Chigo CST-300P12 User manual

CHIGO CAC-FAN COIL Contents
Part 1 Introduction .................................................................................................................... 1
Part 2 Nomenclature ................................................................................................................. 1
Part 3 Product Schedule............................................................................................................ 2
Part 4 External Appearance....................................................................................................... 3
Part 5 Features............................................................................................................................ 3
Part 6 Specifications .................................................................................................................. 4
Part 7 Dimension........................................................................................................................ 6
Part 8 Wiring Diagram................................................................................................................ 7
Part 9 Installation ...................................................................................................................... 8

CHIGO CAC-FAN COIL
1
1. Introduction
Fan coil unit is a kind of compound device which assemble fan and surface-type coil heating-exchanger
together. Fan coil with fresh air supply system is a main type of center air-conditioner system, so it is an
important component of AC devices. Fan coil has horizontal type, vertical type, etc. A cooling (heating)
supply system usually consists of fan coil terminals and chilled water system (heated water system).
CHIGO commercial AC fan coil is designed and manufactured on the base of advanced technology, and
utilize qualified galvanized iron as material. Due to its supper-thin design, it has such advantages: beautiful
outlook, space saving, easy installation, etc. And the most obvious advantage is that it can decrease the
outlet air Temp-difference as low as possible to make room more comfortable, as well as don’t decrease
cooling capacity output. For the large air flow volume design, it can increase room ventilation frequency,
supply more flesh air, and balance room temperature distribution. Benefiting from adoption of advanced
material and technology, it can effectively decrease the running noise and keep running smoothly. With the
advantages above, it can be widely applied in market, hospital, office building, hotel airport, etc..
Part 2 Nomenclature

CHIGO CAC-FAN COIL
Part 3 Product Schedule
NO
Model
Type
Power source
1
CST-200P12
3-Row Duct Type
220-240V~,1Ph, 50Hz
2
CST-300P12
3
CST-400P12
4
CST-500P12
5
CST-600P30
6
CST-800P30
7
CST-1000P30
8
CST-1200P30
9
CST-1400P30

CHIGO CAC-FAN COIL
4. External Appearance
5. Features
●Nested in the ceiling, space-saving and noble.
●High capacity of cooling / heating performance, high efficiency and energy-saving.
●Adjust the indoor temperature rapidly and averagely.
●Low noise fan direct driven by single phase, 3 speed permanent split capacitor motor.
●The air outlet is laid out in the way you desire.
●Unit constructed by electrostatic galvanized sheet, providing maximum protection against corrosion
●Heavy gauge zinc coated steel drainage pan with good insulation processing, avoiding sweating and
corrosion
●Unit tested performance comply with GB4706.32-2004、JB9063-1999 and JB/T4283-1991.

CHIGO CAC-FAN COIL
6. Specifications Chilled Water Fan Coil Units
Model
CST-200P12
CST-300P12
CST-400P12
CST-500P12
CST-600P30
Air-flow
volume(m3/h)
High-speed
340
510
680
850
1020
Middle-speed
285
420
580
700
840
Low-speed
210
320
420
520
620
Cooling
capacity (W)
High-speed
2200
3260
4170
4600
5810
Heating
capacity (W)
High-speed
3480
5320
6810
7910
9980
Fan
Type
Front-wing double-inlet centrifugal type fan
Number
1
2
2
2
2
Nosie
leveldB (A)
Standard
36
37
40
43
47
Motor
Type
3 level speed, low noise, capacitance motor
Number
1
Power supply
220V~240V,1Φ,50Hz
Power
input (W)
Standard
30
39
60
76
106
Coil
Type
copper tube, grilled aluminum fin
Rows
3
Working pressure
1.1MPa
Connection
pipe
Water inlet
RC3/4” internal thread
Water outlet
RC3/4” internal thread
Drainage
ZG3/4” external thread
Water-flow Volume(m3/h)
0.37
0.56
0.72
0.83
1.00
Hydraulic
resistance
(kPa)
Standard
14
20
22
24
34
High Static
Pressure
14
20
22
24
34
Dimension
Width
mm
770
825
927
927
1140
Height
mm
240
240
240
240
240
Depth
mm
472
472
472
490
472
Net weight (kg)
No air-return box
13
15
17
17
20
Remark: 1.All performance data above is based upon 0Pa ambient static pressure.
2. Cooling capacity test condition: air inlet Temp. : 27DB℃/19.5WB℃, water inlet Temp. 7℃, water Temp. difference 5℃.
3. Heating capacity test condition: air inlet Temp. : 21DB℃, water inlet Temp. 60℃, the volume of air and water is same as
cooling.

CHIGO CAC-FAN COIL
Model
CST-800P30
CST-1000P30
CST-1200P30
CST-1400P30
Air-flow
volume(m3/h)
High-speed
1360
1700
2040
2380
Middle-speed
1150
1400
1650
2000
Low-speed
840
1000
1250
1480
Cooling
capacity (W)
High-speed
7920
9070
10800
12600
Heating
capacity (W)
High-speed
13590
16020
16200
18900
Fan
Type
Front-wing double-inlet centrifugal type fan
Number
4
4
4
4
Nosie leveldB (A)
Standard
46
48
51
52
Motor
Type
3 level speed, low noise, capacitance motor
Number
2
Power supply
220V~240V,1Φ,50Hz
Power input (W)
Standard
150
172
210
250
Coil
Type
copper tube, grilled aluminum fin
Rows
3
Working pressure
1.1MPa
Connection
pipe
Water inlet
RC3/4” internal thread
Water outlet
RC3/4” internal thread
Drainage
ZG3/4” external thread
Water-flow Volume(m3/h)
1.36
1.56
1.98
2.24
Hydraulic
resistance
(kPa)
Standard
34
40
42
42
High Static
Pressure
34
40
42
42
Dimension
Width
mm
1440
1546
1835
1835
Height
mm
240
240
240
240
Depth
mm
472
472
472
472
Net weight (kg)
No air-return box
27
32
36
36
Remark: 1.All performance data above is based upon 0Pa ambient static pressure.
2. Cooling capacity test condition: air inlet Temp. : 27DB℃/19.5WB℃, water inlet Temp. 7℃, water Temp. difference 5℃.
3. Heating capacity test condition: air inlet Temp. : 21DB℃, water inlet Temp. 60℃, the volume of air and water is same as
cooling.


CHIGO CAC-FAN COIL
Part 7 Dimension
Duct-type fan coil
mm
model
dimension
CST-200P12
CST-300P12
CST-400P12
CST-500P12
CST-600P30
CST-800P30
CST-1000P30
CST-1200P30
CST-1400P30
A
547
647
747
967
1267
1372
1662
B
517
617
717
937
1237
1342
1632
C
513
613
713
933
1233
1338
1628
D
485
585
685
905
1205
1310
1600
E
770
825
927
1140
1440
1546
1835
Notice:
1. Example above is based on double scroll cases type, it may be different from the one you choose
2. Double-dash line in drawing is the dimension of air-return box (down air-return type and rear air-return
type)
3. If customer need air-return box, please declare when booking, furthermore, please explain whether it is
down air-return type or rear air-return type.

CHIGO CAC-FAN COIL
Part 8 Wiring Diagram
CST-200P12
CST-300P12
CST-400P12
CST-500P12
CST-600P30
CST-800P30 CST-1000P30 CST-1200P30 CST-1400P30

CHIGO CAC-FAN COIL
Part 9 Unit installation
9.1 Installation place
There is enough room for installation and maintenance.
The ceiling is horizontal, and its structure can endure the weight of the indoor unit.
The air outlet and the air inlet are not impeded, and the influence of external air is the least.
The air flow can reach throughout the room.
The connecting pipe and drainpipe could be extracted out easily.
There is no direct radiation from heaters
Caution
Location in the following places may cause malfunction of the machine. (If unavoidable, please consult
your local dealer.)
1. There exists petrolatum.
2. There is salty air surrounding (near the coast).
3. There is caustic gas (the sulfide, for example) existing in the air (near a hot spring).
4. The Volt vibrates violently (in the factories).
9.2 Install the Main Body
Please refer to the following figure for the hanging screw bolts.
Please install with Ø10 hanging screw bolts.
The handling to the ceiling varies from the constructions,
Consult the construction person for the specific condition.
1. The size of the ceiling to be handled------ Do keep the ceiling flat. Consolidate the roof beam for possible
vibration.
2. Cut off the roof beam.
3. Strengthen the place that has been cut off, and consolidate the roof beam.
Carry out the pipe and line operation in the ceiling after finishing the installation of the main body. While
choosing where to start the operation, determine the direction of the pipes to be drawn out. Especially in
case there is a ceiling, position the water refrigerant pipes, drain pipes, indoor lines to the connection
places before hanging up the machine.
The installation of hanging screw bolts.

CHIGO CAC-FAN COIL
Suspending the indoor unit
1.Use tools such as pulleys to hoist the indoor unit to the pendant bolt.
2.Use tools such as gradient to settle the indoor unit horizontally. Lack of horizontality may cause water
leak.
Pipe Connecting
1.The water vent is with the air outlet valve; the other side is air inlet.
2.When connecting the water collecting box, the torque is 6180~7540N.cm (630~770kgf.cm).
3.Put the connecting tubing at the proper position, wrench the nuts with hands, then fasten it with a wrench.
(Refer to Figure 6)
Figure 6
9.3 Connect the Drainage Pipe
1. Install indoor unit drain pipe
The outlet has PTI screw bread, please use sealing materials and pipe sheath (fitting) when connecting
PVC pipes.
CAUTIONS:
The drain pipe of indoor unit must be heat insulated, or it will condense dew, as well as the connections of
the indoor unit.

CHIGO CAC-FAN COIL
Hard PVC binder must be used for pipe connection, and make sure there is no leakage. With the
connection part to the indoor unit, please be noted not to impose pressure on the side of indoor unit pipes.
When the declivity of the drain pipe downwards is over 1/100, there should not be any winding.
The total length of the drain pipe when pulled out traverse shall not exceed 20m, when the pipe is over long,
a prop stand must be installed to prevent winding.
Refer to the figures on the right for the installation of the pipes.
2. Drainage test
Check whether the drainpipe is unhindered
New built house should have this test done before paving the ceiling.
9.4 Wiring Installation
The connecting diagram refers to the wiring diagrams.
This manual suits for next models