CKD PPX Series User manual

MJE-PPX No.0040-81V
INSTRUCTION MANUAL
PARECT PRESSURE SWITCH
PPX series
Read this instruction manual carefully before using this product, particularly the section
describing safety.
Retain this instruction manual with the product for further consultation whenever necessary.
Precaution
● This product is designed for air / non-corrosive gas.
●
● Do not touch electric wiring connections (bare live parts): this will cause an electric shock.
During wiring, keep the power off. Also, do not touch these live parts with wet hands.
● A product intended for use in Japan conforms to the Japanese Measurement Act.
Do not use a product intended for use overseas in Japan.
1PART DESCRIPTION
㸯
Connection
connector
Pressure port
6M type: R1/8+ M5 female screw
6G type: G1/8+ M5 female screw
6N type: NPT1/8+ M5 female screw
PPX
Output 1 operation
indicator
Lights up when com-
parative output 1 is ON
Mode selection key
Unit display
(Note 1, 2)
Main display
Sub display
Setting value
DOWN key
Setting value UP key
Output 2 / analogue
voltage / current out-
put operation indicator
Standard type:
Lights up when com-
parative output 2 is ON
High-function type:
Lights up when analogue
voltage / current output is set
Notes: 1) In the case of a model that is intended for use outside Japan, attach the unit switch plate corresponds to the set
pressure unit.
2) The product for use inside Japan can be set only to “MPa” or “kPa.”
2PIPING
● When connecting a commercial coupler to the pres-
sure port, attach a 12mm spanner (14mm for 6G
type) to the pressure port’s hexagon section to fix
the port, and then tighten with a tightening torque of
9.8N·m or less (M5 female: 1N·m or less). The com-
mercial coupler or pressure port section will be dam-
aged if the tightening torque is excessive.
Wrap sealing tape around the coupler when connect-
ing to prevent leaks.
12mm spanner
3MOUNTING
● The sensor mounting bracket PPX-KL is available as an option. When mounting the sensor
onto the sensor mounting bracket, etc., the tightening torque should be 0.5N·m or less.
M3 (length 6mm) screws
with washers
(Accessory with PPX-KL)
Sensor mounting bracket
PPX-KL (Optional)
● The panel mounting bracket PPX-KHS (optional), as well as the front cover PPX-KCB
(optional) are also available.
● For mounting of the panel mounting bracket, refer to the Instruction Manual en-
closed with PPX-KHS.
4WIRING
Connection method
● Insert the cable with connector PPX-C□ into
this product’s connection connector section
Disconnection method
● Pressing the release lever of the cable with
connector, pull out the connector.
Cable with connector
PPX-C□
Release lever
<Recommended product>
Contact: SPHD-001T-P0.5
Housing: PAP-04V-S
[JST Mfg. Co., Ltd.]
Note:
Do not pull by holding the cable without pressing the release lever, as this can cause cable break or connector break.
<Connection connector pin arrangement>
1 2 3 4
Connector pin No.
Terminal name
1 +V
2 Comparative output 1
3Standard type: Comparative output 2
High-function type: Analogue voltage / current output or external input
4 0V
5I/O CIRCUIT DIAGRAMS
NPN output type
Standard type
Main circuit
(Brown) +V
(Black)
Comparative output 1
(White) Comparative output 2
(Blue) 0V
Load
Load
100mA max.
100mA max.
+
12 to 24V DC
±10%
-
High-function type
Main circuit
(Brown) +V
(White)
Analogue voltage / current output
or external input (Notes 1, 2, 3)
(Black)
Comparative output 1
(Blue) 0V
Load
100mA max.
5V
1kΩ +
12 to 24V DC
±10%
-
PNP output type
Standard type
Main circuit
(Brown) +V
(Black) Comparative output 1
(White)
Comparative output 2
(Blue) 0V
Load
Load
100mA max.
100mA max.
+
12 to 24V DC
±10%
-
High-function type
Main circuit
(Brown) +V
(White)
Analogue voltage / current output
or external input (Notes 1, 2, 3)
(Black)
Comparative output 1
(Blue) 0V
Load
100mA max.
1kΩ
+
12 to 24V DC
±10%
-
Notes: 1) When the analogue current is output, the output load resistance should be 250Ω max.
2) Take care that when the analogue current is output, 5V or more voltage generates.
3) When using the analogue voltage output, be careful to the input impedance of the connected device.
Furthermore, note that if the cable is extended, the cable resistance will cause the voltage to drop.
6OUTPUT MODE AND OUTPUT OPERATION
● The EASY mode, hysteresis mode or window comparator mode can be selected as
the output mode for comparative output 1 and comparative output 2.
Refer to <Comparative output 1 / 2 output mode setting> in “ 8MENU SET-
TING MODE” for details.
EASY mode
● ON / OFF of the comparative output is controlled in this mode.
Pressure
P
0
ON
OFF
Comparative
output
H (Hysteresis)
Notes: 1)
Refer to in “ 9PRO MODE” for setting.
2) “ ” is displayed for comparative output 1 and “ ” for comparative output 2 on the sub-display.
Hysteresis mode
● The comparative output ON / OFF state can be controlled with randomly set hyster-
esis in this mode.
0
Pressure
Comparative
output
H (Hysteresis)
Hi
Lo
ON
OFF
H: 1digit or more
2 digits or more when
using psi unit
Note: “ ” or “ ” is displayed for comparative output 1 and “ ” or “ ” for comparative output 2 on the
sub-display.

Window comparator mode
● In this mode, the ON or OFF state of the comparative output is controlled with a
pressure in the set range.
0
Pressure
Comparative
output
H (Hysteresis)
H (Hysteresis)
Hi
Lo
ON
OFF
Notes: 1)
Refer to in “ 9PRO MODE” for setting.
2) “ ” or “ ” is displayed for comparative output 1 and “ ” or “ ” for comparative output 2 on the
sub-display.
3)
7RUN MODE
Setting the threshold value
● Refer to <Comparative output 1 / 2 output mode setting>, <Analogue voltage
/ current output / external input selection> in “ 8MENU SETTING MODE” for
setting conditions.
● The Sub display conducts the threshold value. Main display does not changed.
Comparative output 1
Comparative output 2
Comparative output 1
Comparative output 2
Comparative output 1
Comparative output 2
EASY mode
(Comparative output 2 is OFF)
EASY mode
Hysteresis mode / Window
comparator mode · Lo side
Hysteresis mode / Window
comparator mode · Hi side
(Note 3)
Press: Increase threshold value to high pressure side.
Press: Decrease threshold value to low pressure side.
Automatic
Display is changed by pressing down.
(Note 2)
Blinks alternately
Notes: 1) If the set pressure range is exceeded,
“ ”
(exceeds the upper limit) or
“ ”
(exceeds the lower limit) will
appear on the sub display.
“ ”
will also appear if the Hi side threshold value exceeds the Lo side threshold
value when setting the “hysteresis mode / window comparator mode” threshold value.
2) Auto-reference value and remote zero-adjustment value are displayed.
For details, refer to “
11
AUTO-REFERENCE FUNCTION” and “
12
REMOTE ZERO-ADJUSTMENT FUNCTION.”
3) In the dash line box is not displayed when not setting “ ” or “ ” in external input switch. For the setting
method, refer to <Analogue voltage / current output / external input selection> in “ 8MENU SETTING
MODE.”
Zero-adjustment function
● The zero-adjustment function forcibly sets the pressure value to “zero” when the
pressure port is opened.
Automatic
Hold down
Key lock function
● The key lock function prevents key operations so that the conditions set in each set-
ting mode are not inadvertently changed.
<Key lock set>
Automatic
Hold down
<Key lock released>
Automatic
Hold down
Peak / bottom hold function
● The peak / bottom hold functions display the peak value and bottom value of the
● The peak value is displayed on the main display and the bottom value is displayed
on the sub-display.
● The higher vacuum side indicates the peak value, while the lower vacuum side indi-
cates the bottom value.
<Peak / bottom hold set>
Hold down Blinks alternately
<Peak / bottom hold released>
Hold down
8MENU SETTING MODE
● The mode will change to RUN mode when the mode selection key is held down
during this setting process. In doing so, changed items before holding down the
mode selection key have been set.
RUN mode
<Comparative output 1 output mode setting>
EASY mode
Hysteresis
mode
Press for 2 sec.
Window
comparator
mode
● Standard type
<Comparative output 2 output mode setting> (Note 1)
EASY mode
Hysteresis
mode
Window
comparator
mode
OFF mode
● High-function type
<N.O. / N.C. selection>
N.C.N.O.
● Standard type
<N.O. / N.C. selection> (Note 1)
Output 1: N.O.
Output 2: N.O.
Output 1: N.C.
Output 2: N.C.
Output 1: N.O.
Output 2: N.C.
Output 1: N.C.
Output 2: N.O.
<Response time setting>
5ms2.5ms 5,000ms
<Display color of the main display selection>
Red when ON
Green when OFF
Green when ON
Red when OFF
Always red
Always green
<Unit selection> (Note 2)
kPaMPa bar
inchHg (Note 3)
kgf/cm2psi
mmHg (Note 3)
RUN mode
● High-function type
<Analogue voltage / current output / external input selection>
Auto-refer-
ence input
Remote
zero-adjust-
ment input
Analogue
voltage output
Analogue
current output
Notes: 1) If the comparative output 2 output mode setting is set to “ ”, the display of N.O. / N.C. selection is the same
as the high-function type.
2) In case Japanese, only “MPa” or “kPa” can be set. In the case of a low pressure type, the unit switch setting
item is not displayed.
3) This is not displayed on the high pressure type.
Setting item Factory setting Description
Comparative output 1
output mode setting
Sets the output operation of comparative output 1.
Comparative output 2
output mode setting
(Standard type only)
Sets the output operation of comparative output 2.
Analogue voltage /
current output / ex-
ternal input selection
(High-function type only)
Selects analogue voltage / current output, auto-reference input, or remote
zero-adjustment input.
N.O. / N.C. selection
Low pressure type
High pressure type
Normal open (N.O.) or normal close (N.C.) can be selected.
Response time setting
Sets the response time.
The response time can be selected from 2.5ms, 5ms, 10ms, 25ms, 50ms,
100ms, 250ms, 500ms, 1,000ms or 5,000ms.
Displayed color of the
main display selection
Displayed color of the main indicator can be changed.
Unit selection
Low pressure type
High pressure type
Pressure unit can be changed.

9PRO MODE
● The mode will change to RUN mode when the mode selection key is held down
during this setting process. However, changed items before holding down the mode
selection key have been set.
RUN mode
<PRO mode>
Press for
4 seconds
<Sub-display selection>
Display OFF
Unit display
No. display
Standard
<Display speed selection>
500ms250ms
<Reset setting>
RUN mode
RUN mode
<Sub-display selection>
When “ ” is set
When “ ” is set
Change the displayed details with
Set pressure
range is displayed
on sub display.
Custom
display
1,000ms
Min.Max.
<Displayed color relation selection>
Relating with
comparative
output 1
Relating with
comparative
output 2
<Eco mode setting>
OFF Standard Max.
Automatic
<Setting check code>
<Setting copy mode>
Copy sending
OFF
Copy sending
ON
Copy sending
ON-L
Copy ready
state
When “No. display” or “Custom display” is set in “Sub display selection.”
● Standard type only
Setting item Factory setting Description
Sub-display selection
Changes the indication of the sub-display.
“ ” : Displays nothing.
“ ” : Presently selected pressure unit is displayed.
“ ” : Desired No. can be shown.
“ ” : Desired numbers, alphabets (some of them cannot be displayed)
and signs can be shown.
Display speed
selection Changes the speed of the displayed pressure value on the main display.
value selection
Sets hysteresis of the EASY mode and the window comparator mode.
(8 steps)
Displayed color rela-
tion selection
(Standard type only)
The setting contents set at the displayed color setting in Menu setting mode
can be related with either comparative output 1 or comparative output 2.
Eco mode setting
Current consumption can be lowered.
“ ” : Normal operation (ECO mode is off.)
“ ” : If any key operation is not carried out for approx. 5 sec. in RUN
mode, the display becomes dark.
“ ” : If any key operation is not carried out for approx. 5 sec. in RUN
mode, the display is turned off.
Press any key to temporarily show the normal indication.
Setting check code Current setting contents can be checked. For codes. refer to “Code table”.
Setting copy mode
The setting of the master side sensor can be copied to the slave side sensors.
For details, refer to “
10
SETTING COPY FUNCTION.”
“ ” : The setting contents are copied.
“ ” : The setting contents are copied, and the slave side sensor goes
into key-lock state.
Reset setting
Returns to default settings (factory settings).
By pressing dowun mode key when “ ” mode, becomes default settings
(factory settings).
Code table
●Main display (1st digit form left)
Code
1st digit 2nd digit 3rd digit 4th digit
Standard type
High-function type
Standard type
Comparative
output 1
output mode
N.O. / N.C.
selection
Comparative
output 2
output mode
N.O. / N.C.
selection
Analogue
voltage / cur-
rent output /
external input
Threshold
display
Displayed
color of the
main display
Displayed
color relation
EASY
N.O. OFF OFF
Analogue
voltage output
P-1, Lo-1
Red when ON
Comparative
output 1
N.C.
EASY
N.O.
Auto reference
Hi-1 Comparative
output 2
Hysteresis
N.O. N.C.
Remote zero-
adjustment
P-2, Lo-2
Green when ON
Comparative
output 1
N.C.
Hysteresis
N.O.
Analogue
current output
Hi-2 Comparative
output 2
Window
comparator
N.O. N.C.
-
ADJ.
Always red
Comparative
output 1
N.C. Window
comparator
N.O.
- -
Comparative
output 2
- -
N.C.
- -
Always green
Comparative
output 1
- - - - - -
Comparative
output 2
●Sub-display (5th digit from left)
Code
5th digit 6th digit 7th digit 8th digit
Response time Unit selection Display speed Eco mode
2.5ms MPa 250ms OFF
5ms kPa 500ms Std
10ms kgf/cm21,000ms Full
25ms bar
- -
50ms psi
- -
100ms mmHg
- -
250ms inchHg
- -
500ms
- - -
1,000ms
- - -
5,000ms
- - -
10
SETTING COPY FUNCTION
● This can copy the settings of the master side sensor to the slave side sensor.
● Be sure to use the setting copy function between the identical models.
This function cannot be used between different models.
● Only one sensor can be connected on slave side with a master side sensor for the
setting copy function.
Setting procedure
1. Set the setting copy function of the master side sensor to “Copy sending ON” or
“Copy sending ON-L”, and then press the mode selection key so that the sensor is
in copy ready state. For details, refer to <Setting copy mode> in “ 9PRO MODE”.
2. Turn OFF the master side sensor.
3. Connect the master side sensor with the slave side sensor as shown below.
(Brown) +V +V (Brown)
(Black) Comparative output 1 Comparative output 1 (Black)
(White) Comparative output 2 (Note 1)
Master side sensor Slave side sensor
Comparative output 2 (Note 1) (White)
(Blue) 0V 0V (Blue)
Power supply
Color code of cable
with connector
Notes: 1) For the high-function type, external input.
4. Turn ON the master side sensor and the slave side sensor at the same time.
(Note 2) (Note 3)
5. Set contents (16-bit coded) are shown in orange on the main display of the master
side sensor and the copying starts.
6. The same code explained above is shown in green on the the main display of the
slave side sensor, and “ ” is shown on the sub-display (When copying is com-
plete.)
7. Turn OFF the power of the master side sensor and the slave side sensor and dis-
connect the wire.
* If copying the setting to another sensor repeatedly, follow steps 3to 7.
Notes: 2) Take care that if the power is not turned on at the same time, the setting contents may not be copied.
3) Note that when the power is on, pulse output is output to comparative output 1.
To cancel the setting copy mode of master side sensor
1. Whilst the slave side sensor is disconnected, turn on the power of the master side
sensor.
2. Press the mode selection key for approx. 2 seconds.

11
AUTO-REFERENCE FUNCTION (ONLY HIGH-FUNCTION TYPE)
● The auto-reference function
corrects the set value using the
detected pressure value during
auto-reference input as the refer-
ence pressure.
● Using the detected pressure val-
ue at auto-reference input P(a)
as a reference, the set value 1’
is automatically corrected to “set
value 1+ P(a)”.
Before
auto-reference
After
auto-reference
ON
OFF
ON
OFF
Atmospheric pressure P(a)
Set value 1
Set value 1’
Detected pressure value
at auto-reference input
Pressure
Set value 1’ after auto-reference is:
1’ = 1+ P(a)
Settable range and set pressure range after correction
● The set pressure range is wider than the rating pressure range so that the auto-
reference function can be handled.
If the corrected set value exceeds the set pressure range when auto-reference input
is carried out, the set value will be automatically corrected to within the set pressure
range. Thus, take care not to exceed the set pressure range.
Operation chart
During normal operation
(each comparative output set to N.O.)
During auto-reference input
(each comparative output set to N.O.)
• Detected pressure at auto-reference input: 10kPa
• Output mode: Hysteresis mode
Output
ON
OFF
Applied pressure (kPa) 0
0
10
10
20
20
30
30
40
40
50
50
60
60Displayed value (kPa)
1 2
10 20Set value (kPa)
Output
ON
OFF
Applied pressure (kPa) 0
0
10
10
20
20
30
30
40
40
50
50
60
60Displayed value (kPa)
P(a) 1’
10 20Set value (kPa)
2’
30
Note: The set values shift in the same manner during the EASY mode or the window comparator mode.
● The detected pressure value at auto-reference input becomes “zero” when the set-
ting of the external input selection function is changed or the power is turned ON
again.
● The auto-reference input value can be checked when setting the threshold value in
RUN mode. Refer to the threshold value setting in “ 7RUN MODE” for details.
12
REMOTE ZERO-ADJUSTMENT FUNCTION (HIGH-FUNCTION TYPE)
● The remote zero-adjustment function forcibly sets the pressure value to “zero” when
the external signal is inputted.
The set value is not corrected when remote zero-adjustment is input. Make sure that the
pressure and set value during remote zero-adjustment do not exceed the set pressure
range.
Operation chart
During normal operation
(each comparative output set to N.O.)
During remote zero-adjustment input
(each comparative output set to N.O.)
• Detected pressure at remote zero-adjustment input: 10kPa
• Output mode: Hysteresis mode
Output
ON
OFF
Applied pressure (kPa) 0
0
10
10
20
20
30
30
40
40
50
50
60
60Displayed value (kPa)
1 2
10 20Set value (kPa)
Output
ON
OFF
Applied pressure (kPa) 0
0
10
10
20
20
30
30
40
40
50
50
60
-10Displayed value (kPa)
1
10 20Set value (kPa)
2
Note: The setting values shift in the same manner during the EASY mode or the window comparator mode.
● The remote zero-adjustment value is cleared when the setting of the external input
selection is changed or the power is turned ON again, and normal operation based
on the atmospheric pressure is resumed.
● The remote zero-adjustment value can be confirmed when setting the threshold
value in RUN mode. Refer to the threshold value setting in “ 7RUN MODE”.
13
ERROR INDICATION
Error message Cause Corrective action
The load is short-circuited causing Turn the power OFF and check the load.
Pressure is applied during zero-
point adjustment.
Applied pressure at the pressure port should be brought to
atmospheric pressure and zero-point adjustment should be
done again.
External input is carried out outside
the rated pressure range.
Applied pressure range should be brought within the rated
pressure range.
Communication error
(Disconnection, faulty connection, etc.)
Check the wiring when using the copy function.
Communication error
(Incorrect model.) when using the copy function.
The applied pressure exceeds the
upper limit of the display pressure
range. Applied pressure range should be brought within the rated
pressure range.
The applied pressure exceeds the
lower limit of the display pressure
range.
When other error massage is displayed, contact us.
14
SPECIFICATIONS
●Model
PPX-R 1 2 3 -4-5-6
1: 01: Low-pressure type, 10: High-pressure type
2: N: NPN output type, P: PNP output type
3: None: Standard type, H: High-function type
4: 6M: R1/8+ M5 female screw (Note 1), 6G: G1/8+ M5 female screw (Note 2)
6N: NPT1/8+ M5 female screw (Note 3)
5: None: Cable with connector enclosed, J: No cable with connector (Note 4)
6: KA: For outside of Japan, None: For inside of Japan
Notes: 1) PNP output type is not available in the 6M type.
2) NPN output type and for inside of Japan are not available in the 6G type.
3) For inside of Japan is not available in the 6N type.
4) High-function type is not available in the J type.
Type
Item
Standard type High-function type
Low-pressure type High-pressure type Low-pressure type High-pressure type
Pressure type Gauge pressure
Rated pressure range -100 to +100kPa -0.1 to +1.0MPa -100 to +100kPa -0.1 to +1.0MPa
Set pressure range
-101.0 to +101.0kPa
-0.101 to +1.010MPa
-101.0 to +101.0kPa
-0.101 to +1.010MPa
Withstand pressure 500kPa 1.5MPa 500kPa 1.5MPa
Non-corrosive gas
Supply voltage 12 to 24V DC ±10%
Power consumption (Note 1)
Normal operation: 720mW or less (current consumption 30mA or less at 24V supply voltage)
ECO mode (STD): 480mW or less (current consumption 20mA or less at 24V supply voltage)
ECO mode (FULL): 360mW or less (current consumption 15mA or less at 24V supply voltage)
Comparative output
<NPN output type>
NPN open-collector transistor
• Maximum sink current: 100mA
• Applied voltage: 30V DC or less
(between comparative output and 0V)
• Residual voltage: 2V or less
(at 100mA sink current )
<PNP output type>
PNP open-collector transistor
• Maximum source current: 100mA
• Applied voltage: 30V DC or less
(between comparative output and +V)
• Residual voltage: 2V or less
(at 100mA source current )
Output operation Selectable either N.O. or N.C., with key operation
Hysteresis Min. 1 digit (variable) (however, 2 digits when using psi units)
Repeatability ±0.1% F.S.
± within 2 digits
±0.2% F.S.
± within 2 digits
±0.1% F.S.
± within 2 digits
±0.2% F.S.
± within 2 digits
Response time 2.5ms, 5ms, 10ms, 25ms, 50ms, 100ms, 250ms, 500ms, 1.000ms or 5,000ms
selectable with key operations
Analogue voltage output
<High-function, low-pressure type>
• Output voltage: 1 to 5V
• Zero point: Within 3V ± 5% F.S.
• Span: Within 4V ± 5% F.S.
• Linearity: Within ± 1% F.S.
• Output impedance: Approx. 1kΩ
<High-function, high-pressure type>
• Output voltage: 0.6 to 5V
• Zero point: Within 1V ± 5% F.S.
• Span: Within 4.4V ± 5% F.S.
• Linearity: Within ± 1% F.S.
• Output impedance: Approx. 1kΩ
Analogue current output
<High-function, low-pressure type>
• Output current: 4 to 20mA
• Zero point: Within 12mA ± 5% F.S.
• Span: Within 16mA ± 5% F.S.
• Linearity: Within ± 1% F.S.
• Load resistance: 250Ω (max.)
<High-function, high-pressure type>
• Output current: 2.4 to 20mA
• Zero point: Within 4mA ± 5% F.S.
• Span: Within 17.6mA ± 5% F.S.
• Linearity: Within ± 1% F.S.
• Load resistance: 250Ω (max.)
External input
<High-function NPN output type>
• ON voltage: 0.4V DC or less
• OFF voltage: 5 to 30V DC or open
• Input impedance: Approx. 10kΩ
• Input time: 1ms or more
<High-function PNP output type>
• ON voltage: 5V to +V DC
• OFF voltage: 0.6V DC or less or open
• Input impedance: Approx. 10kΩ
• Input time: 1ms or more
Ambient temperature -10 to +50°C (No dew condensation or icing allowed), Storage: -10 to +60°C
Ambient humidity 35 to 85% RH, Storage: 35 to 85% RH
Temperature characteristics Within ±0.5% F.S.
(at +20°C reference)
Within ±1% F.S.
(at +20°C reference)
Within ±0.5% F.S.
(at +20°C reference)
Within ±1% F.S.
(at +20°C reference)
Material Pressure port: Stainless steel (SUS 303Cu)
Mounting screw section: Brass (nickel-plated), O-ring: H-NBR, Key part: Silicon rubber
Weight
Approx. 40g (6G type: approx. 45g) (Main body only)
Accessories PPX-C2 (Cable with a connector, 2m long) (optional for Jtype): 1 pc.
Unit switching label: 1 pc. (for outside of Japan only)
Note: Current consumption does not include the analog current output.
15
CAUTIONS
● This product has been developed / produced for industrial use only.
● Use within the rated pressure range.
● Do not apply pressure exceeding the pressure withstandability value. The dia-
phragm will get damaged and correct operation shall not be maintained.
● Make sure that the power supply is off while wiring.
● Take care that wrong wiring will damage the sensor.
● Verify that the supply voltage variation is within the rating.
● If power is supplied from a commercial switching regulator, ensure that the frame
ground (F.G.) terminal of the power supply is connected to an actual ground.
● In case noise generating equipment (switching regulator, inverter motor, etc.) is
used in the vicinity of this sensor, connect the frame ground (F.G.) terminal of the
equipment to an actual ground.
● Do not use during the initial transient time (0.5 sec.) after the power supply is
switched on.
● Extension up to total 100m or less, is possible with more than 0.3mm2of electric
conductor cross-sectional area cable.
● In case of using this product as a CE Marking conformity product, the wire con-
nected to this product must be within 30m.
● Do not run the wires together with high-voltage lines or power lines or put them in
the same raceway. This can cause malfunction due to induction.
●
● Avoid dust, dirt, and steam.
● Take care that the sensor does not come in direct contact with water, oil, grease, or
organic solvents, such as, thinner, etc.
● Do not insert wires, etc, into the pressure port. The diaphragm will get damaged
and correct operation shall not be maintained.
● Do not operate the keys with pointed or sharp objects.
● Make sure that stress by forcible bend or pulling is not applied directly to the sensor
cable joint.
CKD Corporation
2-250, OUJI, KOMAKI, AICHI 485-8551, Japan
http://www.ckd.co.jp
Other manuals for PPX Series
2
Other CKD Switch manuals
Popular Switch manuals by other brands

Alcatel-Lucent
Alcatel-Lucent OmniSwitch 6250 Hardware user's guide

Dell
Dell PowerConnect 3424 user guide

NETGEAR
NETGEAR ProSAFE GS116Ev2 installation guide

Ruelco
Ruelco 30C2 Operation manual

schmersal
schmersal MAF/S 441-11Y operating instructions

Honeywell
Honeywell kromshroeder DL H Series operating instructions