Circutor CirCAMP-4DP User manual

INSTRUCTION MANUAL
(M097B01-03-16A)
Multifunction multimeter
CirCAMP-4DP
CirCAMP-2IP

2
CirCAMP-4DP, CirCAMP-2IP
Instruction Manual

SAFETY PRECAUTIONS
DISCLAIMER
CIRCUTOR, SA reserves the right to make modi cations to the device or the unit speci ca-
tions set out in this instruction manual without prior notice.
CIRCUTOR, SA on its web site, supplies its customers with the latest versions of the device
speci cations and the most updated manuals.
www.circutor.com
DANGER
Warns of a risk, which could result in personal injury or material damage.
ATTENTION
Indicates that special attention should be paid to a speci c point.
Follow the warnings described in this manual with the symbols shown below.
If you must handle the unit for its installation, start-up or maintenance, the following
should be taken into consideration:
Incorrect handling or installation of the unit may result in injury to personnel as well as damage
to the unit. In particular, handling with voltages applied may result in electric shock, which may
cause death or serious injury to personnel. Defective installation or maintenance may also
lead to the risk of re.
Read the manual carefully prior to connecting the unit. Follow all installation and maintenance
instructions throughout the unit’s working life. Pay special attention to the installation stan-
dards of the National Electrical Code.
Refer to the instruction manual before using the unit
In this manual, if the instructions marked with this symbol are not respected or carried out correctly, it can
result in injury or damage to the unit and /or installations.
CIRCUTOR, SA reserves the right to modify features or the product manual without prior noti cation.
3
Instruction Manual
CirCAMP-4DP, CirCAMP-2IP

CONTENTS
SAFETY PRECAUTIONS ���������������������������������������������������������������������������������������������������������������������������������������3
DISCLAIMER ����������������������������������������������������������������������������������������������������������������������������������������������������������3
CONTENTS�������������������������������������������������������������������������������������������������������������������������������������������������������������4
REVISION LOG�������������������������������������������������������������������������������������������������������������������������������������������������������6
1�- VERIFICATION UPON RECEPTION����������������������������������������������������������������������������������������������������������������� 7
2�- PRODUCT DESCRIPTION��������������������������������������������������������������������������������������������������������������������������������7
3�- DEVICE INSTALLATION �����������������������������������������������������������������������������������������������������������������������������������9
3�1�- PRELIMINARY RECOMMENDATIONS ����������������������������������������������������������������������������������������������������9
3�2�- INSTALLATION ���������������������������������������������������������������������������������������������������������������������������������������10
3�3�- DEVICE TERMINALS������������������������������������������������������������������������������������������������������������������������������10
3�3�1�- CirCAMP-4DP MODEL �����������������������������������������������������������������������������������������������������������������10
3�3�2�- CirCAMP-2IP MODEL ������������������������������������������������������������������������������������������������������������������� 11
3�4�- CONNECTION DIAGRAM�����������������������������������������������������������������������������������������������������������������������12
3�4�1�- CirCAMP-4DP MODEL ������������������������������������������������������������������������������������������������������������������12
3�4�2�- CirCAMP-2IP MODEL�������������������������������������������������������������������������������������������������������������������� 13
3�5�- CONNECTIONS����������������������������������������������������������������������������������������������������������������������������������������14
4�- OPERATION ���������������������������������������������������������������������������������������������������������������������������������������������������15
4�1�- KEY FUNCTIONS ������������������������������������������������������������������������������������������������������������������������������������� 15
4�2�- DISPLAY ���������������������������������������������������������������������������������������������������������������������������������������������������15
4�3�- LED INDICATORS������������������������������������������������������������������������������������������������������������������������������������16
4�3�1�- CirCAMP-4DP MODEL ������������������������������������������������������������������������������������������������������������������16
4�3�2�- CirCAMP-2IP MODEL�������������������������������������������������������������������������������������������������������������������� 17
4�4�- IMPULSE INPUTS ������������������������������������������������������������������������������������������������������������������������������������18
4�5�- RELAY OUTPUTS ������������������������������������������������������������������������������������������������������������������������������������19
4�6�- CIRCUIT BREAKER���������������������������������������������������������������������������������������������������������������������������������19
4�6�1�- CirCAMP-4DP MODEL ������������������������������������������������������������������������������������������������������������������� 19
4�6�2�- CirCAMP-2IP MODEL ���������������������������������������������������������������������������������������������������������������������20
4�7�- REAL TIME CLOCK ���������������������������������������������������������������������������������������������������������������������������������21
5�- DISPLAY IMPROVEMENTS ���������������������������������������������������������������������������������������������������������������������������22
5�1�- DISPLAY IN STANDBY MODE����������������������������������������������������������������������������������������������������������������22
5�1�1�- CirCAMP-4DP MODEL ������������������������������������������������������������������������������������������������������������������23
5�1�2�- CirCAMP-2IP MODEL�������������������������������������������������������������������������������������������������������������������� 24
5�2�- DISPLAY IN READING MODE ����������������������������������������������������������������������������������������������������������������� 25
5�2�1�- CirCAMP-4DP MODEL ������������������������������������������������������������������������������������������������������������������� 25
5�2�2�- CirCAMP-2IP MODEL ���������������������������������������������������������������������������������������������������������������������27
6�- CONFIGURATION ������������������������������������������������������������������������������������������������������������������������������������������29
7�- COMMUNICATIONS���������������������������������������������������������������������������������������������������������������������������������������29
7�1�- OPTICAL COMMUNICATIONS PORT ����������������������������������������������������������������������������������������������������� 29
7�2�- PLC COMMUNICATIONS�������������������������������������������������������������������������������������������������������������������������29
7�3�- RS-485 COMMUNICATIONS (according to version)����������������������������������������������������������������������������� 30
7�3�1� CONNECTIONS�������������������������������������������������������������������������������������������������������������������������������30
7�4�- DLMS PROTOCOL�����������������������������������������������������������������������������������������������������������������������������������31
7�4�1�- ABSTRACT OBJECTS: SAP ASSIGNMENT, LN ASSOCIATIONS, COSEM ������������������������������� 31
7�4�2�- IDENTIFICATION NUMBERS ��������������������������������������������������������������������������������������������������������� 35
7�4�3�- CLOCK �������������������������������������������������������������������������������������������������������������������������������������������� 36
7�4�4�- ERRORS������������������������������������������������������������������������������������������������������������������������������������������37
7�4�5�- EVENTS�������������������������������������������������������������������������������������������������������������������������������������������37
7�4�6�- CONTROLLING THE CIRCUIT BREAKER ������������������������������������������������������������������������������������ 45
7�4�7�- FIRMWARE UPDATE ���������������������������������������������������������������������������������������������������������������������� 46
7�4�8�- METERING POINT ID ���������������������������������������������������������������������������������������������������������������������47
7�4�9�- FIRMWARE VERSION �������������������������������������������������������������������������������������������������������������������� 47
7�4�10�- OPTICAL PORT CONFIGURATION ���������������������������������������������������������������������������������������������47
7�4�11�- RS-485 PORT CONFIGURATION ������������������������������������������������������������������������������������������������� 48
7�4�12�- TIMEOUT���������������������������������������������������������������������������������������������������������������������������������������48
7�4�13�- RESETTING THE DEVICE������������������������������������������������������������������������������������������������������������49
7�4�14�- ACTIVE ENERGY��������������������������������������������������������������������������������������������������������������������������49
7�4�15�- IMPULSE INPUTS ������������������������������������������������������������������������������������������������������������������������50
7�4�16�- INSTANTANEOUS VALUES ��������������������������������������������������������������������������������������������������������50
7�4�17�- TRANSFORMER RATIO ���������������������������������������������������������������������������������������������������������������54
4
CirCAMP-4DP, CirCAMP-2IP
Instruction Manual

7�4�18�- OBJECTS RELATED TO PRE-PAYMENT������������������������������������������������������������������������������������ 55
7�4�19�- LOAD PROFILES��������������������������������������������������������������������������������������������������������������������������61
8�- TECHNICAL FEATURES ��������������������������������������������������������������������������������������������������������������������������������63
9�- MAINTENANCE AND TECHNICAL SERVICE������������������������������������������������������������������������������������������������ 67
10�- GUARANTEE�������������������������������������������������������������������������������������������������������������������������������������������������67
11�- CE CERTIFICATE ������������������������������������������������������������������������������������������������������������������������������������������68
5
Instruction Manual
CirCAMP-4DP, CirCAMP-2IP

REVISION LOG
Table 1: Revision log�
Date Revision Description
07/16 M097B01-03-15A Initial Version
02/17 M097B01-03-16A
Changes in the following sections:
2. - 3.3.2. - 3.4.2. - 3.5. - 4. - 4.3.2. - 4.4. - 4.3.2. - 4.4.-
4.5. - 4.6.2. - 5.1.2. - 5.2.2. - 7.4.2. - 7.4.5.6. - 7.4.14. -
7.4.15. - 7.4.16. - 7.4.17. - 7.4.18.1. - 7.4.19. - 8
Note: The images of the devices are for illustrative purposes only and may differ from the orig-
inal device.
6
CirCAMP-4DP, CirCAMP-2IP
Instruction Manual

1�- VERIFICATION UPON RECEPTION
Check the following points when you receive the device:
a) The device meets the specications described in your order.
b) The device has not suffered any damage during transport.
c) Perform an external visual inspection of the device prior to switching it on.
d) Check that it has been delivered with the following:
- An installation guide.
If any problem is noticed upon reception, immediately contact the transport
company and/or CIRCUTOR's after-sales service.
2�- PRODUCT DESCRIPTION
CirCAMP-xxP units are a range of multichannel compact energy meters, with additional inputs
for metering the impulses of other devices, such as water and gas meters.
The system consists of two models:
El CirCAMP-4DP is a static energy meter that can manage 4 single-phase measurements
independently, all sharing the same neutral terminal.
El CirCAMP-2IP is a static energy meter that can manage 2 three-phase measurements,
indirectly /5A and independently in current, all sharing the same voltage.
Active energy is measured in compliance with Class B, according to European Directive
22/2004 EC.
The device features:
- 2 keys that allow you to browse the different screens and program the device.
- Indicator LEDs: 13 CirCAMP-4DP model y 7 CirCAMP-2IP model.
- Verication LEDs: 4 CirCAMP-4DP model y 2 CirCAMP-2IP model.
- LCD display, displays all parameters,
- 2 connection seals,
- 2 terminal covers, to cover the measuring terminals of the device and the xing screws.
7
Instruction Manual
CirCAMP-4DP, CirCAMP-2IP

- Communications via an optical port.
- RS-485 communications (according to version).
- PLC OFDM communications.
The CirCAMP-xxP is offered in different versions, Table 2 shows all of the possible options of
the device.
Table 2: CirCAMP-xxP options�
Options CirCAMP-4DP Code
Connection mode 4 single-phase measurements with shared neutral 1
Accuracy Class B active / Does not measure reactive energy 10
Measurement voltage 230 V E
Current measurement system Transformer D
Current measurement 5(32) A 7
Frequency
50 Hz A
60 Hz B
Automatic (50/60Hz) C
Communications PLC OFDM / RS-485 8
PLC OFDM B
Expansion 4 potential free outputs / 4 inputs 3
Model Pre-payment P
Number of quadrants Storage in both directions 2
Additional features With circuit breaker on the phase lines 2
Options CirCAMP-2IP Code
Connection mode 2 three-phase measurements with common volt-
ages 6
Accuracy Class B active / Does not measure reactive energy 10
Measurement voltage
3 x 127/220 V N
3 x 230/400 V Q
3 x 127/220 V ... 3 x 230/400 V U
Current measurement system Transformer T
Current measurement 5(10) A 8
Frequency
50 Hz A
60 Hz B
Automatic (50/60Hz) C
Communications PLC OFDM / RS-485 8
PLC OFDM B
Expansion 4 potential free outputs / 4 inputs 3
Model Pre-payment P
Number of quadrants Storage in both directions 2
Additional features No additional features 0
8
CirCAMP-4DP, CirCAMP-2IP
Instruction Manual

3�- DEVICE INSTALLATION
3.1.- PRELIMINARY RECOMMENDATIONS
In order to use the device safely, it is critical that individuals who handle it follow
the safety measures set out in the standards of the country where it is being used,
use the personal protective equipment necessary, and pay attention to the vari-
ous warnings indicated in this instruction manual.
The CirCAMP-xxP device must be installed by authorised and qualied staff.
The power supply plug must be disconnected and measuring systems switched off before
handling, altering the connections or replacing the device. It is dangerous to handle the device
while it is powered.
Also, it is critical to keep the cables in perfect condition to avoid accidents, personal injury and
damage to installations.
The manufacturer of the device is not responsible for any damage resulting from failure by the
user or installer to heed the warnings and/or recommendations set out in this manual, nor for
damage resulting from the use of products or accessories that did not come with the device or
that were made by other manufacturers.
If an anomaly or malfunction is detected in the device, do not use the device to take any meas-
urements.
Inspect the work area before taking any measurements. Do not take measurements in danger-
ous areas or where there is a risk of explosion.
Disconnect the device from the power supply (device and measuring system
power supply) before maintaining, repairing or handling the device's connections.
Please contact the after-sales service if you suspect that there is an operational
fault in the device.
9
Instruction Manual
CirCAMP-4DP, CirCAMP-2IP

3.2.- INSTALLATION
On the side of the device are all of the indications adjusted to the CEI 62052-11 standard.
The device is installed on a DIN rail. All connections are located inside the electric panel.
Terminals, opening roofs or removing elements can expose parts that are haz-
ardous to the touch while the device is powered. Do not use the device until it is
fully installed.
3.3.- DEVICE TERMINALS
3�3�1�- CirCAMP-4DP MODEL
Table 3:List of CirCAMP-4DP terminals
Device terminals
1 : Input channel 1 25,26 : Channel 3 relay output
3 : Output channel 1 27,28 : Channel 4 relay output
4 : Input channel 2 / Power supply 31 : Impulse input common
6 : Output channel 2 32 : Channel 1 impulse input
7 : Input channel 3 33 : Channel 2 impulse input
9 : Output channel 3 34 : Channel 3 impulse input
10: Input channel 4 35 : Channel 4 impulse input
11 : Neutral connection 36,37 : Reclose input
12 : Output channel 4 38 : B, RS-485 communications (according to version)
21,22 : Channel 1 relay output 39 : S, RS-485 communications (according to version)
23,24 : Channel 2 relay output 40 : A, RS-485 communications (according to version)
1 3 4 6 11
7910 12 31 32 33 34 35 36 37 38 39 40
21 22 23 24 25 26 27 28
Figure 1:CirCAMP-4DP terminals�
10
CirCAMP-4DP, CirCAMP-2IP
Instruction Manual

3�3�2�- CirCAMP-2IP MODEL
Table 4:List of CirCAMP-2IP terminals
Device terminals
1 : S1, Current input L1 (CH1 y CH2) 23,24 : Channel 2 relay output
3 : S2, Current output L1 (CH1 y CH2) 25,26 : Circuit breaker control 1
4 : S1, Current input L2 (CH1 y CH2) 27,28 : Circuit breaker control 2
6 : S2, Current output L2 (CH1 y CH2) 31 : Impulse input common
7 : S1, Current input L3 (CH1 y CH2) 32 : Channel 1 impulse input
9 : S2, Current output L3 (CH1 y CH2) 33 : Channel 2 impulse input
2: VL1, Voltage input L1 34,35 : Not used
5 : VL2, Voltage input L2 36,37 : Reclose input
8 : VL3, Voltage input L3 38 : B, RS-485 communications (according to version)
11 : Neutral connection 39 : S, RS-485 communications (according to version)
21,22 : Channel 1 relay output 40 : A, RS-485 communications (according to version)
13 4 6 7 9 21 22 23 24 25 26 27 28
CH1 2 5 8 11
31 32 33 34 35 36 37 38 39 40
13467 9
CH2
Figure 2:CirCAMP-2IP terminals�
11
Instruction Manual
CirCAMP-4DP, CirCAMP-2IP

3.4.- CONNECTION DIAGRAM
3�4�1�- CirCAMP-4DP MODEL
1 3 4 6 11
7 9 10 12
31 32 33 34 35 36 37 38 39 40
21 22 23 24 25 26 27 28
L
N
LOAD
Channel 1 Channel 2 Channel 3 Channel 4
CH1
Channel 2
Channel 3 Channel 4
LOAD
LOAD LOAD
Utilizar cualquiera de las 3 fases / Use any line
Channel 1
CH2*
CH3 CH4
Figure 3: Connection diagram, CirCAMP-4DP�
* CH2: The power supply of the device and the PLC communications occur via channel 2.
12
CirCAMP-4DP, CirCAMP-2IP
Instruction Manual

3�4�2�- CirCAMP-2IP MODEL
13 4 6 7 9 21 22 23 24 25 26 27 28
CH1 2 5 8 11
31 32 33 34 35 36 37 38 39 40
13467 9
CH2
L1
N
L2
L3
L1
N
L2
L3
S1 S2
P1 P2 S1 S2
P1 P2 S1 S2
P1 P2
S1 S2
P1 P2
S1 S2
P1 P2
S1 S2
P1 P2
VL1
VL2
VL3
N
Figure 4: Connection diagram, CirCAMP-2IP�
Note: The power supply of the unit is through phase 2
13
Instruction Manual
CirCAMP-4DP, CirCAMP-2IP

3.5.- CONNECTIONS
The CirCAMP-xxP has terminal covers that cover the measuring terminals of the device and
the xing screws (Figure 5).
Figure 5: CirCAMP-xxP terminal covers�
The xing screws are of the mixed type, allowing the use of PZ1 and at head screwdrivers.
Table 5:CirCAMP-xxP connection features
Connection
Model CirCAMP-4DP CirCAMP-2IP
Terminals
1, 3, 4, 6, 7, 9, 10,11,12 1, 3, 4, 6, 7, 9, 2, 5, 8, 11
8 mm 16 mm2≤ 1.2 Nm 8 mm 16 mm2≤ 1.2 Nm
Screwdriver head PZ1 PZ1
Terminals
21 ��� 28 , 31 ��� 40 21 ��� 28 , 31 ��� 40
8 mm 1.5 mm2≤ 0.6 Nm 8 mm 1.5 mm2≤ 0.6 Nm
Screwdriver head Flathead ( 3 x 0.5 mm) Flathead ( 3 x 0.5 mm)
Once connected, the device can be protected with two connection seals (Figure 6).
Figure 6: CirCAMP-xxP seal�
14
CirCAMP-4DP, CirCAMP-2IP
Instruction Manual

4�- OPERATION
The CirCAMP-4DP is a static meter capable of:
Measuring and managing 4 single-phase measurements, independent phase mode.
( CirCAMP-4DP model)
Measuring and managing 1 three-phase measurement, two-phase, etc. , polyphase
mode.( CirCAMP-4DP model)
Measure and manage 2 three-phase measurements independently in current, sharing
the same voltage ( CirCAMP-2IP model)
The device measures:
Active energy stored in both directions.
The active, reactive and apparent power.
Effective voltage and current.
The internal temperature of the unit, CirCAMP-2IP model.
4.1.- KEY FUNCTIONS
The CirCAMP-xxP has 2 keys that allow you to browse the different screens (Table 6):
Table 6: Key functions�
Key Keystroke
For the cyclic movement.
Next screen.
Enters reading mode.
4.2.- DISPLAY
The device features an LCD display where all parameters are displayed (Figure 7):
CirCamp v01.01
s/n: 123456789
Model: 110ED7A83B22
CRC:12341234h
Figure 7:CirCAMP-4DP display�
15
Instruction Manual
CirCAMP-4DP, CirCAMP-2IP

4.3.- LED INDICATORS
4�3�1�- CirCAMP-4DP MODEL
The device features 17 LEDs:
Active Energy pulses
Pulse input
Cutting element
Relay outputs
PLC
CirCAMP-4DP
Figure 8:CirCAMP-4DP LED indicators�
4 to verify the active energy, one for each measurement element. The weight of the
LEDs is 10,000 imp/kWh.
The LEDs will remain lit when the current is lower than the energy meter start-up current.
Once the start-up current is exceeded the LEDs are turned off and emit impulses that are
proportional to the measured energy.
4 to indicate the impulse input of other supplies.
4 to indicate the circuit breaker status.
4 to indicate the relay output status.
1 to indicate the PLC communications status.
Table 7: Status LEDs: CirCAMP-4DP�
LEDs
Cutting element
Power on
The power supply is connected to the electrical network
Power off
The power supply is disconnected from the electrical network
Pulse input Calculation of impulses of other supplies: water, gas, etc.
Relay outputs
Power on
Relay connected.
Power off
Relay disconnected.
16
CirCAMP-4DP, CirCAMP-2IP
Instruction Manual

Table 7 (Cont�): Status LEDs: CirCAMP-4DP�
LEDs
PLC
Power on
Red: It detects other PLC devices but it does not detect the presence of a
concentrator or transducer in the network.
Yellow: After start-up, the recording process can take up to a few hours.
Green: Device recording and fully operational.
Power off
The device does not detect other devices in the PLC network.
4�3�2�- CirCAMP-2IP MODEL
The device features 8 LEDs :
PLC
CirCAMP-2IP
Active Energy pulses
Cutting element
Relay outputs
Pulse input
Figure 9:CirCAMP-2IP LED indicators�
2 to verify the active energy, one for each measurement element. The weight of the
LEDs is 20.000 imp/kWh.
The LEDs will remain lit when the current is lower than the energy meter start-up current.
Once the start-up current is exceeded the LEDs are turned off and emit impulses that are
proportional to the measured energy.
2 to indicate the impulse input of other supplies.
2 to indicate the circuit breaker status.
2 to indicate the relay output status.
1 to indicate the PLC communications status.
Table 8: Status LEDs: CirCAMP-2IP�
LEDs
Cutting element
Power on
The power supply is connected to the electrical network
Power off
The power supply is disconnected from the electrical network
Pulse input Calculation of impulses of other supplies: water, gas, etc.
17
Instruction Manual
CirCAMP-4DP, CirCAMP-2IP

Table 8 (Cont�): Status LEDs: CirCAMP-2IP�
LEDs
Relay outputs
Power on
Relay connected.
Power off
Relay disconnected.
PLC
Power on
Red: It detects other PLC devices but it does not detect the presence of a
concentrator or transducer in the network.
Yellow: After start-up, the recording process can take up to a few hours.
Green: Device recording and fully operational.
Power off
The device does not detect other devices in the PLC network.
4.4.- IMPULSE INPUTS
The device features:
CirCAMP-4DP model: 4 impulse inputs (terminals 31 ... 35 in Table 3), according to UNE EN
62053-31:1999 class B, for the calculation of other supplies.
CirCAMP-2IP model: 2 impulse inputs (terminals 31, 32 and 35 in Table 4), according to UNE
EN 62053-31:1999 class B, for the calculation of other supplies.
31 35
5 V DC
470 Ω
COMM
470 Ω
...
CirCAMP-4DP
31 33
5 V DC
470 Ω
COMM
470 Ω
CirCAMP-2IP
Figure 10:Impulse inputs�
18
CirCAMP-4DP, CirCAMP-2IP
Instruction Manual

4.5.- RELAY OUTPUTS
The device features:
CirCAMP-4DP model: 4 relay outputs (terminals 21 ... 28 in Table 3).
CirCAMP-2IP model: 2 relay outputs (terminals 21 ... 24 in Table 4).
21 28
CirCAMP-4DP
Relay
Channel
1
Channel
2
Channel
3
Channel
4
21 24
CirCAMP-2IP
Relay
Channel
1
Channel
2
Figure 11:Impulse inputs�
4.6.- CIRCUIT BREAKER
4�6�1�- CirCAMP-4DP MODEL
The CirCAMP-4DP features 4 circuit breakers, one for each of the measurement channels
located inside the device, with no parts being accessible from the exterior.
Cut off occurs only on the phase line and can be generated:
By an order� The manager can send a command to open a circuit breaker via any
communications port. These orders are usually used for:
● Cut offs or Reclosures for managing unpaid accounts.
● Commencing or terminating supply service.
The circuit breaker can only be reclosed via another communications command.
Depending on the contracted power. A different power threshold can be congured
for each circuit breaker, which opens the circuit breaker in the case that the power
demanded by the customer is exceeded.
The circuit breaker is reclosed automatically after 2n minutes have passed, with n being
the number of attempted retries. Or automatically, via the reclose input of the CirCAMP-
4DP.
The reclose input is located in terminals 36 and 37 of the device, see Table 3�
19
Instruction Manual
CirCAMP-4DP, CirCAMP-2IP

36 37
5 V DC
470 Ω
COMM
Figure 12:Circuit breaker�
4�6�2�- CirCAMP-2IP MODEL
The CirCAMP-2IP model does not have circuit breakers located inside the unit.
It has two relays (terminals 25... 28 of Table 4) for controlling the external circuit breakers.
The cut-off can be generated:
By an order� The manager can send a command to open a circuit breaker via any
communications port. These orders are usually used for:
● Cut offs or Reclosures for managing unpaid accounts.
● Commencing or terminating supply service.
The circuit breaker can only be reclosed via another communications command.
Depending on the contracted power. A different power threshold can be congured
for each circuit breaker, which opens the circuit breaker in the case that the power
demanded by the customer is exceeded.
The circuit breaker is reclosed automatically after 2n minutes have passed, with n being
the number of attempted retries. Or automatically, via the reclose input of the CirCAMP-
2IP.
The reclose input is located in terminals 36 and 37 of the device, see Table 4 and Figure 12�
20
CirCAMP-4DP, CirCAMP-2IP
Instruction Manual
This manual suits for next models