Clack Valve WS1.25 Guide

Water Specialist
1” Control Valve Series Model: WS1
1.25” Control Valve Series Model: WS1.25
Operation and Instruction Manual for OEM Only.
Please Note: This operation and instruction manual is for the training of
the OEM and for the OEM to use to train their customers. This document
is not to be used as the complete system manual.

Page 2WS1 & 1.25 Manual

WS1 & 1.25 Manual Page 3
Table of Contents
Control Valve Function and Cycles of Operation....................................................................................................4
OEM General Programming Instructions................................................................................................................8
OEM Softener System Setup .....................................................................................................................9
OEM Filter System Setup........................................................................................................................11
Installer Displays/Settings .......................................................................................................................12
User Displays/Settings.............................................................................................................................12
Diagnostics ..............................................................................................................................................14
Valve History ...........................................................................................................................................15
Drawings and Part Numbers
Front Cover and Drive Assembly ............................................................................................................16
FOR INFORMATION COMMON TO ALL 1” & 1.25” CONTROL VALVES REFER TO THE
WS1 & WS1.25 DRAWINGS AND SERVICE MANUAL

Page 4WS1 & 1.25 Manual
Control Valve Function and Cycles of Operation
This glass lled Noryl1(or equivalent) fully automatic control valve is designed as the primary control center to direct and
regulate all cycles of a water softener or lter. When the WS1 or the WS1.25 control valve is manufactured as a softener, the
control valve can be ordered to perform downow or upow regeneration. When the WS1 or WS1.25 control valve is set up
as a lter, the control valve can be set to perform downow regeneration or simply backwash. The control valve can be set
to regenerate on demand (consumption of a predetermined amount of water) and/or as a time clock (passage of a particular
number of days). The control valve can be set so that a softener can meet the Water Quality Association (WQA) Standard
S100 or NSF/ANSI Standard 44 efciency rating.
It is not recommended to change control valves from downow to upow brining or vice versa in the eld. The valve bodies for
downow and upow are unique to the regeneration type and and should not be interchanged. A mismatch of valve body and
regeneration piston will result in hard water bypass during service.
The control valve is compatible with a variety of regenerants and resin cleaners. The control valve is capable of routing the
ow of water in the necessary paths to regenerate or backwash water treatment systems. The injector regulates the ow of
brine or other regenerants. The control valve regulates the ow rates for backwashing, rinsing, and the replenishing of treated
water into a regenerant tank, when applicable.
The control valve uses no traditional fasteners (e.g. screws); instead clips, threaded caps and nuts and snap type latches are
used. Caps and nuts only need to be rmly hand tightened because radial seals are used. Tools required to service the valve
include one small blade screw driver, one large blade screw driver, pliers and a pair of hands. A plastic wrench is available
which eliminates the need for screwdrivers and pliers. Disassembly for servicing takes much less time than comparable
products currently on the market. Control valve installation is made easy because the distributor tube can be cut ½”above
to ½”below the top of tank thread. The distributor tube is held in place by an o-ring seal and the control valve also has a
bayonet lock feature for upper distributor baskets.
The AC adapter power pack comes with a 15 foot power cord and is designed for use with the control valve. The AC adapter
power pack is for dry location use only. The control valve remembers all settings for up to 8 hours if the power goes out and
the battery is not depleted. After 8 hours, the only item that needs to be reset is the time of day; other values are permanently
stored in the nonvolatile memory. If a power loss lasts less than 8 hours and the time ashes on and off, the time of day
should be reset and the non rechargeable battery should be replaced.
Table 1 shows the order of the cycles when the valve is set up as a softener. When the WS1 or WS1.25 control valve is used
as a downow softener, two backwashes always occur. When the WS1 or WS1.25 control valve is used as an upow softener,
only one backwash occurs after brining. The OEM has the option of having the regenerant rell after the rinse cycle or
have the regenerant prell before regeneration. If the OEM chooses to have the regenerant prell before regeneration, the
prell starts two hours before the regeneration time set. During the 2-hour period in which the brine is being made, treated
(softened) water is still available. For example: regeneration time = 2:00 am, prell option selected, downow softener. Fill
occurs at 12:00 a.m., start of backwash cycle occurs at 2:00 a.m.
WS1 & WS1.25 Downflow
Regenerant Refill After
Rinse
WS1 & WS1.25 Downflow
Regenerant Prefill
WS1 & WS1.25
Upflow Regenerant
Refill After Rinse
WS1 & WS1.25
Upflow Regenerant
Prefill
1st Cycle: Backwash
2nd Cycle: Regenerate
3rd Cycle: Backwash
4th Cycle: Rinse
5th Cycle: Fill/Dissolve
6th Cycle: Service
1st Cycle: Fill/Dissolve
2nd Cycle: Backwash
3rd Cycle: Regenerate
4th Cycle: Backwash
5th Cycle: Rinse
6th Cycle: Service
1st Cycle: Regenerate
2nd Cycle: Backwash
3rd Cycle: Rinse
4th Cycle: Fill/Dissolve
5th Cycle: Service
1st Cycle: Fill/Dissolve
2nd Cycle: Regenerate
3rd Cycle: Backwash
4th Cycle: Rinse
5th Cycle: Service
Table 1
Regeneration Cycles Softening
1Noryl is a trademark of Sabic Innovative Plastics IP B.V. Company

WS1 & 1.25 Manual Page 5
Table 4 shows the order of the cycles when the valve is set up as a lter. When the control valve is used as a downow
regenerating lter, the OEM has the option to specify one backwash or two backwashes. If the control valve is set to
regenerate for a lter, the OEM has the option of having the regenerant rell after the rinse cycle or have the regenerant prell
before regeneration. If the OEM chooses to have the regenerant prell before regeneration, the prell starts two hours before
the regeneration time set. During the 2-hour period in which the regenerant is being made, treated water is still available. For
example: regeneration time = 2:00 am, prell option selected, downow lter. Fill occurs at 12:00 a.m., start of backwash
cycle occurs at 2:00 a.m. There is only one rinse. Backwashes can be set to normal or longer. The option selected will apply to
all backwashes. Tables 5 and 6 show the length of the cycles when the valve is set up as a lter.
2These are reference numbers that approximate the amount of salt needed. The actual capacity in grains per pound of salt is
used in calculations.
3 Total time does not include ll time, which is dependent upon the amount of salt needed. When in the ll mode the system
is providing treated water.
When the control valve is used as a non-regenerating lter, the OEM has the option to specify one backwash or two
backwashes. If two backwashes are specied, two rinses occur. Tables 5 and 6 show the length of the cycles when the valve
is set up as a lter. When used as a non-regenerating lter, the downow piston must be installed, the regenerant piston
removed, injector plugs must be installed in both the DN and UP injector locations and the rell elbow must be replaced with
a rell port plug.
Table 2
Backwash Normal Length Softener
Cycle Times in Minutes
WS1 & WS1.25 Downflow Softener WS1 & WS1.25 Upflow Softener
Grains Capacity/lb NaCl 6000 to 3501 3500 to 2501 2500 to 1700 6000 to 3501 3500 to 2501 2500 to 1700
lbs NaCl/cu ft resin2Less than 7.5 7.5 to 12 More than 12 Less than 7.5 7.5 to 12 More than 12
Backwash Normal 6 8 8
Regenerate 45 60 75 45 60 75
Backwash Normal 3 8 10 6 10 12
Rinse 346346
Total357 80 99 54 74 93
Cycle time
in Minutes
WS1 & WS1.25 Downflow Softener WS1 & WS1.25 Upflow Softener
Grains Capacity/lb NaCl 6000 to 3501 3500 to 2501 2500 to 1700 6000 to 3501 3500 to 2501 2500 to 1700
lbs NaCl/cu ft resin2Less than 7.5 7.5 to 12 More than 12 Less than 7.5 7.5 to 12 More than 12
Backwash Longer 8 10 12
Regenerate 45 60 75 60 70 80
Backwash Longer 8 10 12 12 14 16
Rinse 468579
Total365 86 107 77 91 105
Cycle time
in Minutes
Table 3
Backwash Longer Length Softener
Cycle Times in Minutes
When set up as a softener the backwash and rinse cycles automatically increase with increasing salt dosage. Backwashes can
be set to be NORMAL or LONGER. The option selected will apply to all backwashes. Tables 2 and 3 show the length of the
cycles when the valve is set up as a softener.

Page 6WS1 & 1.25 Manual
4 Total time does not include ll time, which is dependent upon the amount of ll needed. When in the ll mode the system is
providing treated water.
5See Installer Display Settings Step 3I, OEM Softener Setup Step 6S and OEM Filter Setup Step 5F for explanations of Day
Override and Gallon Capacity.
The control valve with a water meter can be set for Demand Initiated Regeneration (DIR) only, Time Clock operation only
or DIR and Time Clock which ever comes rst, depending upon what settings are selected for Day Override and Gallon
Capacity.5See Table 7.
If a control valve does not contain a meter, the valve can only act as a time clock, and day override should be set to any
number and gallon capacity should be set to off.
WS1 & WS1.25 Downflow
Regenerant Refill After Rinse
WS1 & WS1.25 Downflow
Regenerant Prefill
WS1 & WS1.25
No Regeneration
1st Cycle: Backwash
2nd Cycle: Regenerate
3rd Cycle: Second Backwash*
4th Cycle: Rinse
5th Cycle: Fill
6th Cycle: Service
1st Cycle: Fill
2nd Cycle: Backwash
3rd Cycle: Regenerate
4th Cycle: Second Backwash*
5th Cycle: Rinse
6th Cycle: Service
1st Cycle: Backwash
2nd Cycle: Rinse
3rd Cycle: Second Backwash*
4th Cycle: Second Rinse**
5th Cycle: Service
Table 4
Regeneration Cycles Filtering
*Second backwash is optional
**Second rinse only occurs if Second Backwash option is selected.
Table 5
Regenerating Filter
Cycle Times in Minutes
WS1 & WS1.25 Single Backwash WS1 & WS1.25 Double Backwash
Normal Longer Normal Longer
Backwash 14 16 8 12
Regenerate 60 60 60 60
2nd Backwash 10 12
Rinse 8 10 8 10
Total482 86 86 94
Table 6
Non-Regenerating Filter
Cycle Times in Minutes
WS1 & WS1.25 Single Backwash WS1 & WS1.25 Double Backwash
Normal Longer Normal Longer
Backwash 14 16 8 12
Rinse 8 10 6 6
2nd Backwash 10 12
2nd Rinse 810
Total 22 26 32 40

WS1 & 1.25 Manual Page 7
For DIR Softeners, there are two options for setting the Gallons Capacity. The Gallons Capacity is automatically calculated if
set to AUTO. Reserve Capacity is automatically estimated based on water usage if AUTO is used. The other option is to set the
Gallons Capacity to a specic number. If a specic number is set, reserve capacity is zero, unless the value is manually set (i.e. the
manufacturer intentionally sets the gallon capacity number below the calculated capacity of the system).
The WS1 & WS1.25 control valves can also be set to regenerate immediately or at the next regeneration time by changing the
Regeneration Time Option. There are three choices for settings:
1. “NORMAL” means regeneration will occur at the preset regeneration time.
2. “on 0” means regeneration will occur when the gallons capacity reaches zero.
3. “NORMAL + on 0” means the regeneration will occur at the preset regeneration time unless the gallons capacity reaches zero.
If the gallons capacity reaches zero the regeneration will begin 10 minutes after no water usage.
The user can initiate manual regeneration. The user has the option to request the manual regeneration at the delayed regeneration
time or to have the regeneration occur immediately:
1. Press and release REGEN. “Regen Today” will ash on the display and the regeneration will occur at the delayed regeneration
time. The user can cancel the request by pressing and releasing REGEN. This method of manually initiating regeneration is not
allowed when the system is set to “on 0”, i.e. to immediately regenerate when the gallon capacity reaches zero.
2. Pressing and holding REGEN for approximately 3 seconds will immediately start the regeneration. The user cannot cancel this
request, except by resetting the control by pressing NEXT and REGEN simultaneously for 3 seconds.
A unique feature of this control valve is the ability to display actual water usage for the last 63 days. The values are initially stored as
“----”. This means the value is unknown. As days pass values are stored as “0” for no ow or the actual number of gallons. The
counting of the gallons starts at the regeneration time. If no regeneration time can be set (i.e. when the valve is set for immediate
regeneration) the counting of gallons starts at 12 a.m. Day 1 is yesterday, day 2 the day before yesterday, etc.
Another unique feature is that the valve automatically calculates a reserve capacity when set up as a softener with “Gallons
Capacity” set to “AUTO” and the “Regeneration Time Option” set to “Normal” or “Normal + on 0”. The actual reserve capacity
is compared to the gallons capacity remaining immediately prior to the preset regeneration time. A regeneration will occur if the
actual reserve capacity is less than the gallons capacity remaining. The actual reserve capacity is calculated by using the estimated
reserve capacity and adjusting it up or down for actual usage.
The estimated reserve capacity for a given day of the week is the maximum value stored for the last three non-trivial water usages
(i.e. more than 20 gallons/day) in seven day intervals.
6Day Override and Gallon Capacity cannot be set to “oFF” at the same time.
Table 7
DIR/Time Clock Options
DIR Time
Clock Reserve Capacity Softener
Filter Settings6
Regenerant Backwash
Only
Day
Override
Gallon
Capacity
Yes Automatically Calculated Yes Off Auto
Yes If desired enter a value less
than estimated capacity Yes Ye s Yes Off Any
Number
Yes Yes Automatically Calculated Yes Any
Number Auto
Yes Yes If desired enter a value less
than estimated capacity Yes Yes Yes Any
Number
Any
Number
Yes None Yes Yes Yes Any
Number Off

Page 8WS1 & 1.25 Manual
OEM General Instructions
The control valve offers multiple procedures that allow the valve to be modied to suit the needs of the installation. These
procedures are:
OEM Softener Setup
OEM Filter Setup
Installer Displays & Settings
User Displays & Settings
Diagnostics
Valve History
These procedures can be accessed in any order. Details on each of the procedures are provided on the following pages.
At the discretion of the manufacturer, the eld technician can access all settings. To “lock out” access to diagnostic and valve
history displays and modications to settings except hardness, day override, time of regeneration and time of day by anyone
but the manufacturer, press ▼, NEXT, ▲, and SET CLOCK in sequence after settings are made. To “unlock”, so other
displays can be viewed and changes can be made, press ▼, NEXT, ▲, and SET CLOCK in sequence.
When in operation normal user displays such as time of day, gallons remaining or days remaining before regeneration are
shown. When stepping through a procedure, if no buttons are pressed within ve minutes the display returns to a normal user
display. Any changes made prior to the ve minute time out are incorporated.
To quickly exit OEM Softener Setup, OEM Filter Setup, Installer Display Settings, Diagnostics or Valve History press SET
CLOCK. Any changes made prior to the exit are incorporated.
When desired all information in Diagnostics may be reset to zero when the valve is moved to a new location. To reset to zero,
press NEXT and ▼simultaneously to go to the Service/OEM 1 screen, and release. Press ▲and ▼simultaneously to reset
diagnostic values to zero. Screen will return to User Display.
Sometimes it is desirable to have the valve initiate and complete two regenerations within 24 hours and then return to
the preset regeneration procedure. It is possible to do a double regeneration if the control valve is set to “NORMAL” or
“NORMAL + on 0” in Step 9S or Step 7F. To do a double regeneration:
1. Press REGEN once. REGEN TODAY will ash on the display.
2. Press and hold REGEN for three seconds until the valve regeneration initiates.
Once the valve has completed the immediate regeneration, the valve will regenerate one more time at the preset regeneration
time.

WS1 & 1.25 Manual Page 9
OEM Softener System Setup Quick Reference
This is a quick reference setup procedure. See OEM Softener System Setup Detail for
more information on available settings.
STEP 1S – Press NEXT and ▼simultaneously for 3 seconds. If screen in step 2S does
not appear in 5 seconds the lock on the valve is activated. To unlock press ▼, NEXT,
▲, and SET CLOCK in sequence, then press NEXT and ▼simultaneously for 3
seconds.
STEP 2S – Choose Softening using ▼ or ▲. Press NEXT to go to Step 3S. Press
REGEN to exit OEM Softener System Setup.
STEP 3S – Enter the ion exchange capacity in grains of hardness as
calcium carbonate for the system based on test data using ▼ or ▲.
Press NEXT to go to Step 4S. Press REGEN to return to previous
step.
STEP 4S – Enter the pounds of salt per regeneration using ▼ or ▲.
Press NEXT to go to Step 5S. Press REGEN to return to previous
step.
STEP 5S – Backwash: Select “NORMAL” or “LONGER” using ▼ or ▲. See Tables
2 or 3 for backwash times. Press NEXT to go to Step 6S. Press REGEN to return to
previous step.
STEP 6S – Set Gallons Capacity using ▼ or ▲:
• “AUTO” (reserve capacity automatically estimated and gallons capacity
automatically calculated from grains capacity and water hardness);
• “oFF” (regeneration based on day override); or
• number of gallons (20 to 50,000).
See Setting Options Table for more detail. Press NEXT to go to Step 7S. Press REGEN
to return to previous step.
STEP 7S – Set Rell option using ▼ or ▲:
• “PoST” to rell the brine tank after the nal rinse; or
• “PrE” to rell the brine tank two hours before the regeneration time set.
Press NEXT to go to Step 8S. Press REGEN to return to previous step.
STEP 8S – Set regenerant downow or upow using ▼ or ▲:
•“dn” if the regenerant is to ow downward through the media; or
•“UP” if the regenerant is to ow upward through the media.
Prior to selecting a regenerant flow direction, verify the correct valve body, main piston,
regenerant piston, and stack are being used, and that the injector or injector plug(s) are in
the correct locations. See Valve Body Compliance Table in WS1 & WS1.25 Drawings and
Service Manual.
Press NEXT to go to Step 9S. Press REGEN to return to previous step.
STEP 9S – Set Regeneration Time Option using ▼ or ▲:
• “NORMAL” means regeneration will occur at the preset time;
• “on 0” means regeneration will occur immediately when the gallons capacity
reaches 0 (zero); or
• “NORMAL + on 0” means regeneration will occur at one of the following:
• the preset time when the gallons capacity falls below the reserve or the
specied number of days between regenerations is reached whichever comes
rst; or
• after 10 minutes of no water usage when the gallon capacity reaches 0 (zero).
See Setting Options Table for more detail. Press NEXT to exit OEM Softener System
Setup. Press REGEN to return to previous step.
RETURN TO
NORMAL MODE
STEP 3S
STEP 2S
STEP 1S
STEP 4S
STEP 5S
STEP 6S
STEP 7S
STEP 8S
STEP 9S

Page 10 WS1 & 1.25 Manual
7 Reserve capacity estimate is based on history of water usage.
Setting Options Table
Volume
Capacity
Regeneration
Time Option
Day
Override Result7
AUTO NORMAL oFF
Reserve capacity automatically estimated.
Regeneration occurs when volume capacity falls below the reserve
capacity at the next Regen Set Time
AUTO NORMAL Any
number
Reserve capacity automatically estimated.
Regeneration occurs at the next Regen Set Time when volume capacity
falls below the reserve capacity or the specified number of days between
regenerations is reached.
Any
number NORMAL oFF
Reserve capacity not automatically estimated.
Regeneration occurs at the next Regen Set Time when volume
capacity reaches 0.
oFF NORMAL Any
number
Reserve capacity not automatically estimated.
Regeneration occurs at the next Regen Set Time when the specified
number of days between regenerations is reached.
Any
number NORMAL Any
number
Reserve capacity not automatically estimated.
Regeneration occurs at the next Regen Set Time when volume
capacity reaches 0 or the specified number of days between
regenerations is reached.
AUTO On 0 oFF
Reserve capacity not automatically estimated.
Regeneration occurs immediately when volume capacity reaches 0.
Time of regeneration will not be allowed to be set because regeneration
will always occur when volume capacity reaches 0.
Any
number On 0 oFF
Reserve capacity not automatically estimated.
Regeneration occurs immediately when volume capacity reaches 0.
Time of regeneration will not be allowed to be set because regeneration
will always occur on 0.
AUTO NORMAL + on 0 oFF
Reserve capacity automatically estimated.
Regeneration occurs when volume capacity falls below the reserve
capacity at the next Regen Set Time or regeneration occurs after 10
minutes of no water usage when volume capacity reaches 0.
AUTO NORMAL + on 0 Any
number
Reserve capacity automatically estimated.
Regeneration occurs at the next Regen Set Time when volume capacity
falls below the reserve capacity or the specified number of days between
regenerations is reached or regeneration occurs after 10 minutes of no
water usage when volume capacity reaches 0.
Any
number NORMAL + on 0 Any
number
Reserve capacity not automatically estimated.
Regeneration occurs at the next Regen Set Time when the specified
number of days between regenerations is reached or regeneration occurs
after 10 minutes of no water usage when volume capacity reaches 0.
Filters should only use shaded options.

WS1 & 1.25 Manual Page 11
OEM Filter System Setup Quick Reference
This is a quick reference setup procedure. See OEM Filter System Setup Detail for
more information on available settings.
STEP 1F – Press NEXT and ▼simultaneously for 3 seconds. If screen in step 2F does
not appear in 5 seconds the lock on the valve is activated. To unlock press ▼, NEXT,
▲, and SET CLOCK in sequence, then press NEXT and ▼simultaneously for 3
seconds.
STEP 2F – Choose Filtering using ▼or ▲. Press NEXT to go to step 3F. Press
REGEN to exit OEM Filter System Setup.
STEP 3F – Enter “oFF” if regenerant is not used (i.e. backwash only) or enter the rell
volume (in gallons) using ▼or ▲. Prior to selecting oFF or regenerant volume, verify the
correct valve body, main piston, regenerant piston, and stack are being used, and that the
injector or injector plug(s) are in the correct locations. See Compliance Table in Service
Instructions under Injector Cap, Screen, Injector Plug and Injector section and Figure 6.
Press NEXT to go to step 4F. Press REGEN to return to previous step.
STEP 4F – Backwash: Select using ▼or ▲:
• “NORMAL” for one “NORMAL” backwash (14 minutes);
•“NORMAL 2” for two “NORMAL” backwashes (8 minutes each);
•“LONGER” for one “LONGER” backwash (16 minutes); or
•“LONGER 2” for two “LONGER” backwashes (12 minutes each).
See Tables 5 and 6 for additional details. Press NEXT to go to step 5F. Press REGEN
to return to previous step.
STEP 5F – Set Gallons Capacity using ▼or ▲:
•“oFF” (regeneration based on day override); or
•number of gallons (20 to 50,000).
See Setting Options Table for more detail. Press NEXT to go to step 6F. Press REGEN
to return to previous step.
STEP 6F – Set Rell option using ▼or ▲:
•“PoST” to rell the brine tank after the nal rinse; or
• “PrE” to rell the brine tank two hours before the regeneration time set.
Press NEXT to go to step 7F. Press REGEN to return to previous step.
STEP 7F – Set Regeneration Time Option using ▼or ▲:
•“NORMAL” means regeneration will occur at the preset time;
•“on 0” means regeneration will occur immediately when the gallons capacity
reaches 0 (zero); or
•“NORMAL + on 0” means regeneration will occur at one of the following:
• the preset time when the specied number of days between regenerations is
reached; or
• after 10 minutes of no water usage when the gallon capacity reaches 0 (zero).
This display will not appear if Step 5F is set to oFF.
See Setting Options Table for more detail. Press NEXT to exit OEM Filter System
Setup. Press REGEN to return to previous step.
RETURN TO
NORMAL MODE
STEP 1F
STEP 2F
STEP 3F
STEP 4F
STEP 5F
STEP 6F
STEP 7F

Page 12 WS1 & 1.25 Manual
STEP 1I - Press NEXT and ▲simultaneously for 3 seconds.
STEP 2I – Hardness: Set the amount of hardness in grains of hardness as
calcium carbonate per gallon using ▼or ▲. The default is 20 with value
ranges from 1 to 150 in 1 grain increments. Note: The grains per gallon can
be increased if soluble iron needs to be reduced. This display will show “–
nA–” if “FILTER” is selected in Step 2F or if ‘AUTO’ is not selected in Step
6S. Press NEXT to go to step 3I. Press REGEN to exit Installer Display
Settings.
STEP 3I – Day Override: When gallon capacity is set to off, Day Override sets the
number of days between regenerations. When gallon capacity is set to AUTO or to
a number, Day Override sets the maximum number of days between regenerations.
If value set to “oFF” regeneration initiation is based solely on gallons used. If value
is set as a number (allowable range from 1 to 28) a regeneration initiation will be
called for on that day even if sufcient number of gallons were not used to call for a
regeneration. Set Day Override using ▼or ▲:
• number of days between regeneration (1 to 28); or
• “oFF”.
See Setting Options Table for more detail on setup. Press NEXT to go to step 4I. Press
REGEN to return to previous step.
STEP 4I – Next Regeneration Time (hour): Set the hour of day for regeneration using
▼or ▲. AM/PM toggles after 12. The default time is 2:00 a.m. This display will show
“REGEN on 0 GAL” if “on 0” is selected in Step 9S or Step 7F. Press NEXT to go to
step 5I. Press REGEN to return to previous step.
STEP 5I – Next Regeneration Time (minutes): Set the minutes of day for regeneration
using ▼or ▲. This display will not be shown if “on 0” is selected in Step 9S or Step
7F. Press NEXT to exit Installer Display Settings. Press REGEN to return to previous
step.
To initiate a manual regeneration immediately, press and hold REGEN for three
seconds. The system will begin to regenerate immediately. The control valve may be
stepped through the various regeneration cycles by pressing REGEN.
General Operation
When the system is operating one of two displays will
be shown. Pressing NEXT will alternate between the
displays. One of the displays is always the current time
of day. The second display is one of the following: days
remaining or gallons remaining. Days remaining is the
number of days left before the system goes through a
regeneration cycle. Capacity remaining is the number
of gallons that will be treated before the system goes
through a regeneration cycle. The user can scroll
between the displays as desired.
If the system has called for a regeneration that will
occur at the preset time of regeneration, the words
REGEN TODAY will appear on the display.
When water is being treated (i.e. water is owing
through the system) the word “Softening” or
“Filtering” ashes on the display if a water meter is
installed.
User Display Settings
RETURN TO
NORMAL MODE
OR
REGEN TODAY
will be displayed if
a regeneration is
expected “Tonight.”
STEP 1I
STEP 2I
STEP 3I
STEP 4I
STEP 5I
Installer Display Settings

WS1 & 1.25 Manual Page 13
Regeneration Mode
Typically a system is set to regenerate at a time of low water usage. An example of a time
with low water usage is when a household is asleep. If there is a demand for water when
the system is regenerating, untreated water will be used.
When the system begins to regenerate, the display will change to include information about the step of the regeneration
process and the time remaining for that step to be completed. The system runs through the steps automatically and will reset
itself to provide treated water when the regeneration has been completed.
Manual Regeneration
Sometimes there is a need to regenerate the system sooner
than when the system calls for it, usually referred to as manual
regeneration. There may be a period of heavy water usage
because of guests or a heavy laundry day.
To initiate a manual regeneration at the preset delayed
regeneration time, when the regeneration time option is set to “NORMAL” or “NORMAL
+ on 0”, press and release REGEN. The words “REGEN TODAY” will ash on the
display to indicate that the system will regenerate at the preset delayed regeneration time. If
you pressed REGEN in error, pressing the button again will cancel the request. Note: If the regeneration time option is set to
“on 0” there is no set delayed regeneration time so “REGEN TODAY” will not activate if REGEN is pressed.
To initiate a manual regeneration immediately, press and hold REGEN for three seconds. The system will begin to regenerate
immediately. The request cannot be cancelled.
Note: For softeners, if brine tank does not contain salt, ll with salt and wait at least two hours before regenerating.
Power Loss
If the power goes out, the system will keep time for up to 8 hours or until the battery is depleted. If a power outage of more
than 8 hours occurs, the time of day will ash on and off which indicates the time of day should be reset. The system will
remember the rest. If a power outage lasts less than 8 hours and the time of day ashes on and off, the non rechargeable
battery should be replaced.
Error Message
If the word “ERROR” and a number are alternately ashing on the display
contact the OEM for help. This indicates that the valve was not able to function
properly.
Set Time of Day
The user can also set the time of day. Time of day should only need to be set after power
outages lasting more than 8 hours, if the battery has been depleted and a power outage
occurs, or when daylight saving time begins or ends. If a power outage lasting more than
8 hours occurs, the time of day will ash on and off which indicates the time of day
should be reset. If a power outage lasts less than 8 hours and the time of day ashes on
and off, the time of day should be reset and the battery replaced.
STEP 1U – Press SET CLOCK.
STEP 2U - Current Time (hour): Set the hour of the day using ▼or ▲. AM/PM toggles
after 12. Press NEXT to go to step 3U.
STEP 3U - Current Time (minutes): Set the minutes of the day using ▼or ▲. Press
NEXT to exit Set Clock. Press REGEN to return to previous step.
STEP 1U
STEP 2U
STEP 3U
REGEN TODAY will
Flash if a regeneration
is expected “Tonight.”

Page 14 WS1 & 1.25 Manual
Diagnostics
STEP 1D – Press ▼or ▲simultaneously for three seconds. If screen in step 2D does not
appear in 5 seconds the lock on the valve is activated. To unlock press ▼, NEXT, ▲, and
SET CLOCK in sequence, then press NEXT and ▼simultaneously for 3 seconds.
STEP 2D
– Days, since last regeneration: This display shows the days since the last
regeneration occurred. Press NEXT to go to Step 3D. Press REGEN to exit Diagnostics.
STEP 3D – Gallons, since last regeneration: This display shows the number of gallons that
have been treated since the last regeneration. This display will equal zero if a water meter is
not installed. Press NEXT to go to Step 4D. Press REGEN to return to previous step.
STEP 4D – Gallons, reserve capacity used for last 7 days: If the valve is set up as a softener,
a meter is installed and Set Gallons Capacity is set to “Auto,” this display shows 0 day
(for today) and ashes the reserve capacity. Pressing ▲will show day 1 (which would be
yesterday) and ashes the reserve capacity used. Pressing ▲again
will show day 2 (the day before yesterday) and the
reserve capacity. Keep pressing ▲to show the gallons
for days 3, 4, 5 and 6. ▼can be pressed to move
backwards in the day series. Press NEXT at any time
to go to Step 5D. Press REGEN to return to previous
step.
STEP 5D - Gallons, 63 day usage history: This display
shows day 1 (for yesterday) and ashes the number of
gallons treated yesterday. Pressing ▲will show day 2
(which would be the day before yesterday) and ashes
the number of gallons treated on that day. Continue
to press ▲to show the maximum number of gallons
treated for the last 63 days. This display will show dashes if a water meter is not installed.
Press NEXT at any time to go to Step 6D. Press REGEN to return to previous step.
STEP 6D – Flow rate, current: The ow rate in gallons per minute will be displayed. If ow
stops the value will fall to zero in a few seconds. This display will equal zero if a water meter
is not installed. Press NEXT to go to Step 7D. Press REGEN to return to previous step.
STEP 7D – Flow rate, maximum last seven days: The maximum ow rate in gallons per
minute that occurred in the last seven days will be displayed. This display will equal zero
if a water meter is not installed. Press NEXT to go to Step 8D. Press REGEN to return to
previous step.
STEP 8D – Gallons, total used since last reset: The total number of gallons used since last
reset will be displayed. This display will equal zero if a water meter is not installed. Press
NEXT to go to Step 9D. Press REGEN to return to previous step.
STEP 9D – Days, total number since last reset: The total number of days the control valve
has been in service since last reset will be displayed. Press NEXT to go to Step 10D. Press
REGEN to return to previous step.
STEP 10D – Regenerations, total number since last reset: The total number of regenerations
that have occurred since last reset will be displayed. Press NEXT to exit Diagnostics. Press
REGEN to return to previous step.
When desired, all information in Diagnostics may be reset to zero when the valve is installed in
a new location. To reset to zero, press NEXT and ▼ simultaneously to go to the Service/OEM
screen, and release. Press ▼and ▲ simultaneously to reset diagnostic values to zero. Screen
will return to user display.
RETURN TO
NORMAL MODE
STEP 1D
STEP 2D
STEP 3D
STEP 4D
STEP 5D
STEP 6D
STEP 7D
STEP 8D
STEP 9D
STEP 10D

WS1 & 1.25 Manual Page 15
8 Values in steps 3VH through 7VH cannot be reset.
RETURN TO
NORMAL MODE
STEP 1VH
STEP 1VH
STEP 2VH
STEP 3VH
STEP 4VH
STEP 5VH
STEP 6VH
STEP 7VH
Valve History
STEP 1VH – Press ▲and ▼simultaneously for three seconds and release. Then
press ▲and ▼simultaneously and release. If screen in step 2VH does not appear in
5 seconds the lock on the valve is activated. To unlock press ▼, NEXT, ▲, and SET
CLOCK in sequence, then press ▲and ▼simultaneously for 3 seconds and release.
Then press ▲and ▼simultaneously and release.
STEP 2VH – Software Version: This display shows the software version of the valve.
Press NEXT to go to Step 3VH. Press REGEN to exit Valve History.
STEP 3VH8
– Flow rate, maximum since startup: This display shows the maximum
ow rate in gallons per minute that has occurred since startup. This display will equal
zero if a water meter is not installed. Press NEXT to go to Step 4VH. Press REGEN
to return to previous step.
STEP 4VH – Gallons, total used since start-up: This display shows the total gallons
treated since startup. This display will equal zero if a water meter is not installed. Press
NEXT to go to Step 5VH. Press REGEN to return to previous step.
STEP 5VH – Days, total since start-up: This display shows the total days since startup.
Press NEXT to go to Step 6VH. Press REGEN to return to previous step.
STEP 6VH – Regenerations, total number since start-up: This display shows the total
number of regenerations that have occurred since startup. Press NEXT to go to Step
7VH. Press REGEN to return to previous step.
STEP 7VH – Error Log: This display shows a history of the last 10 errors generated
by the control during operation. Press ▲or ▼to review each error recorded. Press
NEXT to exit Valve History. Press REGEN to return to previous step.

Page 16 WS1 & 1.25 Manual
Front Cover and Drive Assembly
* Drawing number parts 2, 3, 5 and 6 may be purchased as a complete assembly, part V3002.
Drawing No. Order No. Description Quantity
1 V3175-01 WS1 Front Cover ASY 1
2 V3107-01 WS1 Motor 1
3 V3106-01 WS1 Drive Bracket&Spring Clip 1
4 V3108-10BOARD WS1 PCB XMEGA REPL 1
5 V3110 WS1 Drive Reducing Gear 12x36 3
6 V3109 WS1 Drive Gear Cover 1
V3002 WS1 Drive ASY *
Not Shown
V3186 WS1 AC ADAPTER 120V-12V
1
V3186EU WS1 AC ADAPTER 220-240V-12V EU
V3186UK WS1 AC ADAPTER 220-240V-12V UK
V3186-01 WS1 AC ADAPTER CORD ONLY
Battery Fully Seated
When replacing the battery, align
positives and push down to fully seat. Correct
Battery
Orientation
Battery replacement is
3 volt lithium coin cell
type 2032.
AC Adapter U.S. International
Supply Voltage 120 V AC 230V AC
Supply Frequency 60 Hz 50 Hz
Output Voltage 12 V AC 12 V AC
Output Current 500 mA 500 mA
4
6
3
2
1
5

WS1 & 1.25 Manual Page 17

Page 18 WS1 & 1.25 Manual

WS1 & 1.25 Manual Page 19

Page 20 WS1 & 1.25 Manual
Form No. V3115 – 1/27/2017
Revision History:
U.S. Patents: 6,402,944 • 6,444,127 • 6,776,901
5/27/2014
PAGE 13:
New regeneration cycle status display, new error display
PAGE 15:
Step 7VH Error Log: new display
PAGE 16:
V3108-10BOARD WS1/125 PCB XMEGA REPLACE
New board drawing
9/15/2015
PAGE 16:
Drive Bracket & Spring Clip on drawing was labeled incorrectly - changed from 6 to 3.
3/4/2016
PAGE 17:
1 V3005-02 WS1 Spacer Stack Assembly 1
PAGE 18:
1a V3430-01 WS1.5 Spacer Stack Assembly 1
1b V3005-02 WS1 Spacer Stack Assembly
6/20/2016
Removed Drive Assembly and 1”/1.25” identication drawings - see Service Manual
PAGE 8:
Removed: The one exception is current ow rate display under the diagnostic procedure. The current ow rate display has a
30 minute time out feature.
PAGE 14:
Step 6D - Removed: Turn the water on at one or more taps in the building.
PAGE 16:
* Drawing number parts 2, 3, 5 and 6 may be purchased as a complete assembly, part V3002.
7/12/2016
1/27/2017
This manual suits for next models
1
Table of contents
Other Clack Valve Control Unit manuals
Popular Control Unit manuals by other brands

Monacor
Monacor ATT-506PEU operating instructions

Burkert
Burkert 2610 operating instructions

Initiative Engineering
Initiative Engineering F0525FF quick start guide

Dometic
Dometic Optimus i7700 Operation instructions and users manual

Miele professional
Miele professional XKM 3200 WL PLT operating instructions

SMC Networks
SMC Networks VM1000 Series instruction manual