14 Building Management System
Sistema di rivelazione incendio ed estinzione
3.1.2 COIL Mapping
The “SET COIL” allows you to carry out operations on the addressed control panel. To activate a COIL command relative
to the implementation of an operation it is necessary to set it to “ON”.
Following is the map of COIL registers:
3.2 BACnet
BACnet is a building-automation-network communication protocol developed by ASHRAE (American Society of Heating,
Refrigeration and Air-Conditioning Engineers). BACnet, as a result of its versatility and flexibility, is now extensively used as
a standard communication protocol between devices and building-automation systems made by various manufacturers.
The BACnet protocol used for IFMLAN is subject to licencing regulations.
3.2.1 BACnet licence
The licences for use of the BACnet protocol on Previdia control
panels must be purchased from Inim Electronics.
The order codes are as follows:
•INFLINI0PRALICBAC500, BACnet protocol licence Previdia 500
points, Italian
•INFLINE0PRALICBAC500, BACnet protocol licence Previdia 500
points, English
Each licence allows the management of 500 points. For the
management of a greater number of points it is necessary to
purchase more than one licence. Inim Electronics supplies a single
licence containing the sum of the licences purchased as per the
format indicated here.
3.2.2 Licence activation procedure
1. In order to activate the licence you must communicate the
following data to Inim:
• the licence number shown in the letter [A]
COIL (use the Modbus 0x05 command)
Address Name Address Name
0Activate “Action 1” 1400 Activate/Deactivate loop1 address 1 device's output
... ... ... ...
99 Activate “Action 100” 5239 Activate/Deactivate loop16 address 240 device's output
100 Enable/Disable Zone 1 5400 Enable/Disable I/O 1 of IFM4IIO 1 module
... ... ... ...
1099 Enable/Disable Zone 1000 5463 Enable/Disable I/O 4 of IFM4IO 16 module
1100 Activate/Deactivate I/O 1 of IFM4IO 1 module 5500 Enable/Disable relay 1 of the IFM4R 1 module
... ... ... ...
1163 Activate/Deactivate I/O 4 of IFM4IO 16 module 5563 Enable/Disable relay 4 of the IFM4R 16 module
1200 Activate/Deactivate relay 1 of the IFM4R 1 module 5600 Enable/Disable output 1 of the IFM24160 1 module
... ... ... ...
1263 Activate/Deactivate relay 4 of the IFM4R 16 module 5611 Enable/Disable output 3 of the IFM24160 4 module
1300 Activate/Deactivate output 1 of the IFM24160 1 module 5700 Enable/Disable address 1 of loop 1
... ... ... ...
1311 Activate/Deactivate output 3 of the IFM24160 4 module 9540 Enable/Disable address 240 of loop 16
INIM ELECTRONICS S.r.l.
Legal and operating headquarters: Via Dei Lavoratori 10, Frazione Centobuchi, 63076, Monteprandone (AP), Italy
PIVA & C.F. 01855460448
BAC1234567
1000
BACNET Licence
for the managing of points in Ethernet network.
For the licence activation, send an e-mail to the address
service-previdia@inim.biz
reporting the number indicated here above and
the serial number ofthe module IFMLAN,shown on the side of the module.
A