Channel Safety Systems AlarmSense 2 ZONE User manual

2/4/8 ZONE CONVENTIONAL FIRE ALARM CONTROL PANEL
CHANNEL SAFETY SYSTEMS t: 0845 884 7000
Peterseld Business Park f: 0845 884 6000
Bedford Road
Peterseld
Hampshire e: sales@channelsafety.co.uk
GU32 3QA w: www.channelsafety.co.uk
AlarmSense
2/4/8 ZONE CONVENTIONAL FIRE ALARM
CONTROL PANEL

2/4/8 ZONE CONVENTIONAL FIRE ALARM CONTROL PANEL | 2
Contents
Safety ................................................................................................................................ 3
Important information regarding the safe use of this re alarm panel
Key Features ......................................................................................................................3
Lists the dierent features available on the range of conventional re alarm panels
Fire Alarm Systems - An Overview ...................................................................................4
How re alarm systems operate and a general overview of their key features
User Responsibilities .........................................................................................................5
General guidelines on what the user is expected to do
Panel Layout/Accessing the Controls ...............................................................................6
A summary of the controls and indicators available on this re alarm panel, including:
Control level denition
How to access the panel’s secure user functions
What the indicator lights mean
Fire Conditions ..................................................................................................................8
How an alarm is indicated, and how to deal with it
How to silence the alarm sounders
How to manually activate the alarm sounders (i.e. to evacuate the building)
How to reset a re alarm condition
Fault Conditions ................................................................................................................9
The dierent types of fault that may occur, what they mean and how to deal with them
Disablements ........................................................................................................................10
How to inhibit the functionality of certain parts of the re alarm system
Notes on Delays ...................................................................................................................12
Important information about delays, what they mean and what you should do about them

2/4/8 ZONE CONVENTIONAL FIRE ALARM CONTROL PANEL | 3
System Set-Up Data Chart ...................................................................................................13
Details of how the system has been set-up
Fire Alarm Log Book ............................................................................................................14
A place for you to record details of events such as res, false alarms, call outs, etc.
Certicate of Installation .................................................................................................................19
Certicate of Commissioning ...........................................................................................................20

2/4/8 ZONE CONVENTIONAL FIRE ALARM CONTROL PANEL | 4
SAFETY
The re alarm panel is safe to operate provided it has been installed in compliance with the manufacturer’s instructions and
used in accordance with this user manual.
Do not operate the re alarm panel with its enclosure open. There is no need to open the enclosure except to carry out com-
missioning, maintenance and remedial work. This work must only be carried out by competent service personnel who are fully
conversant with the contents of the separate engineering manual for this product and have the necessary skills for maintain-
ing this equipment.
If the enclosure is damaged in any way, expert advice should be sought regarding its repair.
Regular servicing of the re alarm system is highly recommended, preferably on a continuous maintenance contract and by a
competent organisation. A full-itemised report of the installation should be obtained at least annually.
KEY FEATURES
The key features chart (below) illustrates dierent features available in the range of re panels.
Hint: The panel label will help you identify the type. This user manual details all the available
Non-latching zonesfacility *
Zone delay facility
Coincidence
(double-knock) facility *
Zonetestfacility
Fault diagnostic facilities
Ancillary connections
for system expansion
On-boardrelays
(AUX Fire & Fault Output)
PANEL RANGE
PANEL FEATU R E S
Combined keypad and
keyswitch version available
Panel
LPCB Approved Panel
Program sounders
on new alarm
EN54 Parts 2 & 4Compliant
LPCB Approved
* Non-EN54 Part 2 panel features:
Coincidence
Non-latching zones facility

2/4/8 ZONE CONVENTIONAL FIRE ALARM CONTROL PANEL | 5
FIRE ALARM SYSTEMS – AN OVERVIEW
The primary purpose of a re alarm system is to provide an early warning of a re so that people and animals can be evacu-
ated and action taken to stop the re as soon as possible - all according to a predetermined plan.
Alarms may be raised automatically by smoke or heat detectors, or manually by a person operating a manual call point.
To ensure an alarm is dealt with in an orderly manner, it is important to know where the alarm is coming from. To aid this func-
tion, re alarm systems are usually split into zones, each covering a dierent area of a building.
When an alarm has been raised, the re alarm panel responds by indicating the zone in which the alarm has occurred and
activating all relevant sounders, bells and other alarm outputs to provide a warning of the re.
Additional alarm outputs available on the CFP range of re alarm panels (which may, or may not be used depending on the
requirements of the site) are:
• A Remote Output: this output is activated when the panel is in alarm and is returned to normal when the alarm sound-
ers are silenced. It may be used to signal an alarm condition to other parts of the re alarm system. If used, its function will be
declared on the System Set-Up Data Chart (page 13) of this manual. This output may be disabled if required.
• An Auxiliary Output: this output is activated when the panel is in alarm and is returned to normal when the panel is reset.
It may be used to signal an alarm condition to other parts of the re alarm system. If used, its function will be declared on the
System Set-Up Data Chart (page 13) of this user manual. This output may be disabled if required.
The building’s re management plan should always be executed when the re alarm panel goes into alarm.
See User Responsibilities (page 5) for further details.
Fault monitoring
For obvious reasons, the reliability of the re alarm system is paramount. To this end, the re alarm panel continuously moni-
tors all connections between detectors, manual call points and sounders and also checks it’s own power supply and back-up
batteries for faults.
If a fault is detected anywhere on the system, the panel responds by illuminating one or more of the Fault light(s) located on
the panel front and sounding its internal fault buzzer. The panel’s fault output is also activated, sending notication of the fault
(if connected) to a remote manned monitoring centre or other electronic equipment, as required.
Delays
Certain zones on a re alarm system can be prone to conditions that lead to frequent and unavoidable false alarms, a common
example being a loading bay lled with vehicle smoke. In such areas it may be acceptable to delay the activation of the alarm
sounders and other outputs to give a responsible person time to investigate the cause of the alarm. If the cause is found to be
a true re hazard, the delay can be overridden.
In the event of a false alarm, the panel can be reset. Should the delay period expire without any user intervention, the alarm
sounders will automatically sound to evacuate the premises. To ascertain if any delays have been programmed into the panel,
refer to the System Set-Up Data Chart (page 13).
Disablements
In abnormal conditions, certain parts of the re alarm system can be temporarily turned o (disabled) to suit prevailing condi-
tions. For example, if there is a risk of a false alarm occurring in a zone, say from vehicle exhaust smoke in a loading bay, it is
possible to disable that zone during the risk period, then enable it again afterwards. Another example is the disablement of
outputs during a routine test or temporary fault.
Coincidence
The consequence of a false alarm on some re alarm systems, particularly those connected to sprinkler or gas extinguishant
systems, can be onerous. To help reduce the risk of a false alarm, certain zones on the system can be coupled together so that
the alarm sounders and outputs only activate when there is a re condition on both zones. The only way to tell if and how this
feature has been utilised is to refer to the System Set-up Data Chart (page 13).

2/4/8 ZONE CONVENTIONAL FIRE ALARM CONTROL PANEL | 6
USER RESPONSIBILITIES
BS5839-1 is the British Standard code of practice for the design, installation, commissioning and maintenance of re detection
and re alarm systems for buildings. Section 7 of the standard (User
Responsibilities) states that a named responsible person should be appointed to supervise all matters pertaining to the re
alarm system {clause 47.2a}.
Highlighted below is a summary of the main functions of the responsible person is expected to carry out with regard to
BS5839-1 only. It does not highlight any other responsibilities that may be required of the user or responsible person that is
listed in documentation such as the Employers Guide to Fire Safety, the
Fire Precautions (Workplace) regulations and/or any other legislation relevant to the premises. If in doubt, the re authority
can advise on the re legislation that applies to any given building.
For countries outside the UK, dierent user responsibilities may apply.
BS5839-1 states the responsible person should:
(The bracketed numbers {xx} identify the BS5839-1 clauses to which the summary refers).
1 Ensure the re alarm panel is checked daily to conrm there are no faults on the system {47.2b}.
2 Ensure arrangements are in place for the test, maintenance and regular servicing of the system with regard to Section 6 of
the standard {47.2c}.
Important: Clause 44 of BS5839-1 recommends weekly and monthly tests that should be carried out by the user/responsible
person - please refer to the bottom of this section for further details.
3 Ensure the system log book is kept up to date by recording re signals, fault signals, work on the system, etc, and make sure
it is available for inspection at all times {47.2d/48}.
4 Ensure that all relevant occupants of the protected premises are instructed in the proper use of the system {47.2e}.
5 Take steps to limit the number of false alarms on the system {47f}.
6 Ensure the eectiveness of the system is not impaired by ensuring there is a space of at least 500mm in all directions around
and below every re detector and that all manual call points are unobstructed and easy to see {47g}.
7 Liaise with all relevant building engineers, decorators, etc., to ensure any changes to (or maintenance of), the building’s
fabric does not compromise the protection given by the re alarm system, create faults or false alarms {47h}.
8 Ensure that any structural or occupancy changes planned for the building are done so with due and early consideration
given to any changes that may be required to the re system {47h}.
9 Ensure that a selection of spare parts are held as appropriate within the premises {47j}.
Routine weekly and monthly testing to be undertaken by the user/responsible person:
To meet the requirements of Clause 44 of BS5839-1 we recommend the following tests are carried out at approximately the
same time each week, during normal working hours:
Note: It is essential any alarm receiving centre is contacted before and after these tests to avoid unwanted alarms and to con-
rm the re signal is correctly received.
• Carry out an indicator lamp test to check all Zone lights show and the beeper sounds.
• Operate a manual call point or smoke/heat detector to test the re alarm.
• Check that the alarm sounders operate.
• Reset the system by pressing the Silence/Resound Sounders button and Control Panel Reset button.
• Verify that no manual call points or smoke/heat detectors are obstructed in any way.
• Test a dierent zone each week using a dierent call point or detector so all are tested in rotation.
Monthly attention: Ensure authorised service personnel verify the system’s standby power supply (or supplies) are in good
working order.
Quarterly and periodic inspection, testing, servicing and maintenance
It is the user’s responsibility to ensure that an ongoing periodic plan is in place that meets Clause 45
(Inspection and Servicing) of BS5839-1. The work required to meet this Clause must be carried out by a competent person
with specialist knowledge of re detection and alarm systems.
The standard recognises this will normally be an outside specialist re alarm servicing organisation.
Please note: the above summaries do not replace Sections 6 and 7 of BS5839-1 but are intended to help the user gain a
greater understanding of his or her responsibilities. We strongly recommend the named responsible person familiarises them-
selves with the full and current standard.

2/4/8 ZONE CONVENTIONAL FIRE ALARM CONTROL PANEL | 7
PANEL LAYOUT/ACCESSING THE CONTROLS
The re alarm panel allows both keyswitch and keypad entry methods for entering access level two.
Note: Repeater Fault and Output Delays lights are not on the CFP Economy Panel.
Two levels of control are available to user(s) of this re alarm panel; General User and Authorised User.
1. General User Controls (access level one)
When the panel is in access level one, the indicator lights on the panel front give a comprehensive overview of the system’s
current status. Any re and fault conditions are clearly displayed, disablements highlighted and the status of all outputs re-
ported. For detailed descriptions of what each light means, see page 7.
The only functions that can be performed by the user when the panel is in access level one are:
• Muting the panel’s internal sounder by pressing the Silence Internal Sounder button;
• Overriding any delays (CFP model dependent - see page 3) which may have been programmed into the panel by pressing
the Silence/Resound Sounders button (only applicable when the panel
is in alarm); or
• Putting the panel into access level two (the Authorised User state) - see below.
2. Authorised User Controls (access level two)
To avoid unauthorised changes to critical parts of the re alarm system, controls such as silencing the sounders, resetting an
alarm condition and setting disablements are only accessible via a secure method
of entry which puts the panel into access level two.
To put the panel into access level two using keypad entry:
Enter the code 2 1 4 3 using the keypad buttons on the panel front. During the code entry sequence, the panel’s Accessed
light will pulse. If an incorrect sequence of numbers is entered after four button presses the Accessed light will stop pulsing
and you must enter the code again. When the correct code is entered, the Accessed light will be lit steady to indicate that the
controls are operative. To exit access level two, press the Exit Access Mode button.
To put the panel into access level two using the keyswitch:
Turn the key to the‘I’ position (Note: The key cannot be removed when in this position). When the key
is in the ‘I’position, the Accessed light will be lit steady to indicate that the controls are operative.
To exit access level two, turn the key back to the ‘O’position.
Details of how to use the Authorised User controls can be found on pages 8 to 11 of this user manual.

2/4/8 ZONE CONVENTIONAL FIRE ALARM CONTROL PANEL | 8
What the indicator lights mean
The table below summarises the various indicators available on the re alarm panel and what they mean in their various
states. The nal column highlights the pages(s) you should turn to for further information.
LIGHT STATUS OF LIGHT WHAT THIS MEANS FURTHER READING
(General Fire)
Flashing Red The panel has detected a fire alarm condition, or
the Silence/Resound Sounders button has been
pressed to evacuate the building
Page 8 (Fire Conditions)
Steady Red There is a silenced fire alarm condition on the
system
Fire Zones
1 to 8
Flashing Red A fire alarm condition has been detected on the
zones which are flashing
Steady Red There is a silenced fire alarm condition on the
zones which are lit steady
Zone Fault/Disable/Test
1 to 8
Flashing Yellow
(in sync. with the
General Fault light)
Faulty wiring has been detected on the zones
which are flashing
Page 9 (Fault Conditions)
Flashing Yellow
(in sync. with the
Test light)
The zones which are flashing are in test mode
Steady Yellow The zones which are lit steady have been disabled Page 10 (Disablements)
Supply Present Steady Green The panel is supplied with power Page 4 (Overview)
Remote Output Steady Red The remote output has been activated
Test Flashing Yellow The panel is in test mode
Accessed Flashing Yellow The access code is in the process of being entered Page 6 (Accessing the Controls)
Steady Yellow The panel is in access level two
General Disablement Flashing Yellow The panel is in the disablement selection state Page 10 (Disablements)
Steady Yellow Part of the system has been manually disabled
and/or one or more of the fire zones have a delay
applied to them (CFP model dependent - see page 3)
Page 10 (Disablements)
Page 12 (Notes on Delays)
Fault Output Status Steady Yellow The fault output has been disabled Page 10 (Disablements)
Remote Output Status Flashing Yellow A fault has been detected on the output’s auxiliary
24V supply
Page 9 (Fault Conditions)
Steady Yellow The remote output has been disabled Page 10 (Disablements)
General Fault Flashing Yellow A fault has been detected on the system Page 9 (Fault Conditions)
Power Supply Fault Flashing Yellow The panel has detected a fault with its power
supply, battery charger or back-up batteries
System Fault Flashing Yellow The panel has detected a microprocessor fault
Repeater Fault (model
dependent - see page 3)
Flashing Yellow The panel has detected a wiring/communication
fault on the repeater network
Sounder Status Flashing Yellow Faulty wiring has been detected on the panel’s
sounder circuits
Steady Yellow The alarm sounders have been disabled Page 10 (Disablements)
Auxiliary Output Status Steady Yellow The panel’s auxiliary output has been disabled Page 10 (Disablements)
Output Delays (CFP
model dependent - see
page 3)
Steady Yellow Delays have been programmed into the panel Page 12 (Notes on Delays)
Flashing Yellow A delay is running
FIR
E
Testing the indicator lights
To test the panel’s indicator lights are working correctly, press the Lamp Test button when the panel is in the accessed state.
The panel’s internal beeper also sounds when pressing this button to show it is working correctly.

2/4/8 ZONE CONVENTIONAL FIRE ALARM CONTROL PANEL | 9
FIRE CONDITIONS
When the re alarm panel receives an alarm trigger from a detector or manual call point located in a zone that is not already in
a re state, it will:
• Flash the general re and appropriate Fire Zone light(s) on the panel front.
• Activate its internal sounder.
• Start the alarm sounders and outputs including, if enabled, the remote and auxiliary outputs (provided there are no delays
applicable to the zone which is in alarm - model dependent, see page 3).
At this point the building’s re management plan should be executed!
Important Note: Zones which have been disabled cannot be triggered into an alarm condition (see page 10 for further infor-
mation on disablements).
Silencing the alarm sounders
• The alarm sounders may be silenced by putting the panel into access level two and pressing the
Silence/Resound Sounders button.
The alarm sounders and the panel’s internal sounder will stop sounding and the light(s) for the zone(s) in alarm and the Gen-
eral Fire light will be lit steady. The remote output will turn o, but the auxiliary output will stay on.
New zone in alarm
Should a new zone be triggered into alarm whilst the alarm sounders are silenced, the panel will:
• Automatically reactivate the alarm sounders (if programmed to do so).
• Flash the General Fire light and appropriate Fire Zone light(s) for any new zone(s) in alarm.
• Keep the light(s) for the previous zone(s) in re lit steady.
Manually activating the alarm sounders (i.e. to evacuate the building
• Momentarily pressing the Silence/Resound Sounders button when the panel is in access level two (see page 6) will cause the
alarm sounders to sound. Note: The panel’s remote and auxiliary re outputs will not be triggered when the building is manu-
ally evacuated in this way.
Pressing the Silence/Resound Sounders button again will silence the alarm sounders.
Note: If the sounders have been disabled, pressing the Silence/Resound Sounders button will have no eect.
Resetting the panel
• After the cause of the alarm has been investigated and cleared and the alarm sounders have been silenced, the panel can be
reset by pressing the Control Panel Reset button.
The panel will give a double beep to indicate the reset process has started and, after a few seconds, the
Fire Zone and General Fire lights will go out to indicate the process is complete. If there are still alarm triggers on any zone the
panel will go back into alarm as before.
Fire Zone Lights
General Fire Light
27 35 4618
Fire Zones
Fire

2/4/8 ZONE CONVENTIONAL FIRE ALARM CONTROL PANEL | 10
FAULT CONDITIONS
When a fault occurs on a critical part of the re alarm system, the panel responds by activating its internal sounder and il-
luminating the General Fault light and any other Fault light(s) relating to the fault. The panel’s fault output will also activate
(provided it hasn’t been disabled). The type of faults typically indicated at the re alarm panel are described below:
In the event of a fault condition:
• Mute the panel’s internal sounder by pressing the Silence Internal Sounder button (the panel does not have to be in access
level two to do this).
• Record the fault(s) in the Fire Alarm Log Book (page 14) and take appropriate action to correct it/them.
See User Responsibilities (page 5).
When a fault has been rectied the indicator light for that fault is automatically turned o. If all faults are cleared, the General
Fault light will go out, and the panel’s internal sounder will be silent (if not already muted). If the re alarm panel is reset any
existing fault(s) will reappear as before and the silencing process will have to be repeated.

2/4/8 ZONE CONVENTIONAL FIRE ALARM CONTROL PANEL | 11
DISABLEMENTS
Certain re alarm panel functions can be temporarily disabled (i.e. switched o) to suit certain conditions. For example, if
there is a risk of a false alarm in a zone, e.g. from vehicle exhaust smoke in a loading bay, it is possible for the user to disable
that zone during the risk period and enable it again afterwards. Another example is the disablement of outputs during a rou-
tine test or temporary fault.
The following is a list of options that may be disabled by a level two user at the re alarm panel and the eect their disable-
ment will have on how the system works:
To disable or enable any of the above options:
1. Put the re alarm panel into access level two (see Authorised User Controls - page 6).
2. Start the selection process by pressing and holding the Next Option button for 3 seconds.
The General Disablement light will ash and the Fault light relating to the rst option in the above table will ash to show it is
selected.
If the light ashes at a slower rate than the General Disablement light, the option is enabled.
If the light ashes at the same rate as the General Disablement light, the option is disabled.
3. If necessary, press the Enable/Disable button to toggle the selected option between disabled and enabled.
4. To conrm your choice, press the Next Option button.
This will move the selection process on to the next available option in the above table and the Fault light relating to this
new option will ash to show it is selected. The previous option’s Fault light will now be lit steady to conrm it is disabled, or
switched o to conrm it is enabled.
5. Repeat steps 3 & 4 for every available option until the selection process is complete.
The disablement/enablement process is complete when all available options have been selected in turn and the
Next Option button is pressed for the last time. At this point all disabled options will be lit steady and all enabled options will
have their lights switched o.
Note: The selection process can be exited at any time by pressing the Exit Access Mode button, or by turning the keyswitch to
‘O’position. The only changes that will be saved will be those made prior to the last press of the Next Option button.

2/4/8 ZONE CONVENTIONAL FIRE ALARM CONTROL PANEL | 12
Notes about disablements
(a) The option of disabling or enabling zones 3 & 4 and zones 5, 6, 7 & 8 is only available if these zones are tted. If they are not
tted, the selection process will skip to the next available option.
(b) The option of disabling or enabling output delays is only available if delays have been programmed into the re alarm
panel by the installation engineer. If a delay has been programmed into the panel the Output Delays light will be lit when the
panel is in the normal (i.e. non-accessed) state.
Important: Please refer to the ‘Notes on Delays’(page 12) before proceeding to make any changes to the way the delays func-
tion operates.
Diagram to show the disablement/enablement selection sequence

2/4/8 ZONE CONVENTIONAL FIRE ALARM CONTROL PANEL | 13
NOTES ON DELAYS
What is a delay?
A delay can be programmed into the re alarm panel to postpone the activation of the alarm sounders and other outputs for
a predetermined length of time. The delay period gives a responsible person time to investigate the cause of an alarm, usually
in areas which are prone to false alarm (such as vehicle exhaust smoke in a loading bay) before the building is evacuated. If
the cause of the alarm is found to be a true re hazard, the delay can be overridden and the alarm sounders activated immedi-
ately.
Alternatively, in the case of a false alarm, the panel can be reset.
Delay options
One, some or all of the zones on the re alarm panel can have a delay applied to them to suit the requirements of the site. The
same delay period applies to all delayed zones and is adjustable to a maximum of 10 minutes. The programming of delays
must only be carried out by competent service personnel who are advised to record all relevant delay data on the System Set-
Up Data Chart (page 13) of this user manual. Delays should only be used with the prior knowledge and consent of all relevant
authorities, i.e. re ocer, building control, etc.
Delay indication
If delays have been programmed into the panel the Output Delays light and the General Disablement light will be lit steady.
This means the immediate turning on of the alarm sounders and other outputs on one or more zones has been disabled. The
only way to ascertain which zones have been programmed with a delay is to refer to the System Set-Up Data Chart (page 13)
What happens when there is a re alarm condition on a delayed zone?
Should an alarm occur on a delayed zone, the panel will:
• Flash its General Fire and appropriate Fire Zone light(s)
• Sound its internal sounder
• Start the delay countdown sequence
• Indicate a delay is running by ashing its Output Delays light
How to override a delay in the event of a true re alarm condition
• If, on investigation, the cause of the alarm on the delayed zone is found to be a true re hazard, pressing the Silence/Resound
Sounders button at any time will override the delay and activate the alarm sounders and outputs with immediate eect.
How to reset the system in the event of a false alarm
• If, on investigation, the cause of the alarm is found to be false, put the panel into access level two (see Authorised User Con-
trols - page 6) and press the Control Panel Reset button.
How to turn the delays function on or o
Any delays that have been programmed into the panel can be turned on or o by putting the panel into access level two and
following the disablement/enablement selection process as described on pages 10 and 11.
Selecting the Output Delays option and then pressing the Enable/Disable button so that the Output
Delays light ashes in synchronisation with the General Disablement light shows that the delays are on.
Pressing the Enable/Disable button again will make the Output Delays light ash slower than the General
Disablement light, showing that the delays are o.
Having chosen the desired setting, pressing the Next Option button will exit the disablement/enablement selection process.
The Output Delays light will now be lit steady with the
General Disablement light, showing that delays are on, or the Output Delays light will be o, showing that delays are o.

2/4/8 ZONE CONVENTIONAL FIRE ALARM CONTROL PANEL | 14
SYSTEM SET-UP DATA CHART
Important: This page should be carefully completed by an authorised engineer prior to system hand-over.
THE INFORMATION ABOVE WAS COMPLETED BY (name) _______________________________
OF (company) _________________________________________ ON (date) __________________
(*) NOTES ON COINCIDENCE: The following applies to all pairs of zones which are set up for coincidence.
There must be alarms on both zones (i.e. zone 1 and zone 2) before the alarm sounders and outputs turn
on. If only one of the zones (i.e. zone 1) goes into alarm, the panel indicates the alarm by illuminating the
relevant light on the panel front and sounding its internal sounder, thus prompting the user to investi-
gate. If found to be false, the alarm can be reset or, if found to be a true re condition, the sounders can be
manually activated by pressing the
Silence/Resound Sounders button - as detailed on page 8.

2/4/8 ZONE CONVENTIONAL FIRE ALARM CONTROL PANEL | 15
FIRE ALARM LOG BOOK
It is recommended that this log book be maintained by a responsible person, who should ensure that every entry is properly
recorded. In the UK, this is necessary to satisfy the recommendations of BS5839-1, compliance with which may be a require-
ment of legislation. If your premises are certicated under the Fire Precautions Act 1971, failure to keep a suitable log book
may be a breach of the requirements of the certicate, which is a criminal oence. In order to satisfy the requirements of
BS5839-1 the following must be recorded:
• The name of the responsible person;
• Brief details of the maintenance arrangements;
• Dates and times of all tests, including re drills;
• Dates and times of all res to which the system responds;
• Dates and times of all false alarms;
• Causes, circumstances surrounding, and category of false alarms (if known);
• The identity of any manual call point or re detector that triggers any of the above re alarm signals (if known);
• Dates, times and type of all faults and defects.
• Dates and times of all maintenance (e.g service visit or non-routine attention).

2/4/8 ZONE CONVENTIONAL FIRE ALARM CONTROL PANEL | 16
Details of tests (including fire drills), actual fire alarms, disablements or enablements and faults should be recorded here.
False alarms and maintenance work should also be recorded on page 18

2/4/8 ZONE CONVENTIONAL FIRE ALARM CONTROL PANEL | 17

2/4/8 ZONE CONVENTIONAL FIRE ALARM CONTROL PANEL | 18

2/4/8 ZONE CONVENTIONAL FIRE ALARM CONTROL PANEL | 19
False alarms
Maintenance work

2/4/8 ZONE CONVENTIONAL FIRE ALARM CONTROL PANEL | 20
BS5839-1 recommends that certicates be issued for all aspects of the re alarm system including design, installation,
commissioning, acceptance, verication (optional) and maintenance. Therefore, before this user manual is handed over, the
following installation certicate and commissioning certicate (overleaf) should be completed as appropriate by the relevant
installation/commissioning engineer(s). Please ensure that the System Set-Up Data Chart (page 13) and the relevant parts
of the Fire Alarm Log Book (page 14) are also completed as appropriate. For countries outside the UK, dierent certication
requirements may apply.
This manual suits for next models
2
Table of contents
Other Channel Safety Systems Control Panel manuals
Popular Control Panel manuals by other brands

Deckma Hamburg
Deckma Hamburg NLS 3000 Technical documentation

Extron electronics
Extron electronics Decorator-Style Series Setup guide

Notifier
Notifier AFC-600 installation manual

Mircom
Mircom FA-300 Series Installation and operation manual

Mitsubishi
Mitsubishi FX-20P-E Operation manual

D+H
D+H RZN 43-E Series Instructions for use