Coelbo SWITCHMATIC 2 User manual

1
SWITCHMATIC
SWITCHMATIC 2
ADVANCED SETTINGS
Risk of damaging the pressure assemblies and/or the plant.
Risk by electric shock.
Risk for people and/or objects.

2
SWITCHMATIC - SWITCHMATIC 2
GENERAL
Read carefully the instructions before installing this unit. Verify the tech
nical characteristics of the motor in order to assure the compatibility with
the device.
DESCRIPTION diagram A
SWITCHMATIC is an electronic pressure switch with integrated digital ma
nometer. It manages the start and stop of a singlephase pump up to
2.2kW 3 HP. Cutin and cutout pressures are easily adjustable through
the users control panel.
Wiring is analogous to the traditional electromechanical switch.
It can operate as a diff erential pressure switch and as reverse pressure
switch.
Unit SWITCHMATIC 2 in addition to all the features of the basic SWITCH
MATIC includes instantaneous reading of current drawn. This patented
system controls and manages the overcurrent, dryrun operation and
fastcycling.
Unit SWITCHMATIC 2 in addition to all the features of individual assembly
includes the option to be synchronized to another unit SWITCHMATIC 2
managing and protecting 2 pumps operating in cascade with alternated
starting sequence.
CLASSIFICATION AND TYPE
According to IEC 607301 and EN 607301 this unit is a control sensor
device, electronic, independent assembly, programming type A with action
type 1B microdisconnection. Operating value: I <20% I learned. Pollution
degree 2 clean environment. Rated impulse voltage: cat II / 2500V. Tem
peratures for ball test: enclousure 75 and PCB 125.
OPERATING CHARACTERISTICS diagram C
• Adjustable cutin and cutout pressures.
• Integrated digital pressure gauge with bar and psi indication.
• Inner pressure transmitter.
• Dryrun protection:
• Through minimum adjusted height for basic SWITCHMATIC.
• Through the instantaneous current consumption in case of SWIT
CHMATIC 2.
• Overcurrent protection only SWM2.
• ART Function Automatic Reset Test. When the device has stopped
the pump by the intervention of the dryrunning protection system,
the ART tries, with scheduled basis, to restart the pump in order to
restore the water supply. See “ART. Automatic reset function“. Must be
activated in the step 6 of the ADVANCED MENU Ar1.
• Fast cycling: when the hydropneumatic tank has lost too much air and,
consequently, frequent startstop cycles are produced this alarm is
activated and is delayed the start of the pump. Must be activated in
the step 2 of the BASIC MENU rc1.
• Manual start pushbutton ENTER.
• 3 operation modes: diff erential, reverse and synchronized only
SWM2.
• Control panel with 3digit display, LED indicator lights and push
buttons.
• Voltfree contact for monitoring the alarms displayed in screen origi
nated by irregularities or problems of the system only type SWITCH
MATIC 2A.
• Available settings:
• Standby mode.
• Minimum period between fast cycles.
• Start and stop delay.
TECHNICAL CHARACTERISTICS
• Rated motor power: 0,372,2 kW
• Power supply: ~1 x 110230 V
• Pessure max. 0,8 MPa
• Frequency: 50/60Hz
• Max. current: 16 A
• Protection degree: IP55
• Max water Temperature: 50ºC
• Max environment Temperature: 60ºC
• Cutin range start pressure 0,5÷7 bar
• Cutot range stop pressure 1÷8 bar
• Max. diff erential 7,5 bar
• Minimum diff erential adjustable 0,5÷1,5 bar
• Factory setting start/stop 3/4 bar
• Hydraulic inlet G 1/4” Female
• Net weight without cables 0,3 kg
HYDRAULIC INSTALLATION diagram A
SWITCHMATIC equipment must be threaded to a fi tting G1/4” male
at the pump´s outlet.
Before connecting the SWITCHMATIC verify that the hydraulic system is
properly installed, especially if the hydropneumatic tank is pressurized.
ELECTRIC CONNECTION diagram B
The electric connection must be performed by qualifi ed personal in
compliance with regulation of each country.
Before doing manipulations inside the device, it must be disconnected
from the electric supply.
Wrong connection could spoil the electronic circuit.
The manufacturer declines all responsability in damages caused by
wrong connections.
Check if power supply is between 115230V.
If you have purchased the unit without cables follow diagram B:
• Use cables type H07RNF 3G1 or 3G1,5 with section enough to the
power installed.
• Do the pump connection U, V and .
• Do the power supply connection L1, N and .
• The earth conductor must be longer than the others. It will be the fi rst
one to be mounted during the assembly and the last one to be dis
connected during the dismantling. The earth conductors connec
tions are compulsory!
CONTROL PANEL diagram C
The meanings of the diff erent control panel elements are summarized on
the following tables, where:
• O means lit LED light.
• O means slowfl ashing.
• O means fastfl ashing.
DISPLAY ACTION
OPERATION MODE Is showed on screen instantaneous pressure or instanta
neous current consumption
ADJUSTMENT MODE
Is displayed on screen the adjusted start pressure
blinking.
Is displayed on screen the adjusted stop pressure blin
king.
Is displayed the adjusted rated current blinking only
SW2.
ALARM MODE Is displayed the alarm code
STANDBY MODE Are displayed 3 fl ashing dots
BASIC CONFIGURA
TION MODE Is displayed the sequence of basic confi guration para
meters
ADVANCED CONFI
GURATION MODE Is displayed the sequence of advanced confi guration
parameters
LEDS STATE MEANING
bar
OIt indicates the instantaneous pressure in bar
O It indicates the instantaneous pressure in bar +
pump operating only SW1
psi
OIt indicates the instantaneous pressure in psi
O It indicates the instantaneous pressure in psi +
pump operating only SW1
A
only SW2
OIt indicates the instantaneous current consumption
in Ampere units
O Pump ON
START O Is displayed the start pressure
O Adjusting start pressure
STOP O Is displayed the stop pressure
O Adjusting stop pressure
O Ratifi ed dryrunning or overload alarms
O Dryrunning alarm performing ART or overload
alarm preforming any of the 4 restore attempts
O Fastcycling alarm

3
PBUTTON TOUCH ACTION
click!
From state ON: unit OFF.
From state OFF: the pump starts and keeps opera
ting until reaching Pstop.
From any confi guration MENU: the parameter
value is accepted.
HOLD
DOWN
From state ON: unit OFF.
From state OFF: the pump starts and keeps opera
ting until the pushbutton is released.
click! Pstart is displayed on the screen for 3 seconds.
3” Pstart adjustment mode.
click! Pstop is displayed on the screen for 3 seconds.
3” Pstop adjustment mode.
click!
Is displayed on the screen instantaneous current
consumption.
If it is already displayed then we switch to instanta
neous pressure view.
3” Rated current adjustment.
STARTUP diagram C
Before starting the device please read the previous sections, espe
cially “Hydraulic Installation” and “Electrical connection”.
Follow next steps:
1. Start the device by pressing .
2. Only for type SW2 set the pump rated current intensity value.
Press during 3 seconds.
The current intensity value is displayed on screen, LED A lights up and
display is fl ashing.
By mean of and is adjusted the rated current refl ected in the
characteristics plate of the motor. See Note 1.
Press for validation.
3. Set the cutin start pressure:
Press during 3 seconds.
The start pressure value is displayed on screen, LED START lights up
and display is fl ashing.
By mean of and is adjusted the start pressure from 0,5 to 7
bar.
Press for validation.
4. Set the cutout stop pressure:
Press during 3 seconds.
The stop pressure value is displayed on screen, LED STOP lights up
and display is fl ashing.
By mean of and is adjusted the stop pressure from 1 to 8 bar.
Press for validation.
5. The unit is ready to operate but more optional adjustments can be set
through basic and advanced MENUS. See the next chapter.
Remark 1: it is important to introduce exactly the rated current
specifi ed on the nameplate of the pump.
BASIC MENU + diagram C
Press simultaneously + during 5 seconds.
By mean of or the values can be changed.
Press for validation.
The parameters sequence is:
it TYPE SYSTEM REACTION FACTORY
SETTING
1 BAR P We can select the pressure units displayed
beetween bar and psi. bar
2 rc0 rc1 Fastcycling alarm activated rc1 or disabled
rc0. rc0
3 r.01 r.99
Only if fastcycling alarm has been activated in
the previous step rc1. It can be choosed the
maximum time period between 3 consecuti
ve starts that will be considered fast cycling
between 1 sec. and 99 sec.
5 se
conds
4 Sb0 Sb1 Standby mode activated Sb1, for low power
consumption, or disabled Sb0. Sb0
ADVANCED MENU + +
Press simultaneously + + during 5 seconds.
By mean of or the values can be changed.
Press for validation.
The parameters sequence is:
it TYPE SYSTEM REACTION FACTORY
SETTING
1 nc no Select the operation MODE as a conventio
nal pressure switch nc = normally closed or
reverse no = normally open. nc
2 E00 E01/02
Only Switchmatic2. Select the operation
mode Individual E00 or Master/Slave E01/
E02 in case of be assembled in groups of
two pumps.
E00
3 d.05 d.1 Only Switchmatic 2. Sets the minimum
diff erential between Pstart 1 and Pstart 2
and/or Pstop 1 and Pstop 2. d.05
4 ct0 ct9 Sets a time delay between 0 and 9 seconds
to the start is not available in synchronized
operation mode. ct0
5 dt0 dt9 Sets a time delay between 0 and 9 seconds
to the stop. dt0
6 Ar0 Ar1 Activation of the automatic restore system
ART Ar1 o disable Ar0. Ar0
7 d0.5 d1.5 Sets the minimum diff erential between
Pstart and Pstop values between 0.5 bar 7,0
psi and 1.5 bar 21.7 psi.
0,5 bar
7,0psi
8 P0.0 Px.x
It allows setting a minimum operating
pressure under which the device would
determine dryrunning operation. It is very
usefull in the basic model SWITCHMATIC
where there is no reading of current intensi
ty drawn. See Note 2.
0 bar
0 psi
9 t05 t99
Set the time period between 5 and 99
seconds below the minimum operating
pressure that will be considered a dry
running operation.
20”
10 c10 c30 It allows setting a % of nominal current
above which the device will activate the
overcurrent protection. c20
11 dr0 dr1
Only for SWITCHMATIC 2. It allows the
activation of accurate dryrunning detection
DR1 or to disable it DR0. See chapter
ACCURATE DRYRUNNING DETECTION.
dr0
Remark 2:
Basic SWITCHMATIC can only detect dryrunning operation
through the minimum pressure. This means that plumber must
determine the water column of the installation, the start pressu
re of the pump and place the minimum pressure below the start
pressure.
It can also occur that pumping system is running out of its curve so
that the pump is unable to provide the minimum pressure because
the fl ow requirement is excessive. In this case SWITCHMATIC would
activate a false dryrunning alarm.
If these concepts are not clear, it is preferable not confi gure this
protection or install the SWITCHMATIC 2 with accurate and easy
setting of dryrun detection.

4
SYNCHRONISATION ONLY FOR SWITCHMATIC 2
SWITCHMATIC 2 can be synchronized to another unit SWITCHMATIC 2
managing and protecting 2 pumps operating in cascade with alternated
starting sequence. Next steps must be followed:
1. SET identical cutin and cutout pressures in both units.
2. GO TO ADVANCED MENU: + +
In step 2: select E01 in a unit this one will be the master and select E02
in the other unit this one will be the slave.
In step 3: select identical parameters of diff erential d.XX.
3. Press repeatedly until exit the ADVANCED MENU.
4. Press in order to disable the units. Is displayed “OFF”.
5. Press again in both units in order to activate the synchronization.
Remark 3: after 10 cycles the unit confi gured E01 will display pressu
re and the unit confi gured E02 will display current in Amps.
ACCURATE DRYRUNNING DETECTION diagram C
In the SWITCHMATIC 2 model it is enough to set the rated current of the
pump in order to activate the overcurrent and dryrunning protection.
However, the accuracy of dryrunning detection can be improved by the
activation of DR1 parameter in the ADVANCED MENU. The following steps
must be followed:
1. Drain the hydraulic installation and verify that the hydropneumatic tank
is infl ated to the required pressure.
2. Go to the ADVANCED MENU:
Press simultaneously + + during 5 seconds.
Press 7 consecutive times to accept and go to the next step until
reaching dr0.
Using , set dr1.
3. Press and close all the valves.
4. The pump will start, will fi ll the installation and will stop at the cutout
pressure.
5. Now, SWITCHMATIC 2 knows the current consumption curve of the
pump.
If you install a new pump this process should be repeated.
If you enter the CURRENT INTENSITY MENU by pressing for 3 seconds
all this process is invalidated because is predominant the rated current
manually introduced.
PRESSURE SENSOR CALIBRATION
In case of wrong lecture of the pressure sensor it can be adjusted again.
For the pressure sensor calibration is necessary to have a pressure gauge
in the installation. Proceed following next steps:
ZERO REGULATION
1. Open the taps living the hydraulic net without pressure.
2. Press simultaneously the buttons and until the display show
0.0 fl ashing.
3. Press to validate.
FULL SCALE
1. Start the pump until cutout of the pressure switch.
2. Press simultaneously the buttons and till the display fl ashes
with a fi gure.
3. Adjust the pressure with the arrows pushbuttons to get the pressure
desired.
4. Press to validate.
Remark 4: pressure sensor decalibration should not be a normal
event. If it is frequently repeated contact the technical service.
WARNINGS AND ALARMS
COD. DESCRIPTION SYSTEM REACTION
A01
O
DRYRUNNING
Only for
SWITCHMATIC 2
When is detected a dryrun operation the
pump is automatically stopped. By mean
of ENTER the normal operation can be
manually restored.
O
After the activation of the dryrunning
alarm if the Automatic system reset ART
is enabled, a fi rst attempt at 5 minutes and
then an attempt every 30 minutes for 24
hours is performed in order to restore the
normal operation. This alarm can also be
reset manually with the ENTER pushbut
ton. If the alarm persists after 24 h we fi nd
a defi nitive alarm.
A11 O
DRYRUNNING
BY MINIMUM
PRESSURE
Is displayed during normal operation if the
pressure is below the minimum pressure
Px.x previously set during a period
txx also previously set in the ADVAN
CED MENU.
If at any time the pressure exceeds the mi
nimum pressure, the operation is restored
automatically and the alarm is cleared.
Normal operation can also be restored
manually by pressing ENTER.
A02
O
OVERLOAD
Overcurrent alarm is activated when the
nominal pump current is exceeded.
4 automatic reset attempts prior to the
fi nal alarm are performed.
During the attempts display will show
current.
Normal operation can also be restored
manually by pressing ENTER.
O
A04 O FAST CYCLING
This alarm can be unabled or disabled in
the BASIC MENU. The alarm is activated
when 3 consecutive cycles occur in a range
lower than the set time. This alarm does
not stop the normal operation but are
added 5 seconds to the start delay in order
to protect the electric pump.
To reset the normal operation press ENTER.
A05 O
DAMAGED PRES
SURE TRANS
MITTER
CONTACT WITH YOUR SUPPLIER.
EC STAMENT OF COMPLIANCE
COELBO CONTROL SYSTEM, S.L.
States, on our own responsibility, that all materials here with related com
ply with the following European Directives:
2014/35/EU.
2014/30/EU.
2014/65/EU.
Name: SWITCHMATIC
SWITCHMATIC 2
Standards : EN6073026, EN607301, EN6100061, EN6100063, IEC
607301, IEC6073026
F. Roldán Cazorla
Director Técnico
04/05/2016
COELBO CONTROL SYSTEM, S.L.
Ctr de Rubí, 288 P.I. Can Guitard
08228 Terrassa BARCELONA SPAIN

5
DIAGRAM A
INDIVIDUAL
GROUP (ONLY SW2)

6
DIAGRAM B
DIAGRAM C
21/11/17
DIMENSIONS