Clenergy TNK-10000-LV-A1 User manual

TNK-10000-LV-A1
User Manual
Ver. 1.2 / Last Updated - Aug 2023

User Manual / TNK-10000LV-A1
2
Index
- Index -
Statement of Law
Safety Precautions
Preface
Introduction
- Brief Introduction
- Product Properties
- Product Identity Definition
Product Specification
- Size and Weight / Performance Parameter
- Interface Definition
- Battery Management System(BMS)
Voltage Protection / Current Protection
Temperature Protection / Other Protections
Installation and Configuration
- Preparations for Installation
Environmental Requirements
Tools and Data
Technical Preparation
Unpacking Inspection
Engineering Coordination
- Equipment Installation
Floor Installation
Wall Mounted Installation
Electrical Installation
Battery Module DIP Switch Definition and Description
Battery Parameter Settings on the Inverter
Register on the Website after Installation
Use, Maintenance and Troubleshooting
- Battery System Usage and Operation Instructions
- Alarm Description and Processing
- Analysis and Treatment of Common Faults
3
3 - 4
5
6 - 7
6
6
7
8 - 12
8
9 - 10
11 - 12
11
12
13 - 28
13 - 16
13
14
14
15
16
17 - 28
17 -18
18 -19
20 - 24
25 - 27
28
28
29 - 31
29
29 - 30
31

3
User Manual / TNK-10000LV-A1
Statement of Law
TNK is an energy storage solution designed in Australia and manufactured by Xiamen Well Energy
Technology Co., Ltd. Clenergy Technologies is the majority shareholder in this joint venture – Xiamen
Well Energy.
Xiamen Well Energy Technology Co., Ltd. owns the copyright of the document.
No part of this document may be excerpted, reproduced, translated, annotated or duplicated in any
form or by any means without the prior written permission of Xiamen Well Energy Technology Co.,
Ltd.
This product complies with the design requirements of environmental protection and personal safe-
ty. The storage, use and disposal of this product should be in accordance with the product manual,
relevant contract or relevant laws and regulations.
Customers can check for product or technology updates on Xiamen Well Energy Technology Co.,
Ltd.’s website.
The product may be subject to modification without prior notice to the user.
Safety Precautions
To prevent accidental fires or explosions, do not immerse the battery in water or expose it to exces-
sive heat.
Please connect wires correctly during installation. Do not reverse the polarity.
Do not connect the positive (+) or negative (–) terminals to any conductive material such as a wire to
prevent short circuits.
Do not subject the battery to any damage, such as piercing it with sharp objects, striking it with
heavy objects or trampling it.
Turn off the power completely when removing any device from the system or rewiring the system to
reduce the risk of electric shock.
In the unlikely event of fire danger on the battery, use a dry powder fire extinguisher. Using a liquid
fire extinguisher may lead to an explosion.
For your safety, please do not arbitrarily dismantle or disassemble any component. The maintenance
must be performed by authorised technical personnel or our company’s technical support team.
Failure to do so will result in malfunction and will void the warranty.
Do not dispose of the battery in household waste. To reduce environmental impacts, bring your
battery to a certified recycling depot at the end of its life.
Warning
- Statement of Law / Safety Precautions -

User Manual / TNK-10000LV-A1
4
Caution
Our product has been inspected before shipment. Please contact us if you find
components missing, damaged or abnormal phenomena, such as a bulging outer case.
For safety reasons, the product should be grounded properly before use.
To achieve a proper installation and the best outcome for the system, please ensure that
the parameters of the connected devices are compatible.
Do not mix different battery brands, types and models. Never use old and new batteries
together.
Working environment and storage methods could impact the product’s lifespan.
To ensure proper use of the battery, please comply with the operating environment
requirements in the instructions.
For long-term storage, recharge the battery every six months. The charged state must
exceed 80% of the battery capacity.
Please charge the battery within 48 hours upon full discharge or when the
over-discharging protection mode is activated.
Formula of theoretical standby time: T=C/I (Units must be specified, eg., C is the battery
capacity in kWh, I is the total current of the internal loads in A).
If the data-plate or production information sticker is damaged or invalid please contact
you local Well Energy authorised distributor or service center.
The Inverters BMS internal DIP switches are used to assign BMS address on CAN, before
opening unit to set DIP switches please contact Well energy’s support centre and provide
the product ID to receive authorisation to do so.
No other operations related to opening the unit are allowed except for performing DIP
switch settings
- Safety Precautions -

5
User Manual / TNK-10000LV-A1
Preface
Only trained and qualified professionals are allowed to install, operate, and maintain the device.
Please comply with local safety regulations and operational rules during installation, operation and
maintenance to avoid unexpected injury or device damage.
The safety declaration in the manual is supplementary to your local safety regulations.
The manufacturer does not undertake any responsibility for device operations violating general
safety requirements and safety standards.
Manual Declaration
TNK-10000-LV-A1 Lithium Iron Phosphate(LiFePO4) Battery is an external battery product used to store
electricity for residential use. TNK battery can be charged through an inverter by either grid power or
solar power. The stored energy could then be used to supply electricity to the home to reduce grid
usage(maximum self consumption).
TNK-10000-LV-A1 User Manual systematically elaborates on device structure, parameters, basic
procedure, installation methods, operation and maintenance.
Safety Statement
- Preface -

User Manual / TNK-10000LV-A1
6
Introduction
Brief Introduction
TNK-10000-LV-A1 series is equipped with a LiFePO4 battery for residential use. This product with
cutting-edge battery storage technology is developed based on customer needs and market
trends. The purpose is to offer a high-quality product that can supply stable electricity to custom-
ers. The product has a long lifespan and can operate in a wide temperature range environment. Its
compact size allows space-saving and a seamless installation experience.
TNK-10000-LV-A1 series carries our core self-developed battery management system. It can store
energy when the grid is down or PV system is not producing. Several TNK batteries can work
in parallel to form a multi-module system with a larger capacity to meet a longer battery energy
supply time.
Complies with European RoHS, is certified by SGS and employs a non-toxic and
environment-friendly battery.
The Anode material is lithium iron phosphate (LiFePO4) which has high safety performance with a
longer lifespan.
Equipped with a BMS to achieve the best system performance – which possesses protection func-
tions such as over-discharge, over-charge, over-current and abnormal temperature.
Self-management on charging and discharging. Integrated single-core balancing capabilities.
Each modular internal battery is equipped with intelligent diagnosis and design configurations.
Flexible configurations allow multiple batteries used in a paralleled configuration for longer ener-
gy-supplying time.
Self-ventilation with low system noise.
Minimum energy consumption on standby.
No memory effect on battery capacity - it can be charged or discharged shallowly.
Wide range of operating temperature, 0°C ~ +50 °C. At the maximum threshold of +55 °C
- The system can maintain circulation and discharge performance.
Compact size, lightweight and IP65 design for easier installation and maintenance.
Product Properties
TNK-10000-LV-A1 energy storage product is formed by LiFePO4 battery cells that are managed
effectively by its internal battery management system (BMS). The system’s features are as below:
- Introduction -

7
User Manual / TNK-10000LV-A1
Battery Energy Storage System Nameplate
Battery voltage is higher than safe voltage.
Direct contact may cause an electric shock hazard.
Be careful with your actions and be aware of the dangers.
Read the user manual before using.
Do not dispose of this product with general household waste.
Consult your local regulations for proper recycling or disposal instructions.
Do not dispose the battery at will when the battery reaches the end of its lifespan.
It can be used after being recycled by a professional recycling organization.
This battery product meets European directive requirements.
This battery product has passed the TUV certification test.
Product Identity Definition
- Introduction -

User Manual / TNK-10000LV-A1
8
Product Specification
Product Series TNK-10000-LV-A1
Nominal Voltage 51.2 V
Nominal Capacity 200Ah
Dimensions 570 x 190 x 972 mm
Weight 109 kg
IP Rating IP65
Work Voltage Range 44.8 ~ 57.6V
Nominal Energy 10.24 kWh
Nominal Power 5.12 kW
Usable Energy 9.21 kWh
Max Charging Current 105 A
Max Discharge Current 105 A
Size and Weight / Performance Parameters
- Product Specification -

9
User Manual / TNK-10000LV-A1
This section elaborates on the interface functions of the device’s front panel.
Positive
Connector The battery Positive DC connector
1
2
3
4
5
6
7
When the battery is used independently:
The CAN/RS485 socket is connected to the inverter CAN/RS485 interface through
the communication cable.
When the battery is used in parallel:
This CAN/RS485 communication socket is connected to the COM OUT interface
of the next TNK-10000-LV-A1 through communication cable.
The battery Negative DC connector
When the battery is used independently:
This CAN/RS485 socket is not used.
When the battery is used in parallel:
This CAN/RS485 communication socket is connected to the COM IN interface of
another TNK-10000-LV-A1 through communication cable.
(Factory default CAN communication mode)
Press the button to turn on the battery system. When the battery is in a standby
state, such as storage, transportation etc., it has to be turned off by pressing the
power button. The battery system will automatically sleep when the device is
without external load and power for 72 hours. ALM light instruction details are
listed in the table in the table “ALM light instructions” on Page 10.
Circuit Protection
The number of LED lights illuminated shows the batteries state of charge.
Details are in the table “LED status indicators” on Page 10.
COM IN
Negative
Connector
COM OUT
Power
button
DC circuit
breaker
SOC
Interface Definition
- Product Specification -

User Manual / TNK-10000LV-A1
10
ALM light instructions
Blue light on Normal state
Red light on Fault - Discontinue use and contact customer support
Red light flashes Temperature or Voltage out of range - reset device
Red light flashes quickly Fault - Discontinue use and contact customer support
Blue and red lights flash alternately The communication between BMS board and light board
is lost
Blue and red lights flash alternately
and SOC flash
The communication between the light board and the slave
BMS is lost. (This situation only applies to parallel battery
operation.)
LED status indicators
State SOC LED1 LED2 LED3 LED4
Charging
0 ≤ SOC < 25 flash
25 ≤ SOC < 50 on flash
50 ≤ SOC <75 on on flash
75≤ SOC ≤100 on on on flash
Discharging /
Standby
0 ≤ SOC < 25 on
25 ≤ SOC < 50 on on
50 ≤ SOC <75 on on on
75≤ SOC ≤100 on on on on
LED on for 30 seconds
- Product Specification -

11
User Manual / TNK-10000LV-A1
Battery Management System (BMS)
Voltage Protection
Under Voltage Protection
while Discharging
When any battery cell’s voltage or the total voltage is lower
than the rated protection value during discharging, the
over-discharging protection will be activated, and the buzzer
will sound. The battery system will stop supplying power to the
external device. When the voltage of each cell is back to the
rated range, the protection ends.
Over Voltage Protection
while Charging
During the charging stage, the system will stop charging when
the total voltage of the battery pack is higher than the rated
value or the voltage of any single cell reaches the protection
value. When the total voltage of all cells returns to the rated
range, the protection ends.
Current Protection
Over Current Protection
while Charging
When the charge current of any module is higher than 110A,
the over-current protection mode is activated and the current
is limited to 1A. The protection will be deactivated after a rated
delay of 10s. This process will repeat until the current falls below
110A.
Over Current Protection
while Discharging
When the discharge current of any module is higher than
115A, the battery buzzer will sound, and the system will stop
discharging after 15s. When the protection ends, the discharg-
ing will restore in a 60s delay or immediately when a charging
current is present.
The buzzer sound from the alarm function can be deactivated, from the software, resulting in
the system reverting to default factory settings.
- Product Specification -

User Manual / TNK-10000LV-A1
12
Other Protection
Short Circuit Protection
The DC circuit breaker would be triggered by a short circuit
when the battery is on. If the DC circuit breaker does not
operate, the short circuit protection function of the BMS will be
activated automatically to cut off the device’s output.
Self Shutdown When no external loads are present for over 72 hours, the
device will automatically be dormant and go on standby.
The maximum operating current required for the electrical load should be less than the
maximum discharge current capacity of the battery.
Temperature Protection
Under/Over temperature
protection while charging
When the battery’s temperature exceeds the range of 0°C ~ +
55°C during charging, the temperature protection mode will be
activated. The charging of the battery will stop. The protection
mode will be deactivated when it returns to the rated range of
working temperatures.
Under/Over temperature
protection while discharging
When the battery’s temperature exceeds the range of -20°C ~
+ 55°C during discharging, the temperature protection mode
will be activated. The battery will stop supplying power to the
external device. The protection mode will be deactivated when
it returns to the rated range of working temperatures.
- Product Specification -

13
User Manual / TNK-10000LV-A1
Installation and Configuration
Preparations for Installation
This system can only be installed by a person who has been trained in the power-supply system and
possesses sufficient knowledge of the power system.
During installation, the safety regulations listed below should always be followed:
Safety Requirements
All circuits connected to this power system with an external voltage of less than 48V must meet the
SELV requirements defined in IEC60950 standard.
Distribution cable wiring should be reasonable and have the protective measures to avoid touching
on these cables while operating power equipment.
When installing the battery system, the installer must wear the protective items below:
Electrically isolated gloves Safety goggles Safety shoes
Environmental Requirements
Working temperature: -20°C ~ +55°C
Storage temperature: -10°C ~ +55°C
Relative humidity: 5% ~ 85%RH
Elevation: no more than 4000m
Operating environment: Indoor or outdoor installation - the installation point should avoid direct
sunlight and wind, conductive dust and corrosive gas.
The following conditions should be met:
-
Installation locations should be away from corrosive and high humidity environment, such as the sea.
- The surface for product placement shall be flat and level.
- There should be no flammable or explosive materials close to the installation site.
- The optimal ambient temperature is 15°C ~ 30°C.
- Installation and Configuration -
1

User Manual / TNK-10000LV-A1
14
Tools and meters that may be used are shown in the list below.
Screwdriver (Slotted, Phillips)
Torque wrench
Side cutters
Pointed nose pliers
Linesman pliers
Stripping pliers
Electric drill
Multimeter
Clamp current meter
Insulation tape
Temperature meter
Anti-static bracelet
Cable ties
Tape measure
Electrical interface check
For devices that can be connected directly to the battery.
- Ensure that the user equipment, PV equipment or other
power supply equipment has the correct DC interface.
- Ensure that the output/input voltage of the interface meets the
requirements of the battery voltage range on Page 8.
- Ensure that the maximum discharge current of the battery is
higher than the maximum input current of the load. Otherwise,
the battery’s over-current protection mode will be triggered at
full-load operation.
- Ensure that the maximum battery charging current is higher than
the maximum output current from the battery charging device.
If not, the current limiting module in the battery will be triggered
to limit the battery charging current.
Security check
- Firefighting equipment, such as portable dry powder fire
extinguishers, should be placed close to the battery.
- An automatic fire fighting system should be provided in
necessary cases.
- Flammables, explosives and other dangerous materials should be
kept away from the battery.
- Installation and Configuration -
Tools and Data2
Technical Preparation3

15
User Manual / TNK-10000LV-A1
- Installation and Configuration -
When the equipment arrives at the installation site, loading and unloading should be carried out
according to the rules and regulations to prevent the battery from being exposed to sun and rain.
Before unpacking, check the total number of packages against the shipping list attached to each
package.
During unpacking, handle the battery with extra care to protect it from falling, impact, and scratching.
After opening the package, the authorised installer should read the technical documents, check the
products against the packing list, and ensure that all devices are complete and intact. If the internal
packaging is damaged, please contact your local suppler or support centre.
The packing list is given as below:
Battery x 1 Battery bottom bracket x 1
Top mounting bracket x 1 RJ45 Waterproof connector x 2
120Ω CAN resistor x 1
Power cable x 1 pair
connect battery with inverter
Standard communication
cable x 1
User manual x 1 Expansion screw x 9 Positioning cardboard x 2
What’s in the Box4

User Manual / TNK-10000LV-A1
16
Power cable specification
The power cable specification should meet the requirements of maximum charge/discharge current
for each product.
Mounting space and bearing capacity
Ensure sufficient space to install the battery and that the battery rack and bracket meet the load
capacity.
Wiring
Ensure that the power and ground cables are properly wired. All connections should be free of
short-circuits, water and corrosion.
- Installation and Configuration -
Pay attention to the following items before installation:
Engineering Coordination5

17
User Manual / TNK-10000LV-A1
- Installation and Configuration -
Equipment Installation
The surface for battery installation must be able to bear the total weight of the battery. Appropriate
fixings must be used for installation.
Mounting space requirements: in diagram below. Please refer to relevant regulations for further
installation requirements.
Floor installation Wall mounted installation
Step 1
System in off mode
Ensure that the battery is
in off state
Step 2
Mechanical installation
1. Hanger mounting
2. Equipment installation
Step 3
Electrical installation
1. Ground cable connection
2. Electrical installations
3. Inverter connection
4. Communication interface
connection
Floor Installation1
When the battery system is placed directly on the ground, a fixed support must be used to fix the top
of the battery box on the wall.
1. Use the positioning cardboard (provided in the accessory pack) and
ensure the carboard template is positioned level.
2. Mark out the 3 upper fixing location holes for the upper wall bracket
placement.

User Manual / TNK-10000LV-A1
18
3. Drill out the three marked holes with a drill bit. The depth of the hole
must be at least 70mm for use with the supplied M6 fixing expansion bolts.
4. Mount the upper wall bracket to the mounting surface with
appropriate fixings.
5. Apply the M6 expansion bolt to fix the support bracket to the wall by
using the torque of 6NM.
6. Place TNK battery on the bracket you just installed, fixing the support
bracket and the upper part of the battery box with M5 bolts.
Wall Mounted Installation2
The following accessories are required when installing the TNC-10000-LV-A1 on the wall.
Battery bottom bracket x 1 Expansion screw x 6
(if mounting in masonry)
- Installation and Configuration -

19
User Manual / TNK-10000LV-A1
1. Use the positioning cardboard (provided in the accessory package) and
mark the screw hole positions required on the wall.
2. The cardboard must be level while drawing the holes.
3. Based on the position of the marks, drill out the nine marked holes with a
10mm drill bit. The depth of the hole must be at least 70mm for use with the
supplied M6 fixing expansion bolts.
4. Fix the expansion bolt M6 into the bottom of the hole in the wall and
fix the support bracket and battery bottom bracket on the wall with M6
expansion bolts, using a torque of 6NM.
5. Carry or hoist the battery box to the installed battery bottom bracket.
Fix the support bracket and the upper part of the battery box with M5 bolts,
max torque of 6NM.
Next, fix the battery bottom bracket and the bottom part of the battery
box with M5 bolts, max torque of 6NM.
- Installation and Configuration -

User Manual / TNK-10000LV-A1
20
Electrical Installation3
Before connecting the power cables, use a multimeter to measure the cable continuity, short-circuit
condition, and positive and negative ports. Mark them clearly on the cable labels.
Measuring method:
Power cable check
Perform visual inspection of cable connections and insulation for any damage. Perform insulation
resistance and continuity test.
Unit visual inspection
Inspect battery unit to confirm it is free from damage, confirm all electrical connections a free from
damage, debris and moisture.
After visual inspection of the power cable, the positive and negative terminals of the battery should
be connected to the respective positive and negative terminals of the inverter/charger.
1) Connect the battery box to the ground cable
Installers need to prepare M6 OT terminals and ground cables. Ground the battery shell as shown
below. The cross-section of the grounding cable should be at least 6mm², and the bolt-max torque is
6NM.
If there is any question during installation, please contact
your dealer to avoid damage to the equipment.
2) Inverter connection
Multi-Unit Installation:
Module CAN address must be set internally via DIP switch. Before opening the cover to operate, you
must contact Technical Support and provide the product ID. The battery unit ID will be recorded and
authorization to complete the CAN address change may be given. No other operations can be done
except changing the DIP switch mode.
- Installation and Configuration -
Table of contents
Popular Power Supply manuals by other brands

kenall
kenall MEDMASTER MRIPSF-480 installation instructions

BEL
BEL LDN120 Series installation instructions

Extron electronics
Extron electronics PS 1230 installation guide

Rohde & Schwarz
Rohde & Schwarz NGMO1 Service manual

NewMar
NewMar PT-20CE Installation & operation manual

Goobay
Goobay 54799 user manual