LD1 Actuator open or opening
LD2 Actuator closed or closing
LD3 Weather sensor active
LD4 Fault on actuator line
LD5 Fault on call point line
LD6 Fault on smoke sensor line
LD7 Fault on BUS
2x12v 7Ah Batteries
First and intermediate
smoke detector(s)
Last or only smoke
detector (t 10k end of
line resistor)
Single external call point
(ensure J1 is tted)
First and
intermediate
actuator joint box
Last or only actuator
joint box (t 27k end
of line resistor)
230v Feed from a
5A supply
Typical connections for a stand-alone system with built-in
call point and 1 external call point
Jumper settings for actuator
line monitoring and end of
line as shown
DIP Switch settings
(arrows show the
direction the switch is
set = ON)
TAKE CARE TO OBSERVE CABLE CONNECTIONS IN EXTERNAL
BREAK GLASS UNIT.
6 IN BREAK GLASS CONNECTS TO 15 IN PANEL
7 IN BREAK GLASS CONNECTS TO 14 IN PANEL
*
*
Alternative
connections for
Hochiki SLV-E3(HFP)
head and
YBN-R/6SK(WHT)
diode base
If a link to a fire alarm system is required
Link a normally open contact to terminal 16 & 17