
diagrams…) which has to be carefully stored.
− For further details, consult the technical sheet ‘Conditions for Transport and Storage’.
WARNING!
REPLACE WITH
SEALED WITH
METAL PLUG
PTFE TAPE

Pag 8 Installation and maintenance user’s manual
4 CONDITIONS OF SERVICE FOR ELECTRIC ACTUATORS
4.1 Electric actuator: Main description and purpose
− Electric actuator is an apparatus or device formed by a
electric motor, coupled to a main gearbox unit, which
transmits motion and torque to valves.
− Power supply and controls elements (transformer, relays,
leds, electronic boards…) are included in the Centronik
unit. Centronik unit has CPU microprocessor and
electronic boards: Electric actuator is operated and
controlled by means of these electronic and electric device
of the centronik unit, being supplyied with main power.
− Electric actuator can be controlled in LOCAL mode from
the centronik front panel or in REMOTE mode.
− Electric actuators actuators are provided with a
declutchable manual override system in order to operate
manually in case of emergency or fail of power supply.
− Electric actuator can be coupled directly to valve,
− The electric actuator is a device designed to be coupled to
a general purpose industrial valve, to carry out its
movement. The movement is stopped by limit switching or
by torque (thrust) switching. Other applications should be
consulted CENTORK before. CENTORK is not liable for
any possible damages resulting from use in other than
designated applications. Such risk lies entirely on the user.
4.2 Operation modes: OFF, LOCAL and REMOTE mode
Electric actuator can be controlled by the control station (REMOTE mode) and at the local control
(LOCAL mode). Centronik unit is equipped with local controls. The lockable selector switch
LOCAL/OFF/REMOTE allows the operation mode to be set.
4.2.1 OFF mode.
− In this operation mode, the actuator remains connected but does not responds to any order from the
front panel or from the remote control. The front panel control indicates only the power supply status
(led 5).
4.2.2 LOCAL mode.
− With the push buttons OPEN-CLOSE-STOP located on the centronik front panel, the actuator is
operated locally. 5 indication lights (LEDs) show the actuator status from the centronik front panel
(chapter 9.12.2).
− Push buttons are self-retaining type: Once the push button has been pressed , its order or action is
generated, and it remains “active” until a new order or command is generated, or any operation
event takes place such us a limit switch or torque signal, an anomaly action or any centronik function
or event. It is NOT necessary to keep “pressing” the pushbutton or the remote input.
I/O
I/O
I/O
I/O
…
PLC
Fieldbus
master
PLC
Fieldbus

Installation and maintenance user’s manual Pag 9
4.2.3 REMOTE mode.
Electric actuator with ON/OFF duty control:
− Electric actuator can be controlled by the control
station (REMOTE) with the commands OPEN-CLOSE-
STOP (self- retaining) or OPEN-CLOSE as option
(push to run operation), or with Fieldbus
communication.
− ON/OFF duty control means open loop control.
− With self-retaining operation, the actuator continues to
run as long as the STOP command from the control
system (digital input) is not being generated, or any
centronik operation condition takes place.
− With push to run operation (Inching mode) the actuator
continues to run as long as this command from the
control system (digital input) remains. It is necessary
to keep “pressing” the pushbutton or the remote input.
− Electronic position transmitter (0-4/20mA, 0-2/10V or
resistive value) can be employed, as option, which in
order to provide the real valve position indication.
Electric actuator with Modulating duty control:
− Electric actuator is equipped with an electronic integral
positioner which automatically positions the valve in
accordance with the analog input control signal (4/20mA
current signal and voltage signal as option) or the input
control from Fieldbus communication.
− Modulating duty control means close loop control. The
modulating duty registers and compares the analog input
control and the actual position value (Feedback signa
given by actuator position transmitter). The electric
actuator runs to OPEN or CLOSE direction, according to
the deviation detected.
− The modulationg behaviour is stabilised by determining
inner (internal) and outer (external) dead bands, rest
time and therefore the wear of valve and actuator can
be reduced.
4.3 Temperature range
CENTORK Electric actuators work in a temperature range from -20ºC to +65ºC.
4.4 Actuator and motor duty service
Electric actuator has been designed for valve motorization which requires ON-OFF and inching or
modulating duty service.
− ON-OFF duty service: Electric actuator has been designed as S2 20-50% Max 30min duty cycle at
nominal torque, according to IEC standards: Nominal torque is rated to 50% of max tripping torque
(100%), value marked on actuator nameplates. Higher nominal torques can reduce the actuator’s
service life and S2 duty cycle.
− Inching or modulating duty service: Electric actuators has been designed as S4 30-50%, at 1.200-
300 starts per hour, at nominal torque. Nominal torque is rated to 50% of max tripping torque
(100%), value marked on actuator nameplates. Higher nominal torques can reduce the actuator’s
service life and S4 duty cycle conditions.
OPEN loop control
centronik ON/OFF duty
Digital input
Open-Close-Stop Position transmitter
(TPS)
optional
CLOSE loop control
centronik Modulating duty
CONTROL
Sensor
Analog input
4-20 mA
Position transmitter
(TPS)

Pag 10 Installation and maintenance user’s manual
4.5 IP protection degree
− CENTORK Electric actuators are designed in their standard version with IP67 (acc. EN 60.529)
environmental protection although IP68 protection may be supplied on request.
− IP67 and IP68 protection degree is only guarantee employing proper protection plug and
cable gland (For cable entries), according to IP degree (See chapter ELECTRIC
CONNNECTIONS) .
− It is necessary to observe storing and maintenance rules written on TRANSPORT AND STORAGE
chapter as well.
4.6 Painting and protection against corrosion
− CENTORK has designed three protection degree: Standard protection, P1 and P2. For technical
details, consult CENTORK technical datasheets.
− Electric actuator are coated with a epoxy- two components primer (Film thickness depends on
protection class selected, actuators are coated with intermediates primers) followed by a
polyurethane component paint coat. The standard colour is blue RAL 5.003. Other colours are
possible (Option). Other film thickness under request.

Installation and maintenance user’s manual Pag 11
5 ABOUT PROFIBUS-DP
Nowadays information technology (IT) is increasingly determining growth in the world of automation.
The communications capability of devices and continuous, transparent information routes are
indispensable components of future-oriented automation concepts. ProfiBus represents one of the
best-known industrial FieldBus protocols from Europe. ProfiBus can be used in a very wide range of
applications as a multi-application communications link for industrial devices, as well as cell-level
communication.
Standardized as EN50.170, ensures manufacturers and users investments and guarantees the
independence of the manufacturer.
These user manual does not pretend to provide a detailed introduction to PROFIBUS-DP. If more
detailed information were needed, please refer to specialized bibliography.
5.1 General description
ProfiBus utilizes a non-powered two-wire (RS485) network. A ProfiBus Network may have up to 126
nodes. It can transfer a maximum of 244 bytes data per node per cycle. Communication (baud) rates
are selectable but overall end-to-end network distance varies with speed. Maximum Communication
(baud) rate is 12Mbps with a maximum distance of 100M (328ft). The maximum distance is 1200M
(3936 ft) at 93.75Kbps without repeaters.
ProfiBus connects to a wide variety of field devices including discrete and analog I/O, drives, robots,
HMI/MMI products, pneumatic valves, actuators, transducers, and flow measuring equipment.
The data flows by the field cyclically. The Master devices of the fieldbus, are the ones to control the
data flow cycles in the fieldbus. They are capable of sending messages without an external request.
The Slave devices are those that only can listen to the messages sent by a master and answer that
message if was sent to its address. CENTRONIK PROFIBUS-DP actuators can only be slave devices.
Typical slave devices are input/output devices, actuators and plant sensors. They never have bus
access, they only acknowledge or reply messages coming from a master.
5.2 Network overview
The media for the fieldbus is a shielded copper cable consisting of a twisted pair. The baudrate for the
bus is between 9.6 Kbaud to max. 12 Mbaud. The PROFIBUS-DP network can consist of 126 nodes
and the total amount of data for PROFIBUS-DP are 244 Byte out per node and 244 Byte in per node.
NOTE: Node No. 126 is only used for commissioning purposes and should not be used to exchange
user data.

Pag 12 Installation and maintenance user’s manual
5.3 Technical features for PROFIBUS-DP
The table below gives a summary of the technical features and the figure on the next side shows the
bus cycle time of a PROFIBUS-DP system.
Transmission technique: EIA RS 485 twisted pair cable or fiber optic
PROFIBUS DIN 19245 Part 1 9.6 Kbit/s up to 12Mbit/s, max. distance 200m at 1.5 Mbit/s
extendible with repeaters
Mono-Master or Multi-Master systems supported
Master Slave Devices, max. 126 stations possible
Communications: Peer-to-Peer (user data
transfer) or Multicast (synchronization)
Cyclic Master-Slave transfer and acyclic Master-Master data
transfer
Operate: cyclic transfer of input and output data
Clear: inputs are read and outputs are cleared
Stop: Only Master-Master functions are possible
Sync-Mode: Outputs are synchronized
Freeze-Mode: Inputs are synchronized
Cyclic user data transfer between DP-Master(s) and DP
Slave(s)
Activation or deactivation of individual DP-Slaves
Checking of the configuration of the DP-Slaves
Powerful diagnosis mechanisms, 3 hierarchical levels of the
diagnosis messages
Synchronization of inputs and/or outputs
Address assignments for the DP-Slaves over the bus with
Master class 2
Configuration of the DP-Master (DPM1) over the bus
Max. 244 bytes input and output data per DP-Slave, typical
32 bytes
All messages are transmitted with Hamming Distance HD=4
Watch-Dog Timer at DP-Slaves
Access protection for the inputs/outputs at the DP-Slaves
Data transfer monitoring with configurable timer interval at
the DP-Master (DPM1)
Cabling and installation: Connecting or disconnecting of stations without affection of
other stations
Functionality:
Security and protection mechanisms:
Summary Technical Features for PROFIBUS-DP
Medium access: Hybrid medium access
protocol according to DIN 19245 Part 1
Operation Modes:
Synchronization: enables
synchronization of the inputs and/or
outputs of all DP Slaves

Installation and maintenance user’s manual Pag 13
6 CENTORK PROFIBUS-DP INTERFACE OVERVIEW
This section provides an overview over the PROFIBUS-DP interface of the CENTRONIK electric
actuators.
6.1 Mechanical overview
The interface for Profibus-DP, located in the centroniik unit, is a slave node that can be read and
written to, from a Profibus-DP master station. The interface Profibus-DP will not initiate communication
to other nodes, it will only respond to incoming commands.
6.2 Protocol & Supported Functions
− Fieldbus type: PROFIBUS-DP EN 50.170 (DIN 19.245)
− Protocol version: ver. 1.10
− Protocol stack supplier: SIEMENS
− Extended functions supported: Diagnostics & User Parameter data.
− Auto baudrate detection supported. Baudrate range: 9.6 Kbit-12Mbit
− Hardware prepared for DP-V1 extensions.
− Save/Load configuration in Flash supported.
6.3 Physical Interface
− Transmission media: Profibus bus line, type A or B specified in EN50.170
− Topology: Master-Slave communication
− Fieldbus connectors: Standard Centork connecting terminals,9 pin female DSUB, on
demand.
− Cable: Shielded copper cable, Twisted pair
− Isolation: The bus is galvanically separated from the other electronics with an on board
DC/DC converter. Bus signals (A-line and B-line) are isolated via opto-couplers.
− Profibus-DP communication ASIC: SPC3 chip from Siemens.
6.4 Configuration & Indications
− Address range: 1-99.
− Maximum cyclic I/O data size: 244 bytes in, max 244 bytes out, max. 416 bytes total
− Maximum User Parameter data/Diagnostics length: 237 bytes.
− Bus termination switch onboard.
− LED-indications: ON-line, OFF-line, Fieldbus related diagnostic.
6.5 Data Exchange
− I/O data transmission: The interface only supports cyclic I/O data transmission.

Pag 14 Installation and maintenance user’s manual
7 MOUNTING TO THE VALVE
7.1 Pre-Installation Inspection
− Verify the actuators nameplate to insure correct model number, torque, operating speed, voltage and
enclosure type before installation or use.
− It is important to verify that the output torque of the actuator is appropriate for the torque
requirements of the valve and that the actuator duty cycle is appropriate of the intended application
7.2 ACTUATOR MOUNTING
− Do not lift the actuator by the handwheel. Do not attach to the handwheel ropes or hooks to
lift by hoist.
− The actuator may be mounted in any position
− The CENTORK quarter turn electric actuator Series are supplied with a female drive output.
ISO5211. Bolt patterns are provided for actuator mounting. The actuator drive bush is removable
for ease of machining (except for 480.006). To remove the drive bush, just take out the 2 fixing
screws.
− It is mandatory that the actuator be firmly secured to a sturdy mounting bracket or directly mounted
to the valve’s ISO mounting pad. High tensile bolts or studs with spring locking washers must be
used.
− The valve output shaft must be inline with the actuator output drive to avoid side-loading the shaft.
To avoid any backlash no flexibility in the mounting bracket or mounting should be allowed.
− Reserve the space for maintenance routines and tasks.

Installation and maintenance user’s manual Pag 15
8 ELECTRICAL CONNECTIONS
CAUTION: Safety instructions on chapter 2 must be observed. Work on electrical system or
equipment must only be carried out by skilled electrician.
8.1 Wiring diagram (electric manoeuvre)
Electric actuator datasheet, supplied with the actuator, includes a PROPOSED WIRING DIAGRAM,
delivered with other technical documentation.
Capacitors for single-phase A.C. motors are delivered with electric actuators. Each capacitor is
dimensioned according to motor voltage and power.
Features of electric and electronic components listed on appendix. Wiring diagram are included on
appendix.
8.2 Terminal plan and wiring
The electric connection diagram or terminal plan is depicted on Electric actuator datasheet,
supplied with the electric actuator, and it can be found printed on a label inside of electrical
compartment cover.
− Open the electrical cover.
− Feed the cable(s) through the cable glands . Fix proper cable
glands according to IP67 or IP68 protection degree.
Figure 8.2.1 Figure 8.2.2 Figure 8.2.3
A) Electric actuator with Plug-socket connectors (Figure 8.2.1) with screws
− Unscrew the attachment plate from the connection cover.
− With a suitable screwdriver, connect the cables for the control signals according to the electric
connection diagram.
B) Electric actuator with Terminals connection (Figure 8.2.2)
− With a suitable screwdriver (SD 0,6x3,5 DIN 5264-A), connect the cables for the control signals
according to the electric connection diagram (Figure 8.2.3).
Caution!
− Connect the earth cable terminal to the earth connection
located inside of electric connection cover (M5 screw hole).
− Once you have checked that the connections have been properly
carried out, close the connection cover and check the proper
connection, the state of the o-ring seal and the proper installation of
the latter, greasing it slightly. Fasten the 4 screws crosswise.
− Fix proper cable glands according to IP67 or IP68 protection degree.
Replace the protection plug with suitable metallic protection
plug sealed with PTFE . Tighten cable glands and protection plugs
to ensure enclosure IP67 (IP68 if applicable).
− Check that all cable glands are correctly tighten.
− Clean sealing faces at terminal cover and check whether O-ring is in
good condition. Mount cover and tighten cover bolts.
WARNING!
REPLACE WITH
SEALED WITH
METAL PLUG
PTFE TAPE

Pag 16 Installation and maintenance user’s manual
9 PRELIMINARY TEST AND SETTINGS
CAUTION: SAFETY INSTRUCTIONS described on chapter 2 must be observed. Work on
electrical system or equipment must only be carried out by skilled electrician.
− Before to start with the preliminary test, actuator should be correctly mounted on valve and correctly
wired as well, according to previous chapters (7 and 8).
− Operate or move the valve manually (Chapter 9.2) and check that the actuator rotates in the right
direction (Visual disc indicator or valve shaft could help for this). Instructions have been made for
standard electric actuators: CLOCKWISE TO CLOSE.
− Achieve the following setting procedure:
DIP-SWITCHES
Configuration
Chapter
9.3
Chapters
9.4
9.5
and
Chapters
9.7
9.10
to
Open and close
limit switch
adjustment
Optional elements
adjustment
Potenciometer
TPS
Auxilary limit switch
Chapter
9.3
Chapters
and
9.4
9.5
Chapters
to
9.7
9.10
Chapter
9.11
Chapter
10
Chapter
10
DIP-SWITCHES
Configuration
Open and close
limit switch
adjustment
Optional elements
adjustment
Programables parameter
adjustment
Fieldbus
Configuration
Fieldbus
Configuration
Potenciometer
TPS
Auxilary limit switch
ON/OFF duty
Modulating and ON/OFF with dispaly duty
Fieldbus
Programation
Chapter
11.3
Fieldbus
Programation
Chapter
Chapter
11.1
or
11.2

Installation and maintenance user’s manual Pag 17
9.1 Handwheel and Declutching
Quarter turn electric actuators are provided with a declutchable manual override system. The
override engagement lever returns automatically to auto position when the actuator is operated
electrically.
For 480.006 models
− In order to manually operate the actuator, take the key
wrench tool (See picture)
− Key wrench tool has to be coupled to square shaft of the
actuator in order to operate it.
− Turn clockwise to close and anti-clockwise to open.
For 480.010 models and higher
− In order to manually operate the actuator, pull the manual override
− Engagement lever towards the handwheel until it remains in position.
− Turn the handwheel until the valve reaches the required position
− Turn clockwise to close and anti-clockwise to open
9.2 DIP-SWITCHES configuration
Caution!
This is a sensitive electronic device. Manipulation of setting
switches should be mde very carrefuly, in a way that other
electronic components are not damaged.
In order to confugurate the Dip-switches, switch-off the Centronik unit
(led 5 OFF) and open the centronik front panel carefully. In the CPU
board, the Dip-switches are located as indicated in the next figure.
9.2.1 Operation mode
SW1 SW2 SW3 Operation mode
ON OFF OFF Open by limit switching and close by torque
switching
OFF ON OFF Open and close by limit switching
ON ON OFF Open and close by torque switching
Note: Open or close by torque switching means that the Centronik consider that the valve is close or
open when the open/close limit switch and the open/close torque switch are activated. Limit switch
must be adjust as in Open and close by limit switch.

Pag 18 Installation and maintenance user’s manual
9.2.2 Digital or Relay Outputs configuration (only in ON/OFF duty)
SW5 SW6 SW7 OUTPUT 1 OUTPUT 2 OUTPUT 3 OUTPUT 4 OUTPUT 5
OFF OFF OFF Valve
OPEN
Valve
CLOSE LOCAL REMOTE ANOMALY
ON OFF OFF
Overtorque
reached in
OPEN
Overtorque
reched in
CLOSE
LOCAL REMOTE ANOMALY
OFF ON OFF Valve
OPEN
Overtorque
reched in
CLOSE
LOCAL REMOTE ANOMALY
ON ON OFF Valve
OPEN
Valve
CLOSE
Overtorque
reched in
OPEN
Overtorque
reched in
CLOSE
ANOMALY
OFF OFF ON Valve
OPEN
Valve
CLOSE Overtorque Not used ANOMALY
Anomaly: Motor protection tripped, limit switch fault, torque switch fault, blinker fault or lost phase.
9.2.3 Actuator and valve (Sense of rotation)
Electric actuator and valve sense of rotation must be the
same. Electric actuator sense of rotation criteria is
CLOCKWISE TO CLOCK. Sense of rotation is critical for
many components (Microswitches, potentiometer,4-20
mA transmitter). A correct operation cannot be
warranty in case of different sense of rotation
valve/actuator)
− Operate the Electric actuator via handwheel (See
Manual operation chapter).
− Check that running the handwheel clockwise, valve
moves to close. If the turn direction is not correct,
stop immediately and verify.
− Configurate the dip-switch 4
SW4 Direction to close
ON Anti-clockwise
OFF Clockwise
Instructions have been made for standard electric actuators: CLOCKWISE TO CLOSE
This manual suits for next models
4
Table of contents
Other Centork Controllers manuals
Popular Controllers manuals by other brands

YASKAWA
YASKAWA SigmaLogic7 Compact Hardware manual

ROBO Cylinder
ROBO Cylinder RCP6 instruction manual

Easyrain
Easyrain Rain Bird ESP-TM Series Installation, Programming, & Operation

Chromalox
Chromalox 3340 Setting manual

Omron
Omron E5ED-B instruction manual

RLE Technologies
RLE Technologies SeaHawk LD310 quick start guide