manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Cleaveland Controls
  6. •
  7. Switch
  8. •
  9. Cleaveland Controls RFS-4150 User manual

Cleaveland Controls RFS-4150 User manual

·Cleveland Controls
Di-".ision~of
UniControl Inc.
Model·
RFS-4150
/
AIR PRESSURE SENSING SWITCH WITH ADJUSTABLESET POINT
APPLICATION
•'
Model RFS-4150 is a general purpose prov-
ing switch designed for HVAC and Energy
Management-applicatipns. This switch can
be used to sense positive, negative,
or
dif-
ferential air pressure.
GENERAL DESCRIPTION &
OPERATION
The
plated
hotJsiog_contains_a__dlapbLagm~<L~
__
-------,
calibration spring, and a snap-acting switch.
The sample line connections located on
each side
of
the diaphragm accept
o/is",
W',
and
7'\s"
flexible tubing. Various electrical
connections are available.
MOUNTING {FIG. 1)
Select a mounting location which is free
from vibration. The Model RFS-4150 must
be mounted with the diaphragm
in
any verti-
cal plane
in
order to maintain the specified
operating set point. Avoid mounting with the
sample line connections
in
the "up" position.
The standard model
is
surface~mounted
via
th~
two round holes (0.14" dia.) ortwo
of
the
fourslots
(o/is"
wide) on the zinc-plated strap
bracket.The mounting holes and slots are
3-Va"
apart. Custom mounting configurations
are available.
Figure
1:
Mount with the diaphragm
in
any
vertical plane.
-
-~,-~
·~
\1)
AIR SAMPLING CONNECTION
{FIG. 2)
Tri-barbed sample line connectors suitable
to
accept flexible tubing are situated on either
side
of
the diaphragm as shown
in
Figure
2.
The tri-barbed connectors accept
·o/is",
Y..",
and
o/;s"
ID
flexible tubing. For sample
lines up to 10 feet
in
length,
11s"
ID
tubing
is
acceptable. For lines up to 20 feet, use
Y.."
ID tubing.
Locate the sampling probe a minimum
of
Figure 2
INLET
Positive Only
LowerNegative
HigherPositive
NLETL
Negative Only
HigherNegative
LowerPositive
--
-1;5-ductl:liameters-downstreamiromth.::.-.:H.·--+t=lctu.r:e
~---
---
------+
source. Install the sampling probe as close
to the center
of
the airstream as possible.
Refer to Figure 2 to identify the high pres-
sure inlet (H)
and
the low pressure inlet
(L).
Selectone ofthe five application options
listed below, and connect the sample lines
as recommended.
HIGH
PRESSURE
LOW
PRESSURE
0
N.C.
N.O.
Positive
Pressure
Only:
Connect
the
sample line to inlet
H;
inlet L remains open
to the atmosphere. ·
Negative
Pressure
Only:
Connect
the
sample line to inlet
L;
inlefH
remains open
to the atmosphere. · ·
Two Negative Samples: Connectthe higher
negative sample
to
inletL. Connectthe lower
negative sample to inlet'
H. \
Two Positive Samples: Connectthe higher
' positive sampleto inlet
~
Connectthe lower
positive sample to inlet
L.
\
One·Positive and One Negative Sample:
Connectthe positive sampleto inlet
H.
Con-
nect,the negative sample to inlet
L,.
Figure 4
To
prove
excessive
air
flow
or
pressure:
...,.NO
ALARM
c
e-_____-
~--------~~N~~c+-C-0-N-TROL
To
prove
insufficient
air
flow
or
pressure:
JlO
CONTROL
c
0--___:__""
.......
Q--1----
~--------~N~C
ALARM
4.098(104)
ELECTRICAL CONNECTIONS
(FIGURES 3 &
4}
Beforepressure is applied to the diaphragm,
the switch contacts will be in the normally
closed (NC) position. Wire control and alarm
functions
as
shown
in
Figure 4.
FIELD ADJUSTMENT
The adjustment range
of
an RFS-4150 Air-
Switch is 0.15±0.02" we to 5.0"wc.
To
adjust the set point,
t~rn
the adjusting
screw
counterclockwise .until motion
has
stopped. Next, turn the adjusting screw 5
complete turns clockwis'll·to
engage
the
spring.
;•
From this
p~t,
the nexteight turns will be
used fortheiactual calibratibn. Each full turn
represents
a~proximate'iy
0.61" we.
Please note:
To
properly calibrate an air
switch, a digital manometer
or
other mea-
suring device should be used to confirm the
actual set point. ' ·
1-----
.3.066(78)----1
Reference Dimensions in Inches (Millimeters)

Popular Switch manuals by other brands

VXI SM8000 Series user manual

VXI

VXI SM8000 Series user manual

SMART Titanium MS 5/6 ES manual

SMART

SMART Titanium MS 5/6 ES manual

CPLUS DESKTOP STATION C01 Guide

CPLUS

CPLUS DESKTOP STATION C01 Guide

Painless Performance 50340 installation instructions

Painless Performance

Painless Performance 50340 installation instructions

TRENDnet TFC-1600MM user guide

TRENDnet

TRENDnet TFC-1600MM user guide

CAMBRIONIX ThunderSync3-C10 user manual

CAMBRIONIX

CAMBRIONIX ThunderSync3-C10 user manual

TP-Link TL-SG2200 installation guide

TP-Link

TP-Link TL-SG2200 installation guide

WiQuest WQST110RDK-HUB-USB4 Evaluation guide

WiQuest

WiQuest WQST110RDK-HUB-USB4 Evaluation guide

Ham DinSwitch quick start guide

Ham

Ham DinSwitch quick start guide

Clas Ohlson HD4201 user manual

Clas Ohlson

Clas Ohlson HD4201 user manual

HP StorageWorks SN6000 Installation and reference guide

HP

HP StorageWorks SN6000 Installation and reference guide

Honeywell 14CE101 installation instructions

Honeywell

Honeywell 14CE101 installation instructions

Travel Vision DDS Installation & user manual

Travel Vision

Travel Vision DDS Installation & user manual

RLE Technologies F1000 user guide

RLE Technologies

RLE Technologies F1000 user guide

KTI Networks KS-280 installation guide

KTI Networks

KTI Networks KS-280 installation guide

Crestron HD-MD6X2-4K-E Do guide

Crestron

Crestron HD-MD6X2-4K-E Do guide

Eircom Advantage 2000 System manual

Eircom

Eircom Advantage 2000 System manual

Lantech LES-2400-RPS user manual

Lantech

Lantech LES-2400-RPS user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.