5. Operating instructions
5.1) Usage
Valve materials have to be fully compatible with the fluid circulating through the valve.
Otherwise, valve could be seriously damaged.
The main purpose of pressure reducing valves is to reduce the fluid pressure to optimum
operating values, constantly below the maximum permitted vales so as not to damage
installations after the reducing valve.
The pressure reducing valves is recommended for use in liquid or gas with inlet
pressures no higher than 25 bar (not suitable for steam).
The pressure reducing valve is factory regulated with an outlet pressure value of 3 bar.
5.2) Setting instructions
The pressure reducer has been preset at 3 bar of outlet pressure. If is necessary to
modify it, follow next instructions:
a. Check that hydraulic circuit is completely full and close all devices (valves, taps,
etc.).
b. Loosen the nut (part.15).
c. To reduce the outlet pressure, loosen the adjusting screw (part.16) rotating
counterclockwise.
d. To increase the outlet pressure, tighten the adjusting screw (part.16) rotating
clockwise.
e. In order to simplify this operation, connect a pressure gauge replacing the plug
(part.4), which indicates outlet pressure.
f. When you get the desired outlet, pressure tighten the nut (part 15).
5.3) Cavitation Chart
Advice: If you want to reduce the outlet pressure with respect to the inlet pressure more
than the recommended by the diagram cavitation (zona3), we recommend installing a
second pressure reducing valve in serially to divide the pressure drop in two separate
falls within the zona3 (optimum operating area).